Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-10-31 Cont ID  
Sent By ccole Date 2016-10-31 Time 17:56 Rev Time 0.00
Received By ccole Date 2016-10-31 Time 17:56 Sent To  
Notes
2016-11-01 07:25:46MECHANICAL PROVISOS
 10/31/16
  
 1) REVISE THE PLANS UNDER MASTER PERMIT #15120536 TO
 SHOW THE HARVEY UNDERSLAB EXHAUST SYSTEM IN THE PORSCHE
 REPAIR GARAGE.
  
 2) MANUFACTURER'S SPECIFICATIONS FOR ALL COMPONENTS
 MUST BE ONSITE AT TIME OF INSPECTION.
  
 3) THE BLOWER EXHAUST TERMINATION SHALL BE IN
 COMPLIANCE WITH SECTION 501.3.1 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-12 Cont ID  
Sent By ccole Date 2016-10-12 Time 10:43 Rev Time 0.00
Received By ccole Date 2016-10-12 Time 10:43 Sent To  
Notes
2016-10-12 11:25:411ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100179
 10/12/16
  
 1) THE PLANS MUST BEAR THE ORIGINAL SIGNATURE AND SEAL
 AND TITLE BLOCK OF THE ENGINEER JOHN P. REED- SECTION
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE.
  
 2) A REVISION TO THE APPROVED ARCHITECTURAL, MECHANICAL
 AND ELECTRICAL PLAN SHEETS ARE REQUIRED TO SHOW THE
 CHANGE TO THE UNDERGROUND EXHAUST SYSTEM, AND THE
 CHANGE MUST BE APPROVED WITH SIGNATURES BY THE DESIGN
 PROFESSIONALS OF RECORD.
  
 3) REFER TO SECTION 603.8.3 AND VERIFY THE UNDERGROUND
 PVC DUCTS ARE IN COMPLIANCE WITH THE ASTM D2412 TESTING
 STANDARD.
  
 4) REFER TO SECTION 603.18.1 AND VERIFY STRUCTURAL
 COMPLIANCE FOR THE FLOOR FITTINGS.
  
 5) THE PLAN APPEARS TO INDICATE THAT THE BLOWER FOR THE
 EXHAUST SYSTEM IS DISCHARGING INTO THE EQUIPMENT ROOM.
 PLEASE NOTE PER SECTION 501.1 EXHAUST SHALL DISCHARGE
 TO THE OUTDOORS AT A POINT WHERE IT WILL NOT CAUSE A
 NUISANCE AND NOT LESS THAN THE DISTANCES SPECIFIED IN
 SECTIION 501.3.1.
  
 6) CLARIFY HOW THE BLOWER SIZE WAS DETERMNINED- SHOW
 CALCULATUIONS.
  
 6) THE KEY NOTE 20 IN A HEX SYMBOL IS SHOWN IN MANY
 PLANCES ON THE PLAN WITH NO EXPLANATION OF WHAT IT IS
 INDICATING- PLEASE CLAIFY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER