Plan Review Details - Permit 16100587
Plan Review Stops For Permit 16100587
Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-02-20 Cont ID  
Sent By mgonzale Date 2017-02-20 Time   Rev Time 1.00
Received By mgonzale Date 2017-02-20 Time   Sent To I
Notes
2017-02-20 14:44:17ADDRESS MECHANICAL DISCIPLINE COMMENTS
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-10-27 Cont ID  
Sent By scaldero Date 2016-10-27 Time 15:22 Rev Time 0.00
Received By scaldero Date 2016-10-27 Time 14:44 Sent To M
Notes
2016-10-27 15:22:00PERMIT # 16100587
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PASSED PROVISO
  
 PROVISO COMMENTS TO BE VERIFIED AND CONFIRMED AT THE
 TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 COMMENTS WILL RESULT IN A FAILED INSPECTION.
  
 1) ENSURE THAT THE FIRE LINE MANUFACTURER?S SPECS ARE
 ON-SITE FOR THE FIRE INSPECTOR?S REVIEW AT THE TIME OF
 THE INSPECTION. CLOSE ATTENTION SHALL BE OBSERVED FOR
 THE PROPER TORQUEING OF RESTRAINT BOLTS.
 NFPA 24
 10.7: REQUIREMENTS FOR LAYING PIPE
 10.7.1: PIPES, VALVES, HYDRANTS, GASKETS, AND FITTINGS
 SHALL BE INSPECTED PRIOR TO INSTALLATION (SEE FIGURE
 10.10.1).
 10.7.2: THE TORQUEING OF BOLTED JOINTS SHALL BE
 CHECKED.
  
 2) DO NOT COVER THE FIRE LINE PRIOR TO THE FIRE
 INSPECTION.
 NFPA 24
 10.3.5: PIPE JOINT ASSEMBLY
 10.3.5.1: JOINTS SHALL BE ASSEMBLED BY PERSONS FAMILIAR
 WITH THE PARTICULAR MATERIALS BEING USED AND IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTION AND
 SPECIFICATIONS.
 10.3.5.2: ALL BOLTED JOINT ACCESSORIES SHALL BE CLEANED
 AND THOROUGHLY COATED WITH ASPHALT OR OTHER
 CORROSION-RETARDING MATERIAL, AFTER INSTALLATION.
  
 10.10.2.2.4*: THE TRENCH SHALL BE BACKFILLED BETWEEN
 JOINTS BEFORE TESTING TO PREVENT MOVEMENT OF PIPE.
  
 3) TEST THE FIRE LINE PER NFPA 24
 10.10: TESTING AND ACCEPTANCE
 10.10.1: APPROVAL OF UNDERGROUND PIPING. THE INSTALLING
 CONTRACTOR SHALL BE RESPONSIBLE FOR THE FOLLOWING:
 (1) NOTIFYING THE AHJ AND THE OWNER?S REPRESENTATIVE OF
 THE TIME AND DATE TESTING IS TO BE PERFORMED.
 (2) PERFORMING ALL REQUIRED ACCEPTANCE TESTS.
 (3) COMPLETING AND SIGNING THE CONTRACTOR?S MATERIAL
 AND TEST CERTIFICATE?S, SHOWN IN FIGURE 10.10.1.
  
 10.10.2.2: HYDROSTATIC TEST
 10.10.2.2.1*: ALL PIPING AND ATTACHED APPURTENANCES
 SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE
 HYDROSTATICALLY TESTED AT 200 PSI (13.8 BAR) OR 50 PSI
 (3.5 BAR) IN EXCESS OF THE SYSTEM WORKING PRESSURE,
 WHICHEVER IS GREATER, AND SHALL MAINTAIN THAT PRESSURE
 FOR 2 HOURS.
 10.10.2.2.2: PRESSURE LOSS SHALL BE DETERMINED BY A
 DROP IN GAUGE PRESSURE OR VISUAL LEAKAGE.
 10.10.2.2.3: THE TEST PRESSURE SHALL BE READ FROM ONE
 OF THE FOLLOWING, LOCATED AT THE LOWEST ELEVATION OF
 THE SYSTEM BEING TESTED:
 (1) A GAUGE LOCATED AT ONE OF THE HYDRANT OUTLETS
 (2) A GAUGE LOCATED AT THE LOWEST POINT WHERE NO
 HYDRANTS ARE PROVIDED
 10.10.2.2.4*: THE TRENCH SHALL BE BACKFILLED BETWEEN
 JOINTS BEFORE TESTING TO PREVENT MOVEMENT OF PIPE.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-21 Cont ID  
Sent By cpuell Date 2017-02-21 Time 12:50 Rev Time 0.00
Received By cpuell Date 2016-10-21 Time 12:51 Sent To  
Notes
2016-10-24 12:52:06ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-07 Cont ID  
Sent By ccole Date 2016-11-07 Time 08:26 Rev Time 0.00
Received By ccole Date 2016-11-07 Time 08:26 Sent To ENG
Notes
2016-11-07 08:35:261ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100587
 11/7/16
  
 1) THE PLANS MUST BEAR THE SIGNATURE AND SEAL OF THE
 ENGINEER RESPONSIBLE FOR THE DESIGN- SEE SECTION 107.1
 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE, SECTION
 471.005 FLORIDA STATUTES, AND SECTION 61G15-23.002
 FLORIDA ADMINSTRATIVE CODE.
  
 2) UNDERGROUND UTILITY CONTRACTORS BY LICENSURE ARE NOT
 PERMITTED TO INSTALL UNDERGROUND FIRE LINES- SEE
 FLORIDA STATUTES SECTION 489.105 (N), AND SECTION
 633.102 FOR LICENSURE INFORMATION.
  
 3) PLEASE PERMANENTLY BIND THE LOOSE PLANS SHEETS
 TOGETHER, AND PROVIDE A COVER SHEET WITH CODE DATA
 INFORMATION AND A PLAN INDEX- SECTION 107.2 WPB
 AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  