Plan Review Details - Permit 16100008
Plan Review Stops For Permit 16100008
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-10-27 Cont ID  
Sent By scaldero Date 2016-10-27 Time 14:39 Rev Time 0.00
Received By scaldero Date 2016-10-27 Time 14:39 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-10-03 Cont ID  
Sent By scaldero Date 2016-10-03 Time 14:56 Rev Time 0.00
Received By scaldero Date 2016-10-03 Time 14:54 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-12-01 Cont ID  
Sent By ccole Date 2016-12-01 Time 11:42 Rev Time 0.00
Received By ccole Date 2016-11-23 Time 09:42 Sent To  
Notes
2016-11-23 09:43:03RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-22 Cont ID  
Sent By ccole Date 2016-11-22 Time 14:52 Rev Time 0.00
Received By ccole Date 2016-11-14 Time 13:28 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-31 Cont ID  
Sent By ccole Date 2016-10-31 Time 15:54 Rev Time 0.00
Received By ccole Date 2016-10-21 Time 10:06 Sent To  
Notes
2016-10-24 10:06:59RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-03 Cont ID  
Sent By ccole Date 2016-10-03 Time 16:44 Rev Time 0.00
Received By ccole Date 2016-10-03 Time 14:40 Sent To  
Notes
2016-10-03 14:40:21ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-12-01 Cont ID  
Sent By ccole Date 2016-12-01 Time 11:39 Rev Time 0.00
Received By ccole Date 2016-12-01 Time 11:39 Sent To  
Notes
2016-12-01 11:42:31MECHANICAL PROVISO:
 12/1/16
  
 A REVISION TO THE APPROVED MECHANICAL AND ELECTRICAL
 PLANS TO SHOW THE GREASE EXHAUST FAN AT ROOFTOP
 TERMINATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-11-22 Cont ID  
Sent By ccole Date 2016-11-22 Time 14:52 Rev Time 0.00
Received By ccole Date 2016-11-18 Time 14:52 Sent To  
Notes
2016-11-22 15:03:243RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16100008
 11/22/16
  
 1) THE SUBMITTED SPECS FOR THE PIZZA OVEN AND THE
 GREASE DUCT EACH SPECIFY COMPLIANCE WITH NFPA 96.
 PLEASE REFER TO SECTION 7.8.2.1(8) . A HINGED UPBLAST
 FAN IS REQUIRED FOR THE GREASE DUCT TERMINATING AT THE
 ROOFTOP.
  
 2) PLEASE CORRECT PLAN KEY NOTE #13 SPECIFYING THE
 WRONG TYPE OF EXHAUST DUCTWORK.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-10-31 Cont ID  
Sent By ccole Date 2016-10-31 Time 15:25 Rev Time 0.00
Received By ccole Date 2016-10-31 Time 15:25 Sent To  
Notes
2016-10-31 15:43:062ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16100008
 10/31/16
  
 1) THE REQUESTED SPECS FOR THE PIZZA OVEN THAT INDICATE
 COMPLIANCE WITH THE ANSI Z21.1, ANSI Z21.58, OR ANSI
 Z83.11 WERE NOT SUBMITTED.
  
 2) PROVIDE DOCUMENTATION FROM THE MANUFACTURER OF THE
 PIZZA OVEN THAT STATES FIRE SUPPRESSION IS NOT
 REQUIRED.
  
 3) INDICATE ON THE PLAN WHICH OF THE 5 DUCT MODELS IN
 THE SUBMITTED SPECIFICATIONS WILL BE INSTALLED- DW,
 DW-2R, DW 2R TYPE HT, DW-3R, OR DW-3Z. THE REVISED PLAN
 APPEARS TO INDICATE THE DUCT MAKING A ZERO-CLEARANCE
 PENETRATION OF THE COMBUSTIBLE ROOF SURFACE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By ccole Date 2016-10-03 Time 16:27 Rev Time 0.00
Received By ccole Date 2016-10-03 Time 16:27 Sent To  
Notes
2016-10-03 16:44:181ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100008
 10/3/2016
  
 1) THE SUBMITTED VENTING PLAN FOR THE OVEN REQUIRES THE
 NAME, TITLE BLOCK, AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN- SECTION 107 WPB AMENDMENTS
 TO THE FBC.
  
 2) THE EXHAUST OUTLET SHALL HAVE THE DISCHARGE OPENING
 LOCATED NOT LESS THAN 40 " ABOVE THE ROOF SURFACE- SEE
 SECTION 506.3.13. THE SUBMITTED PLAN IS INDICATING 36".
  
 3) THE PIZZA OVEN SHALL BE TESTED IN ACCORDANCE WITH
 ANZI Z21.1, ANSI Z21.58, OR ANZIZ83.11. PLEASE PROVIDE
 DOCUMENTATION TO VERIFY COMPLIANCE.
  
 4) THE SUBMITTAL FOR THE VENT APPEARS TO HAVE PAGES
 MISSING FROM THRE DOCUMENT- PLEASE PROVIDE A COMPLETE
 SUBMITTAL.
  
 5) ADVISORY: A SEPARATE PERMIT AND PLANS ARE REQUIRED
 FOR THE FIRE SUPPRESSION SYSTEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  