Plan Review Stops For Permit 16100579 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2017-02-02 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-02-02 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-02-02 |
Time |
14:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2017-01-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-01-09 |
Time |
08:52 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-01-05 |
Time |
13:42 |
Sent To |
|
|
Notes |
2017-01-09 08:53:05 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 2ND REVIEW | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PLAN PG. A-1 INDICATES TWO DIFFERENT EXISTING | | ELEVATIONS. PLEASE CLARIFY. | | 2. PLAN PG. A-1 LEVEL OF WORK STATES "THERE IS NO WORK | | BEING DONE OTHER THAN PAINTING AND MINOR REPAIRS". | | MODIFY STATEMENT TO REFLECT ALL PROPOSED WORK PER FBC | | 2014 EXISTING BUILDING. | | 3. ENERGY SUBMITTAL DOES NOT REFLECT PROPOSED AREA OF | | WORK. AREA CALCULATIONS PER PLAN PG. A-1 STATES | | CONVERTED GARAGE AS 270 SQ. FT. ENERGY SUBMITTAL USES | | 486 SQ. FT. PLEASE CLARIFY. | | 4. PROVIDE DETAILS FOR OHD IN-FILL AND EXISTING | | EXTERIOR WALLS AND CEILING. INDICATE REQUIRED | | INSULATION FOR WALLS AND CEILING. THE BUILDING THERMAL | | ENVELOPE SHALL MEET THE REQUIREMENTS OF TABLE R402.1.1 | | BASED ON THE CLIMATE ZONE SPECIFIED IN CHAPTER 3. | | 5. A/C COMPRESSOR ENCROACHES ON EMERGENCY ESCAPE & | | RESCUE OPENING PER FBC R310. | | 6. CERTIFICATION LETTER BY DESIGNER OF RECORD JAMES | | PHILIP DRAGO, AIA ONLY ADDRESSES THE PLUMBING AND | | ELECTRICAL WORK COMPLETED FOR THE NEW MASTER SUITE. | | 7. PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE | | PREVIOUSLY COMPLETED WORK TO BE MADE ACCESSIBLE AND | | OPEN FOR INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION | | FOR ALL CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO | | FBC 110 & FBC 117. | | THE BUILDING OFFICIAL MAY REQUIRE TESTS OR TEST REPORTS | | AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE TO BE MADE | | AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN APPROVED | | TESTING LABORATORY OR OTHER APPROVED AGENCY. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED AND MARK VOID. | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-10-21 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-10-21 |
Time |
15:25 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-10-21 |
Time |
15:25 |
Sent To |
E |
|
Notes |
2016-10-21 15:42:56 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER ? PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | | | ILLEGAL GARAGE CONVERSION - ALL WORK PER CITY CODES | | SUBJECT TO FIELD INSPECTOR'S APPROVAL | | | | 1. MECHANICAL PERMIT AND PLAN REVIEW REQUIRED. | | 2. ELECTRICAL PERMIT AND PLAN REVIEW REQUIRED. | | 3. PLUMBING PERMIT AND PLAN REVIEW REQUIRED. | | 4. PALM BEACH COUNTY IMPACT FEES REQUIRED. | | 5. PROVIDE ENERGY SUBMITTAL. | | 6. PROVIDE FRAMING DETAILS FOR OVERHEAD DOOR IN-FILL. | | | | IMPACT FEES | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 | | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO | | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | COMPLIANCE BY SECTION 405. | | | | R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD | | (MANDATORY). | | THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY | | PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND | | CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT | | BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY. | | FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)] | | REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN | | ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND | | NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD | | CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE | | LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A | | DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT | | THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE | | BUILDER ACCURATELY REFLECTS THE PLANS AND | | SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE | | FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE | | FOUND IN APPENDIX C. | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | DESIGN. (SEE ALSO SECTION 107.3.5). | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2017-01-25 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2017-01-25 |
Time |
09:15 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2017-01-19 |
Time |
10:32 |
Sent To |
|
|
Notes |
2017-01-25 09:17:49 | 3RD REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | - PASSED WITH THE FOLLOWING PROVISO | | | | 1] NOTE INDICATES SMOKE ALARMS PER FBC 2010, PLEASE | | ADJUST TO FBC-R 2014 SECTIONS 314 & 315. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2017-01-04 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2017-01-04 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2017-01-04 |
Time |
16:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-10-26 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-10-26 |
Time |
16:22 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-10-26 |
Time |
15:03 |
Sent To |
M |
|
Notes |
2016-10-26 16:22:20 | 1ST REVISION 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] CLEARLY DEFINE THE SCOPE OF WORK TO A ALTERATION | | LEVEL 2 PER THE EXISTING FBC 2014 SECTION 504. | | | | 2] PROVIDE THE EXISTING ELECTRIC SERVICE RISER WITH | | WIRE AND CONDUIT SIZES, AND GROUNDING DETAIL. SHOW | | COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES WITH | | MATCHING CIRCUITS ON FLOOR PLAN. FBC- 107.3.5.3 | | | | 3] MISSING A RECEPTACLE OUTLET PER SPACING REQUIREMENTS | | IN THE MASTER BATH WALL FACING THE MASTER SUITE. FBC-R | | SECTION E3901.1.2.1 | | | | 4] ADD A GENERAL ELECTRICAL NOTE FOR TAMPER RESISTANT | | RECEPTACLES ACCORDING WITH FBC-R SECTION E4002.14 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2017-02-16 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-02-16 |
Time |
14:39 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-02-14 |
Time |
13:09 |
Sent To |
|
|
Notes |
2017-02-14 13:09:57 | IMPACT FEES ROUTED TO CTHROOP |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2017-02-02 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-02-02 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-01-17 |
Time |
13:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2017-01-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-01-09 |
Time |
08:52 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-12-14 |
Time |
10:01 |
Sent To |
|
|
Notes |
2017-01-03 18:13:01 | R11 | 2016-12-16 10:01:43 | R11 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-11-02 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2016-11-02 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2016-10-20 |
Time |
16:42 |
Sent To |
|
|
Notes |
2016-10-26 17:55:52 | ROUTED TO GEORGE JOHNSON 10/26/2016 - JORGE V. | 2016-10-20 16:42:13 | REVISION ROUTED TO MVALDES |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
4 |
Status |
P |
Date |
2017-02-16 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-02-16 |
Time |
14:39 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-02-16 |
Time |
14:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
3 |
Status |
F |
Date |
2017-02-02 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-02-02 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-02-02 |
Time |
14:18 |
Sent To |
|
|
Notes |
2017-02-02 14:21:17 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 3RD REVIEW | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
F |
Date |
2017-01-06 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-01-06 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-01-06 |
Time |
15:49 |
Sent To |
|
|
Notes |
2017-01-06 15:56:36 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 2ND REVIEW | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2016-10-21 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-10-21 |
Time |
15:54 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-10-21 |
Time |
15:54 |
Sent To |
|
|
Notes |
2016-10-21 15:55:39 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER ? PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | | | IMPACT FEES | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2017-01-03 |
|
|
Cont ID |
|
Sent By |
jvalido |
Date |
2017-01-03 |
Time |
18:09 |
Rev Time |
0.00 |
Received By |
jvalido |
Date |
2017-01-03 |
Time |
18:08 |
Sent To |
|
|
Notes |
2017-01-03 18:09:09 | REFER TO PERMIT #16120628. PERMIT HAS BEEN APPROVED BY | | HAROLD MOESER. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-10-26 |
Time |
17:22 |
Rev Time |
0.00 |
Received By |
jvalido |
Date |
2016-10-26 |
Time |
16:10 |
Sent To |
|
|
Notes |
2016-10-26 17:17:32 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH | | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND | | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS | | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH | | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR | | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC | | MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS | | OF FLORIDA STATUTES | | | | (1) PROVIDE MECHANICAL PLANS AS PER 107.2.1.4. (SEE | | ABOVE). | | (2) DESIGNATE EXISTING AND NEW DUCTWORK, IF APPLICABLE. | | (3) PROVIDE EQUIPMENT SCHEDULE AS PER R403.6.1 | | (4) SHOW LOCATION OF CONDENSERS. | | (5) PROVIDE CONDENSER TIE DOWN DETAIL AS PER FBC 2014 | | (6) PROVIDE EXHAUST IN ALL BATHROOMS. | | (7) PROVIDE RETURN FROM ALL BEDROOMS. | | | | FLORIDA ENERGY CODE FBC 2014 | | | | R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED | | IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT | | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR | | OTHER APPROVED HEATING AND COOLING CALCULATION | | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE | | DIRECTIONAL ORIENTATION OF THE BUILDING. THE | | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR | | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH | | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN | | CONDITIONS DESCRIBED IN | | SECTION R302.1. THIS CODE DOES NOT ALLOW DESIGNER | | SAFETY FACTORS, PROVISIONS FOR FUTURE EXPANSION OR | | OTHER FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM | | SIZING CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY | | LOCAL INTERMITTENT MECHANICAL VENTILATION SUCH AS | | STANDARD KITCHEN AND BATHROOM EXHAUST SYSTEMS. | | | | (8) PROVIDE HEAT LOAD CALCULATIONS AS PER R403.6.1 (SEE | | ABOVE). SUMMARIES ARE NOT ACCEPTABLE. | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2017-02-02 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-02-02 |
Time |
13:28 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-02-02 |
Time |
13:28 |
Sent To |
|
|
Notes |
2017-02-02 13:28:53 | PLUMBING PROVISO: | | THE FOLLOWING SHALL BE PROVIDED FOR INSPECTIONS | | 1. PROVIDE AN APPROVED PLUMBING RISER DIAGRAM FOR NEW | | BATHROOM. PER WPB AMEND TO FBC 107.3.5.3(11) | | 2. THE PLUMBING FOR NEW MASTER BATHROOM SHALL BE TESTED | | AND THE UNDERGROUND PIPING IS TO BE INSPECTED VIA VIDEO | | CAMERA, PROVIDE COPY OF VIDEO. SHOWER PAN SHALL BE | | EXPOSED AND TESTED PER FBC RES SECTION P2503 INSPECTION | | AND TESTS | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2017-01-05 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-01-05 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-01-05 |
Time |
16:07 |
Sent To |
|
|
Notes |
2017-01-05 15:56:34 | 2ND REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: 2ND REQEST HAS NOT COMPLIED | | | | 1. PROVIDE PLUMBING RISER DIAGRAM FOR NEW BATHROOM. PER | | WPB AMEND TO FBC 107.3.5.3(11) | | | | 3. THE PLUMBING FOR NEW MASTER BATHROOM SHALL BE TESTED | | AND THE UNDERGROUND PIPING IS TO BE INSPECTED VIA VIDEO | | CAMERA. PER FBC RES SECTION P2503 INSPECTION AND TESTS | | PLEASE PLACE NOTE ON PLAN INDICATING THIS. | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2016-10-27 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-10-27 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-10-27 |
Time |
09:22 |
Sent To |
|
|
Notes |
2016-10-27 09:53:49 | 1ST REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1. PROVIDE PLUMBING RISER DIAGRAM FOR NEW BATHROOM. PER | | WPB AMEND TO FBC 107.3.5.3(11) | | | | 3. THE PLUMBING FOR NEW MASTER BATHROOM SHALL BE TESTED | | AND THE UNDERGROUND PIPING IS TO BE INSPECTED VIA VIDEO | | CAMERA. PER FBC RES SECTION P2503 INSPECTION AND TESTS | | PLEASE PLACE NOTE ON PLAN INDICATING THIS. | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2017-01-26 |
|
|
Cont ID |
|
Sent By |
njwira |
Date |
2017-01-26 |
Time |
15:21 |
Rev Time |
0.00 |
Received By |
njwira |
Date |
2017-01-26 |
Time |
14:10 |
Sent To |
|
|
Notes |
2017-01-26 15:23:17 | 1/26/17- PASSED | | | | CONVERTING GARAGE INTO A BATHROOM AND MASTER BEDROOM | | MECHANICAL EQUIPMENT HAS A 3FT. SETBACK MEETING THE | | 1FT. REQUIREMENT | | ONE KITCHEN ONLY | | NO TREES BEING MOVED | | | | PLEASE CONTACT | | NATHAN WIRA | | [email protected] | | (561)822-1442 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2016-12-21 |
|
|
Cont ID |
|
Sent By |
njwira |
Date |
2016-12-21 |
Time |
19:17 |
Rev Time |
0.00 |
Received By |
njwira |
Date |
2016-12-21 |
Time |
17:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2016-11-01 |
|
|
Cont ID |
|
Sent By |
njwira |
Date |
2016-11-01 |
Time |
16:54 |
Rev Time |
0.00 |
Received By |
njwira |
Date |
2016-10-27 |
Time |
15:52 |
Sent To |
I |
|
Notes |
2016-11-01 16:55:04 | MEETS HEIGHT REQUIREMENT | | NOT ADDING A NEW KITCHEN STILL ONE UNIT | | | | PLEASE CONTACT | | NATHAN WIRA | | [email protected] | | (561)822-1442 | | |
|
|