Plan Review Details - Permit 16100163
Plan Review Stops For Permit 16100163
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-10-21 Cont ID  
Sent By cthroop Date 2016-10-21 Time 12:52 Rev Time 0.00
Received By cthroop Date 2016-10-21 Time 12:47 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-10-24 Cont ID  
Sent By mvaldes Date 2016-10-24 Time 15:15 Rev Time 0.00
Received By mvaldes Date 2016-10-24 Time 14:37 Sent To  
Notes
2016-10-24 15:15:441ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 PASSED WITH THE FOLLOWING PROVISO'S (RED-LINED ON
 PLANS)
  
 1] NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS
  
 2] NEC 600.6 - PROVIDE DISCONNECT SWITCH AT SIGN
 LOCATION.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-24 Cont ID  
Sent By mvaldes Date 2016-10-24 Time 15:16 Rev Time 0.00
Received By mvaldes Date 2016-10-11 Time 16:17 Sent To  
Notes
2016-10-11 16:18:00ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2016-10-20 Cont ID  
Sent By   Date 2016-10-20 Time   Rev Time 0.00
Received By kmartin Date 2016-10-20 Time 16:24 Sent To B
Notes
2016-10-13 17:21:07ROUTED TO KEVIN MARTIN


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved