Plan Review Details - Permit 16100030
Plan Review Stops For Permit 16100030 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-06-08 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-06-06 |
Time |
13:12 |
Sent To |
|
|
Notes |
2018-06-07 13:12:50 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-05-11 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-04-24 |
Time |
14:35 |
Sent To |
|
|
Notes |
2018-04-25 14:36:02 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2017-07-21 |
Time |
|
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2017-07-18 |
Time |
09:18 |
Sent To |
|
|
Notes |
2017-07-20 09:18:45 | CCOLE'S DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-10-13 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-10-13 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-10-03 |
Time |
13:16 |
Sent To |
|
|
Notes |
2016-10-04 13:16:57 | SUBMITTAL ROUTED TO CCOLE |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2018-06-08 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-06-08 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-06-08 |
Time |
14:51 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2018-05-11 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-05-11 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-05-11 |
Time |
13:59 |
Sent To |
I |
|
Notes |
2018-05-11 14:17:24 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #16100030 | | 5/11/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) AS PREVIOUSLY NOTED, ALL OF THE SMOKE CONTROL FANS | | MUST BE EQUIPPED WITH A MINIMUM OF TWO BELTS PER | | SECTION 909.10.5. FBC-10, AND THE SMOKE CONTROL | | RATIONAL ANALYSIS FOR THE PROJECT BY JOSEPH E. HAUF P.E | | (SEE FANS- PAGE 21). THE LETTER FROM TOM BARROW COMPANY | | TO KAST CONSTRUCTION THAT WAS SUBMITTED TO THE BUILDING | | DEPARTMENT STATES THAT ALL OF THE SMOKE CONTROL FANS | | | | ARE UL LISTED AND LABELED FOR SMOKE CONTROL, HOWEVER | | THIS IS NOT THE ISSUE IN DISPUTE. THE ISSUE IS THE | | LETTER ALSO STATES THAT THE SMOKE CONTROL FANS GEF-1-1, | | GEF-1-2, SEF-1-1, LPF-1-1, SPF-1-1, SPF-R-1, AND | | SPF-R-2 ARE EQUIPPED WITH 1 BELT ONLY, AND THEREFORE | | ARE NON-COMPLIANT. DUE TO THE FACT THAT THIS IS THE 3RD | | REVIEW OF THE PROJECT, THE ISSUE WAS REFERRED TO ROBERT | | BROWN | | | | BUILDING OFFICIAL FOR WPB. HIS JUDGEMENT IS THAT THE | | TWO-BELT MINIMUM REQUIREMENT WILLL BE ENFORCED. AS A | | RESULT THESE COMMENTS HAVE BEEN WRITTEN, AND A PHONE | | CALL WAS PLACED TO TWR ENGINEERS TO ALERT THEM. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2017-07-21 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-07-21 |
Time |
11:17 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-07-21 |
Time |
11:17 |
Sent To |
|
|
Notes |
2017-07-21 11:32:13 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16100030 | | 7/21/2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) AS PREVIOUSLY NOTED, THE LOREN COOK QMX AND CPS FANS | | MUST BE EQUIPPED WITH A MINIMUM OF TWO BELTS PER | | SECTION 909.10.5. FBC-10, AND THE SMOKE CONTROL | | RATIONAL ANALYSIS FOR THE PROJECT BY JOSEPH E. HAUF P.E | | (SEE FANS- PAGE 21). ADDITIONALLY, PLEASE PROVIDE | | VERIFICATION THAT THE FANS BEAR THE UL LISTING AND | | LABELING AS POWER VENTILATORS FOR SMOKE CONTROL | | SYSTEMS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-10-13 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-10-13 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-10-13 |
Time |
10:06 |
Sent To |
|
|
Notes |
2016-10-13 10:47:41 | 1ST REVIEW FBC-2014 MECHANICAL | | MASTER #15031312 | | REVISION #16100030 | | 333 DOWNTOWN | | 10/13/16 | | | | 1) BELT-DRIVEN SMOKE CONTROL FANS ARE REQUIRED TO HAVE | | A MINIMUM OF TWO BELTS PER SECTION 513.10.5. THE | | SUBMITTALS DO NOT INDICATE COMPLAINCE, HOWEVER THE | | EMAIL FROM KAST CONSTRUCTION INDICATES THAT FANS- | | LPF-1, SPF-R-1-1, AND SPF-R-2-1 EACH HAVE ONLY ONE | | BELT. (SEE COPIED EMAIL BELOW COMMENT #3). | | | | 2) PROVIDE A FL. PRODUCT APPROVAL AND/OR MIAMI-DADE NOA | | FOR THE COOK SHUTTER. | | | | 3) THE FAN SCHEDULE ON APPROVED SHEET M4.01A MUST BE | | REVISED TO MATCH THE FANS SELECTED FOR USE ON THE | | PROJECT. | | | | | | MATT STILL, SENIOR PROJECT MANAGER | | PHONE 561-689-2910 | | CELL 561-603-9031 | | FAX 561-689-2911 | | EMAIL [email protected] | | 701 NORTHPOINT PARKWAY, SUITE 400 | | WEST PALM BEACH, FL 33407 | | WWW.KASTBUILD.COM | | | | FROM: WALKER, JIM [MAILTO:[email protected]] | | SENT: THURSDAY, OCTOBER 06, 2016 2:13 PM | | TO: MATT STILL ; FRANK WYNES | | | | SUBJECT: RE: 333 DOWNTOWN | | | | MATT AND FRANK, | | | | HERE IS THE ANSWER. IF THEY ARE REVIEWING THE SMOKE | | CONTROL FANS WITH UL RATING THAT WE HAVE UNDER | | SUBMITTAL RIGHT NOW, HERE IS THE BELT COUNT. | | | | LPF-1 GROOVE DRIVE ? 1 BELT | | SPF-1-1 2 GROOVE DRIVE ? 2 BELTS | | SPF1-2 2 GROOVE DRIVE ? 2 BELTS | | SPF-R-1 1 GROOVE DRIVE -1 BELT | | SPF-R-2 1 GROOVE DRIVE ? 1 BELT | | | | | | LET ME KNOW IF I CAN BE OF MORE ASSISTANCE. | | | | THANKS, | | | | BEST REGARDS, | | | | JIM WALKER | | SALES ENGINEER | | | | ** SEND QUOTE REQUESTS TO [email protected] | | ** CC TO ME [email protected] | | | | TOM BARROW COMPANY - TAMPA | | OFFICE: 813-888-9000 EXT. 223 | | MOBILE: 813-401-6755 | | WWW.TOMBARROW.COM | | AIR COOLED CHILLERS IN STOCK | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |