Plan Review Details - Permit 16100211
Plan Review Stops For Permit 16100211
Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-10-28 Cont ID  
Sent By gjohnson Date 2016-10-28 Time 13:24 Rev Time 0.00
Received By gjohnson Date 2016-10-28 Time 13:24 Sent To  
Notes
2016-10-28 13:24:341ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SITE PLAN THAT SHOWS THE NEW GENERATOR AND
 FUEL STORAGE TANK. TO INCLUDE DISTANCES FROM
 SURROUNDING STRUCTURES AND TRAFFIC BARRIERS. PER WPB
 AMEND TO FBC 107.2.1
  
 2. PROVIDE COMPLETE RISER DIAGRAM FOR FUEL PIPING PER
 WPB AMEND TO FBC 107.3.5.1.5(1)(9)
  
 3. MANUFACTURE SPECIFICATION FOR STORAGE TANK. PER WPB
 AMEND TO FBC 107.2.1
  
 4. STRAPPING AND TIE DOWN DETAILS. PER WPB AMEND TO FBC
 107.2.1
  
 4. MSDS SHEETS FO R DIESEL FUEL. PER WPB AMEND TO FBC
 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-28 Cont ID  
Sent By gjohnson Date 2016-10-28 Time 13:24 Rev Time 0.00
Received By gjohnson Date 2016-10-12 Time 11:30 Sent To  
Notes
2016-10-13 11:31:03TRAVELLING WITH GENERATOR PERMIT 16100209