Plan Review Details - Permit 16100125
Plan Review Stops For Permit 16100125
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-25 Cont ID  
Sent By ccole Date 2016-10-25 Time 11:19 Rev Time 0.00
Received By ccole Date 2016-10-25 Time 11:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-11 Cont ID  
Sent By ccole Date 2016-10-11 Time 16:13 Rev Time 0.00
Received By ccole Date 2016-10-11 Time 16:13 Sent To  
Notes
2016-10-11 16:32:251ST REVIEW FBC-2014 BUILDING
 PERMIT #16100125
 10/11/16
  
 1) THE SUBMITTED CALCULATIONS AND UPLIFT ZONE SCHEMATIC
 DRAWING FROM ATLAS STRUCTURAL ENGINEERING LLC EACH MUST
 BEAR THE ORIGINAL SIGNATURES AND SEALS OF THE EINGINEER
 OF RECORD PER FLORIDA STATUE AND SECTION 61G15-23.002
 FAC.
  
 2) REFER TO GENERAL LIMITATION NOTE #5 OF NOA
 13-1113.03 AND PROVIDE THE PULL TEST RESULTS.
  
 3) PROVIDE ENLARGED DRAWINGS OF EACH ROOF SECTION
 SHOWING THE LOCATIONS OF EXISTING ROOF DRAINS AND
 SCUPPERS AND ALL ROOFTOP MECHANICAL EQUIPMENT. A)
 PROVIDE A SCOPE OF WORK FOR THE ROOFTOP EQUIPMENT-
 CLARIFY IF ANY EQUIPMENT, STANDS, OR CURBS ARE BEING
 TEMPORARILY REMOVED, OR REPLACED DURING THE REROOFING
 PROCESS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-25 Cont ID  
Sent By ccole Date 2016-10-25 Time 11:19 Rev Time 0.00
Received By ccole Date 2016-10-21 Time 12:57 Sent To  
Notes
2016-10-24 12:57:15RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-11 Cont ID  
Sent By ccole Date 2016-10-11 Time 16:13 Rev Time 0.00
Received By ccole Date 2016-10-11 Time 16:13 Sent To  
Notes
2016-10-11 11:45:31CCOLE


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved