Plan Review Details - Permit 16100586
Plan Review Stops For Permit 16100586
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-02 Cont ID  
Sent By tklarge Date 2016-11-02 Time 06:30 Rev Time 0.00
Received By tklarge Date 2016-10-31 Time 09:10 Sent To  
Notes
2016-11-01 09:11:12RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-22 Cont ID  
Sent By tklarge Date 2016-10-22 Time 04:59 Rev Time 0.00
Received By tklarge Date 2016-10-20 Time 10:58 Sent To  
Notes
2016-10-21 10:58:20PLUMB -$5000

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-11-02 Cont ID  
Sent By tklarge Date 2016-11-02 Time 06:29 Rev Time 0.00
Received By tklarge Date 2016-11-02 Time 06:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-10-22 Cont ID  
Sent By tklarge Date 2016-10-22 Time 04:59 Rev Time 0.00
Received By tklarge Date 2016-10-22 Time 04:53 Sent To  
Notes
2016-10-22 04:59:061) CLEARLY SHOW THE SCOPE OF WORK ON THE SUBMITTED
 PLANS. THE PLANS SHOW AN ELECTRIC VALVE AND A LATERAL
 LINE AND THAT IS ALL. WHAT IS THE SIZE OF THE LINE,
 WHERE ARE THE HEADS LOCATED, IS THERE AN EXISTING
 BACKFLOW PREVENTER AND RAIN SENSOR ON THIS SYSTEM, WHAT
 IS THE SOURCE OF WATER IF NOT CITY WATER ETC. IF SO,
 PROVIDE THE LOCATION OF THE BACKFLOW DEVICE AND THE
 RAIN SENSOR AND CONTROLLER. ETC. THESE PLANS ARE
 EXTREMELY VAGUE. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  