Plan Review Details - Permit 16100512
Plan Review Stops For Permit 16100512
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-14 Cont ID  
Sent By hmoser Date 2016-12-14 Time 13:27 Rev Time 0.00
Received By hmoser Date 2016-12-02 Time 12:31 Sent To  
Notes
2016-12-05 12:32:10RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-24 Cont ID  
Sent By hmoser Date 2016-10-24 Time 15:29 Rev Time 0.00
Received By hmoser Date 2016-10-19 Time 13:10 Sent To  
Notes
2016-10-19 13:10:26ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-12-14 Cont ID  
Sent By hmoser Date 2016-12-14 Time 13:27 Rev Time 0.00
Received By hmoser Date 2016-12-14 Time 13:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-24 Cont ID  
Sent By hmoser Date 2016-10-24 Time 14:21 Rev Time 0.00
Received By hmoser Date 2016-10-24 Time 14:20 Sent To E
Notes
2016-10-24 14:42:03PLAN DENIED
 1) PLAN DENIED PROVIDE A DETAIL FROM THE ENGINEER ON
 CURB TIEDOWN TO ROOF AND AIR MAKEUP UNIT TO CURB
 PER SECTION 301.15 WIND RESISTANCE 2014 FBC (M)
 2) APPLICATION SHOWS INSTALLATION OF (3) AIR MAKEUP
 UNITS
 AND DUCT WORK. THERE IS NO DUCTWORK SHOW-EN ON THE PLAN
 3) PROVIDE A EQUIPMENT SCHEDULE ON THE FIVE EXHAUST
 FANS
 YOU ARE REPLACING ON THE PLAN. PER SECTION 107 FBC 2014
  
 PLAN REVIEW BY HAROLD MOSER