Plan Review Details - Permit 16100030
Plan Review Stops For Permit 16100030
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-06-08 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-06 Time 13:12 Sent To  
Notes
2018-06-07 13:12:50RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-05-11 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-24 Time 14:35 Sent To  
Notes
2018-04-25 14:36:02RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-07-21 Time   Rev Time 0.00
Received By cpuell Date 2017-07-18 Time 09:18 Sent To  
Notes
2017-07-20 09:18:45CCOLE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-13 Cont ID  
Sent By ccole Date 2016-10-13 Time 10:06 Rev Time 0.00
Received By ccole Date 2016-10-03 Time 13:16 Sent To  
Notes
2016-10-04 13:16:57SUBMITTAL ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-06-08 Cont ID  
Sent By ccole Date 2018-06-08 Time 14:51 Rev Time 0.00
Received By ccole Date 2018-06-08 Time 14:51 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-05-11 Cont ID  
Sent By ccole Date 2018-05-11 Time 13:59 Rev Time 0.00
Received By ccole Date 2018-05-11 Time 13:59 Sent To I
Notes
2018-05-11 14:17:243RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16100030
 5/11/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS PREVIOUSLY NOTED, ALL OF THE SMOKE CONTROL FANS
 MUST BE EQUIPPED WITH A MINIMUM OF TWO BELTS PER
 SECTION 909.10.5. FBC-10, AND THE SMOKE CONTROL
 RATIONAL ANALYSIS FOR THE PROJECT BY JOSEPH E. HAUF P.E
 (SEE FANS- PAGE 21). THE LETTER FROM TOM BARROW COMPANY
 TO KAST CONSTRUCTION THAT WAS SUBMITTED TO THE BUILDING
 DEPARTMENT STATES THAT ALL OF THE SMOKE CONTROL FANS
  
 ARE UL LISTED AND LABELED FOR SMOKE CONTROL, HOWEVER
 THIS IS NOT THE ISSUE IN DISPUTE. THE ISSUE IS THE
 LETTER ALSO STATES THAT THE SMOKE CONTROL FANS GEF-1-1,
 GEF-1-2, SEF-1-1, LPF-1-1, SPF-1-1, SPF-R-1, AND
 SPF-R-2 ARE EQUIPPED WITH 1 BELT ONLY, AND THEREFORE
 ARE NON-COMPLIANT. DUE TO THE FACT THAT THIS IS THE 3RD
 REVIEW OF THE PROJECT, THE ISSUE WAS REFERRED TO ROBERT
 BROWN
  
 BUILDING OFFICIAL FOR WPB. HIS JUDGEMENT IS THAT THE
 TWO-BELT MINIMUM REQUIREMENT WILLL BE ENFORCED. AS A
 RESULT THESE COMMENTS HAVE BEEN WRITTEN, AND A PHONE
 CALL WAS PLACED TO TWR ENGINEERS TO ALERT THEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-07-21 Cont ID  
Sent By ccole Date 2017-07-21 Time 11:17 Rev Time 0.00
Received By ccole Date 2017-07-21 Time 11:17 Sent To  
Notes
2017-07-21 11:32:132ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16100030
 7/21/2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS PREVIOUSLY NOTED, THE LOREN COOK QMX AND CPS FANS
 MUST BE EQUIPPED WITH A MINIMUM OF TWO BELTS PER
 SECTION 909.10.5. FBC-10, AND THE SMOKE CONTROL
 RATIONAL ANALYSIS FOR THE PROJECT BY JOSEPH E. HAUF P.E
 (SEE FANS- PAGE 21). ADDITIONALLY, PLEASE PROVIDE
 VERIFICATION THAT THE FANS BEAR THE UL LISTING AND
 LABELING AS POWER VENTILATORS FOR SMOKE CONTROL
 SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-13 Cont ID  
Sent By ccole Date 2016-10-13 Time 10:06 Rev Time 0.00
Received By ccole Date 2016-10-13 Time 10:06 Sent To  
Notes
2016-10-13 10:47:411ST REVIEW FBC-2014 MECHANICAL
 MASTER #15031312
 REVISION #16100030
 333 DOWNTOWN
 10/13/16
  
 1) BELT-DRIVEN SMOKE CONTROL FANS ARE REQUIRED TO HAVE
 A MINIMUM OF TWO BELTS PER SECTION 513.10.5. THE
 SUBMITTALS DO NOT INDICATE COMPLAINCE, HOWEVER THE
 EMAIL FROM KAST CONSTRUCTION INDICATES THAT FANS-
 LPF-1, SPF-R-1-1, AND SPF-R-2-1 EACH HAVE ONLY ONE
 BELT. (SEE COPIED EMAIL BELOW COMMENT #3).
  
 2) PROVIDE A FL. PRODUCT APPROVAL AND/OR MIAMI-DADE NOA
 FOR THE COOK SHUTTER.
  
 3) THE FAN SCHEDULE ON APPROVED SHEET M4.01A MUST BE
 REVISED TO MATCH THE FANS SELECTED FOR USE ON THE
 PROJECT.
  
  
 MATT STILL, SENIOR PROJECT MANAGER
 PHONE 561-689-2910
 CELL 561-603-9031
 FAX 561-689-2911
 EMAIL [email protected]
 701 NORTHPOINT PARKWAY, SUITE 400
 WEST PALM BEACH, FL 33407
 WWW.KASTBUILD.COM
  
 FROM: WALKER, JIM [MAILTO:[email protected]]
 SENT: THURSDAY, OCTOBER 06, 2016 2:13 PM
 TO: MATT STILL ; FRANK WYNES
 
 SUBJECT: RE: 333 DOWNTOWN
  
 MATT AND FRANK,
  
 HERE IS THE ANSWER. IF THEY ARE REVIEWING THE SMOKE
 CONTROL FANS WITH UL RATING THAT WE HAVE UNDER
 SUBMITTAL RIGHT NOW, HERE IS THE BELT COUNT.
  
 LPF-1 GROOVE DRIVE ? 1 BELT
 SPF-1-1 2 GROOVE DRIVE ? 2 BELTS
 SPF1-2 2 GROOVE DRIVE ? 2 BELTS
 SPF-R-1 1 GROOVE DRIVE -1 BELT
 SPF-R-2 1 GROOVE DRIVE ? 1 BELT
  
  
 LET ME KNOW IF I CAN BE OF MORE ASSISTANCE.
  
 THANKS,
  
 BEST REGARDS,
  
 JIM WALKER
 SALES ENGINEER
  
 ** SEND QUOTE REQUESTS TO [email protected]
 ** CC TO ME [email protected]
  
 TOM BARROW COMPANY - TAMPA
 OFFICE: 813-888-9000 EXT. 223
 MOBILE: 813-401-6755
 WWW.TOMBARROW.COM
 AIR COOLED CHILLERS IN STOCK
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  