Plan Review Details - Permit 16100127
Plan Review Stops For Permit 16100127
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-27 Cont ID  
Sent By jwitmer Date 2016-12-27 Time 08:20 Rev Time 0.00
Received By jwitmer Date 2016-12-27 Time 08:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-02 Cont ID  
Sent By jwitmer Date 2016-11-02 Time 07:26 Rev Time 0.00
Received By jwitmer Date 2016-11-02 Time 07:08 Sent To  
Notes
2016-11-02 07:26:18BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16100127
 ADD: 5444 N HAVERHILL/ NATIONALS CLUBHOUSE
 CONT: DAVCO ELECTRICAL CONTRACTORS
 TEL: 561-732-3434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 02/2016
 ACTION: DENIED
  
 1) NONE OF THE PLANS SUBMITTED OR SUPPORTING DOCUMENTS
 PROVIDE THE WIND DESIGN CRITERIA FOR GENERATORS AND OR
 COVERS EXPOSED TO WIND. 2014 FBC-B 1603.1.4 WIND DESIGN
 DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 2) PLEASE SHOW HOW THE DAY TANK AND GENERATOR ARE GOING
 TO BE HELD AGAINST THE MOMENT OF OVERTURNING.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-10-24 Cont ID  
Sent By vperez Date 2016-10-24 Time 10:11 Rev Time 0.00
Received By vperez Date 2016-10-24 Time 10:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-10-21 Cont ID  
Sent By wjolin Date 2016-10-21 Time 08:35 Rev Time 0.00
Received By wjolin Date 2016-10-21 Time 08:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-27 Cont ID  
Sent By jwitmer Date 2016-12-27 Time 08:18 Rev Time 0.00
Received By jwitmer Date 2016-12-22 Time 13:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-15 Cont ID  
Sent By cpuell Date 2016-11-15 Time 18:33 Rev Time 0.00
Received By cpuell Date 2016-10-12 Time 08:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2016-11-09 Cont ID  
Sent By tklarge Date 2016-11-09 Time 11:03 Rev Time 0.00
Received By tklarge Date 2016-11-09 Time 06:01 Sent To  
Notes
2016-11-09 11:05:14THIS A SELFF CONTAINED SYSTEM WITH THE FUEL TANK
 LOCATED BELOW THE GENERATOR (BELLY TANK). THE UNIT IS
 PRE-PIPED FROM THE MANUFACTURER. A PLUMBING PERMIT IS
 NOT REQUIRED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-12-27 Cont ID  
Sent By jwitmer Date 2016-12-27 Time 08:18 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2016-12-27 08:18:14PAPER GENERATOR TIE DOWN DETAILS WITH SIGNATURE AND
 SEAL. OK/ JW
2016-12-16 11:16:4112/22/16 SIGNED AND SEALED SHEETS FOR TIE DOWN DETAIL
 GIVEN TO JWITMER
2016-10-13 08:18:0710/13/16 - **DIGITALLY SIGNED SHEET UNDER SIGNATURES
 FOLDER**

Review Stop Z ZONING
Rev No 1 Status P Date 2016-11-14 Cont ID  
Sent By ajones Date 2016-11-14 Time 17:04 Rev Time 0.00
Received By ajones Date 2016-11-14 Time 17:04 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved