Plan Review Details - Permit 16100579
Plan Review Stops For Permit 16100579
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-02-02 Cont ID  
Sent By cthroop Date 2017-02-02 Time 14:21 Rev Time 0.00
Received By cthroop Date 2017-02-02 Time 14:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-01-09 Cont ID  
Sent By cthroop Date 2017-01-09 Time 08:52 Rev Time 0.00
Received By cthroop Date 2017-01-05 Time 13:42 Sent To  
Notes
2017-01-09 08:53:05BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLAN PG. A-1 INDICATES TWO DIFFERENT EXISTING
 ELEVATIONS. PLEASE CLARIFY.
 2. PLAN PG. A-1 LEVEL OF WORK STATES "THERE IS NO WORK
 BEING DONE OTHER THAN PAINTING AND MINOR REPAIRS".
 MODIFY STATEMENT TO REFLECT ALL PROPOSED WORK PER FBC
 2014 EXISTING BUILDING.
 3. ENERGY SUBMITTAL DOES NOT REFLECT PROPOSED AREA OF
 WORK. AREA CALCULATIONS PER PLAN PG. A-1 STATES
 CONVERTED GARAGE AS 270 SQ. FT. ENERGY SUBMITTAL USES
 486 SQ. FT. PLEASE CLARIFY.
 4. PROVIDE DETAILS FOR OHD IN-FILL AND EXISTING
 EXTERIOR WALLS AND CEILING. INDICATE REQUIRED
 INSULATION FOR WALLS AND CEILING. THE BUILDING THERMAL
 ENVELOPE SHALL MEET THE REQUIREMENTS OF TABLE R402.1.1
 BASED ON THE CLIMATE ZONE SPECIFIED IN CHAPTER 3.
 5. A/C COMPRESSOR ENCROACHES ON EMERGENCY ESCAPE &
 RESCUE OPENING PER FBC R310.
 6. CERTIFICATION LETTER BY DESIGNER OF RECORD JAMES
 PHILIP DRAGO, AIA ONLY ADDRESSES THE PLUMBING AND
 ELECTRICAL WORK COMPLETED FOR THE NEW MASTER SUITE.
 7. PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE
 PREVIOUSLY COMPLETED WORK TO BE MADE ACCESSIBLE AND
 OPEN FOR INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION
 FOR ALL CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO
 FBC 110 & FBC 117.
 THE BUILDING OFFICIAL MAY REQUIRE TESTS OR TEST REPORTS
 AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE TO BE MADE
 AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN APPROVED
 TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-21 Cont ID  
Sent By cthroop Date 2016-10-21 Time 15:25 Rev Time 0.00
Received By cthroop Date 2016-10-21 Time 15:25 Sent To E
Notes
2016-10-21 15:42:56BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 ILLEGAL GARAGE CONVERSION - ALL WORK PER CITY CODES
 SUBJECT TO FIELD INSPECTOR'S APPROVAL
  
 1. MECHANICAL PERMIT AND PLAN REVIEW REQUIRED.
 2. ELECTRICAL PERMIT AND PLAN REVIEW REQUIRED.
 3. PLUMBING PERMIT AND PLAN REVIEW REQUIRED.
 4. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 5. PROVIDE ENERGY SUBMITTAL.
 6. PROVIDE FRAMING DETAILS FOR OVERHEAD DOOR IN-FILL.
  
 IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-01-25 Cont ID  
Sent By mvaldes Date 2017-01-25 Time 09:15 Rev Time 0.00
Received By mvaldes Date 2017-01-19 Time 10:32 Sent To  
Notes
2017-01-25 09:17:493RD REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - PASSED WITH THE FOLLOWING PROVISO
  
 1] NOTE INDICATES SMOKE ALARMS PER FBC 2010, PLEASE
 ADJUST TO FBC-R 2014 SECTIONS 314 & 315.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-04 Cont ID  
Sent By mvaldes Date 2017-01-04 Time 16:49 Rev Time 0.00
Received By mvaldes Date 2017-01-04 Time 16:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-26 Cont ID  
Sent By mvaldes Date 2016-10-26 Time 16:22 Rev Time 0.00
Received By mvaldes Date 2016-10-26 Time 15:03 Sent To M
Notes
2016-10-26 16:22:201ST REVISION 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] CLEARLY DEFINE THE SCOPE OF WORK TO A ALTERATION
 LEVEL 2 PER THE EXISTING FBC 2014 SECTION 504.
  
 2] PROVIDE THE EXISTING ELECTRIC SERVICE RISER WITH
 WIRE AND CONDUIT SIZES, AND GROUNDING DETAIL. SHOW
 COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES WITH
 MATCHING CIRCUITS ON FLOOR PLAN. FBC- 107.3.5.3
  
 3] MISSING A RECEPTACLE OUTLET PER SPACING REQUIREMENTS
 IN THE MASTER BATH WALL FACING THE MASTER SUITE. FBC-R
 SECTION E3901.1.2.1
  
 4] ADD A GENERAL ELECTRICAL NOTE FOR TAMPER RESISTANT
 RECEPTACLES ACCORDING WITH FBC-R SECTION E4002.14

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-02-16 Cont ID  
Sent By cthroop Date 2017-02-16 Time 14:39 Rev Time 0.00
Received By cthroop Date 2017-02-14 Time 13:09 Sent To  
Notes
2017-02-14 13:09:57IMPACT FEES ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-02 Cont ID  
Sent By cthroop Date 2017-02-02 Time 14:18 Rev Time 0.00
Received By cthroop Date 2017-01-17 Time 13:26 Sent To  
Notes
2017-01-18 13:26:55R11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-09 Cont ID  
Sent By cthroop Date 2017-01-09 Time 08:52 Rev Time 0.00
Received By cthroop Date 2016-12-14 Time 10:01 Sent To  
Notes
2017-01-03 18:13:01R11
2016-12-16 10:01:43R11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-02 Cont ID  
Sent By cpuell Date 2016-11-02 Time 14:44 Rev Time 0.00
Received By cpuell Date 2016-10-20 Time 16:42 Sent To  
Notes
2016-10-26 17:55:52ROUTED TO GEORGE JOHNSON 10/26/2016 - JORGE V.
2016-10-20 16:42:13REVISION ROUTED TO MVALDES

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2017-02-16 Cont ID  
Sent By cthroop Date 2017-02-16 Time 14:39 Rev Time 0.00
Received By cthroop Date 2017-02-16 Time 14:39 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-02-02 Cont ID  
Sent By cthroop Date 2017-02-02 Time 14:18 Rev Time 0.00
Received By cthroop Date 2017-02-02 Time 14:18 Sent To  
Notes
2017-02-02 14:21:17BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 3RD REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-01-06 Cont ID  
Sent By cthroop Date 2017-01-06 Time 15:49 Rev Time 0.00
Received By cthroop Date 2017-01-06 Time 15:49 Sent To  
Notes
2017-01-06 15:56:36BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-10-21 Cont ID  
Sent By cthroop Date 2016-10-21 Time 15:54 Rev Time 0.00
Received By cthroop Date 2016-10-21 Time 15:54 Sent To  
Notes
2016-10-21 15:55:39BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-01-03 Cont ID  
Sent By jvalido Date 2017-01-03 Time 18:09 Rev Time 0.00
Received By jvalido Date 2017-01-03 Time 18:08 Sent To  
Notes
2017-01-03 18:09:09REFER TO PERMIT #16120628. PERMIT HAS BEEN APPROVED BY
 HAROLD MOESER.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By mvaldes Date 2016-10-26 Time 17:22 Rev Time 0.00
Received By jvalido Date 2016-10-26 Time 16:10 Sent To  
Notes
2016-10-26 17:17:32CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES
  
 (1) PROVIDE MECHANICAL PLANS AS PER 107.2.1.4. (SEE
 ABOVE).
 (2) DESIGNATE EXISTING AND NEW DUCTWORK, IF APPLICABLE.
 (3) PROVIDE EQUIPMENT SCHEDULE AS PER R403.6.1
 (4) SHOW LOCATION OF CONDENSERS.
 (5) PROVIDE CONDENSER TIE DOWN DETAIL AS PER FBC 2014
 (6) PROVIDE EXHAUST IN ALL BATHROOMS.
 (7) PROVIDE RETURN FROM ALL BEDROOMS.
  
 FLORIDA ENERGY CODE FBC 2014
  
 R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED
 IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN
 SECTION R302.1. THIS CODE DOES NOT ALLOW DESIGNER
 SAFETY FACTORS, PROVISIONS FOR FUTURE EXPANSION OR
 OTHER FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM
 SIZING CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY
 LOCAL INTERMITTENT MECHANICAL VENTILATION SUCH AS
 STANDARD KITCHEN AND BATHROOM EXHAUST SYSTEMS.
  
 (8) PROVIDE HEAT LOAD CALCULATIONS AS PER R403.6.1 (SEE
 ABOVE). SUMMARIES ARE NOT ACCEPTABLE.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-02-02 Cont ID  
Sent By gjohnson Date 2017-02-02 Time 13:28 Rev Time 0.00
Received By gjohnson Date 2017-02-02 Time 13:28 Sent To  
Notes
2017-02-02 13:28:53PLUMBING PROVISO:
 THE FOLLOWING SHALL BE PROVIDED FOR INSPECTIONS
 1. PROVIDE AN APPROVED PLUMBING RISER DIAGRAM FOR NEW
 BATHROOM. PER WPB AMEND TO FBC 107.3.5.3(11)
 2. THE PLUMBING FOR NEW MASTER BATHROOM SHALL BE TESTED
 AND THE UNDERGROUND PIPING IS TO BE INSPECTED VIA VIDEO
 CAMERA, PROVIDE COPY OF VIDEO. SHOWER PAN SHALL BE
 EXPOSED AND TESTED PER FBC RES SECTION P2503 INSPECTION
 AND TESTS
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-01-05 Cont ID  
Sent By gjohnson Date 2017-01-05 Time 16:07 Rev Time 0.00
Received By gjohnson Date 2017-01-05 Time 16:07 Sent To  
Notes
2017-01-05 15:56:342ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 2ND REQEST HAS NOT COMPLIED
  
 1. PROVIDE PLUMBING RISER DIAGRAM FOR NEW BATHROOM. PER
 WPB AMEND TO FBC 107.3.5.3(11)
  
 3. THE PLUMBING FOR NEW MASTER BATHROOM SHALL BE TESTED
 AND THE UNDERGROUND PIPING IS TO BE INSPECTED VIA VIDEO
 CAMERA. PER FBC RES SECTION P2503 INSPECTION AND TESTS
 PLEASE PLACE NOTE ON PLAN INDICATING THIS.
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-10-27 Cont ID  
Sent By gjohnson Date 2016-10-27 Time 09:54 Rev Time 0.00
Received By gjohnson Date 2016-10-27 Time 09:22 Sent To  
Notes
2016-10-27 09:53:491ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE PLUMBING RISER DIAGRAM FOR NEW BATHROOM. PER
 WPB AMEND TO FBC 107.3.5.3(11)
  
 3. THE PLUMBING FOR NEW MASTER BATHROOM SHALL BE TESTED
 AND THE UNDERGROUND PIPING IS TO BE INSPECTED VIA VIDEO
 CAMERA. PER FBC RES SECTION P2503 INSPECTION AND TESTS
 PLEASE PLACE NOTE ON PLAN INDICATING THIS.
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-01-26 Cont ID  
Sent By njwira Date 2017-01-26 Time 15:21 Rev Time 0.00
Received By njwira Date 2017-01-26 Time 14:10 Sent To  
Notes
2017-01-26 15:23:171/26/17- PASSED
  
 CONVERTING GARAGE INTO A BATHROOM AND MASTER BEDROOM
 MECHANICAL EQUIPMENT HAS A 3FT. SETBACK MEETING THE
 1FT. REQUIREMENT
 ONE KITCHEN ONLY
 NO TREES BEING MOVED
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-12-21 Cont ID  
Sent By njwira Date 2016-12-21 Time 19:17 Rev Time 0.00
Received By njwira Date 2016-12-21 Time 17:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-11-01 Cont ID  
Sent By njwira Date 2016-11-01 Time 16:54 Rev Time 0.00
Received By njwira Date 2016-10-27 Time 15:52 Sent To I
Notes
2016-11-01 16:55:04MEETS HEIGHT REQUIREMENT
 NOT ADDING A NEW KITCHEN STILL ONE UNIT
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  