Plan Review Details - Permit 16100149
Plan Review Stops For Permit 16100149
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-11-02 Cont ID  
Sent By mgonzale Date 2016-10-27 Time   Rev Time 0.00
Received By mkhan Date 2016-11-02 Time 11:50 Sent To I
Notes
2016-11-02 11:53:26TIM LARGE, CITY'S PLUMBING INSPECTOR EMAILED THE NEWLY
 SUBMITTED PLANS WHERE A HAND DRAWN LOCATION/SPOT IS
 SHOWN FOR THE NEW GREASE INTERCEPTOR WITH CAPACITY (75
 GPM).
2016-10-27 12:52:56NO LOCATION SPECIFIED ON PLAN.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-02 Cont ID  
Sent By mkhan Date 2016-11-02 Time 11:54 Rev Time 0.00
Received By tklarge Date 2016-11-01 Time 05:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-28 Cont ID  
Sent By tklarge Date 2016-10-28 Time 03:34 Rev Time 0.00
Received By tklarge Date 2016-10-11 Time 13:42 Sent To  
Notes
2016-10-11 13:42:12ROUTED TO PLUMBING <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-11-01 Cont ID  
Sent By tklarge Date 2016-11-01 Time 06:50 Rev Time 0.00
Received By tklarge Date 2016-11-01 Time 05:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-10-12 Cont ID  
Sent By tklarge Date 2016-10-12 Time 06:49 Rev Time 0.00
Received By tklarge Date 2016-10-12 Time 06:40 Sent To  
Notes
2016-10-12 06:45:201) SHOW THE APPROXIMATE LOCATION OF THE INTERCEPTOR ON
 THE SITE PLAN. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER TO
 ENSURE THE NEW INTERCEPTOR IS SIZED PROPERLY. 2014 FPC
 SEC. 1003.2. CONTACT LEE SCHNEEWEISS FROM SCHIER AT
 1-800-538-4792.
 3) WHAT SIZE GREASE INTERCEPTOR IS THIS REPLACING?
 INNDICATE ON THE SITE PLAN.
 4) A SAMPLING PORT IS REQUIRED ON THE DISCHARGE OF THE
 INTERCEPTOR.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  