2016-10-25 12:18:45 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER ? PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| |
| 1. PROVIDE DEMENSIONS OF ROUGH OPENINGS. |
| 2. STATE EXSPOSURE CATEGORY. |
| 3. PROVIDE DESIGN WIND LOADS FOR OPENINGS. |
| 4. IDENTIFY WHICH MODEL DOOR WILL BE INSTALLED FROM |
| PRODUCT APPROVAL. |
| 5. DESIGNER TO PRINT NAME AND SIGN PLANS. |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. (SEE ALSO SECTION 107.3.5). |
| |
| FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN |
| PRESSURES PURSUANT TO FBC-R301.2. |
| |
| R301.2.1 WIND DESIGN CRITERIA. |
| BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF |
| THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND |
| DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1. |
| WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL |
| MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING, |
| THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH |
| PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE |
| WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR |
| HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED |
| TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR |
| WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR |
| WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN |
| GARAGE DOORS). WHERE LOADS FOR GARAGE DOORS ARE NOT |
| OTHERWISE SPECIFIED, THE LOADS LISTED IN TABLE |
| R301.2(4) ADJUSTED FOR HEIGHT AND EXPOSURE USING TABLE |
| R301.2(3) SHALL BE USED TO DETERMINE DESIGN LOAD |
| PERFORMANCE REQUIREMENTS. ASPHALT SHINGLES SHALL BE |
| DESIGNED FOR WIND SPEEDS IN ACCORDANCE WITH SECTION |
| R905.2.4. A CONTINUOUS LOAD PATH SHALL BE PROVIDED TO |
| TRANSMIT THE APPLICABLE UPLIFT FORCES IN SECTION R802.2 |
| FROM THE ROOF ASSEMBLY TO THE FOUNDATION. |
| |
| |