Plan Review Details - Permit 16100003
Plan Review Stops For Permit 16100003 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-04-02 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-03-28 |
Time |
10:33 |
Sent To |
|
|
Notes |
2018-03-29 10:33:55 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2017-07-21 |
Time |
|
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2017-07-18 |
Time |
09:15 |
Sent To |
|
|
Notes |
2017-07-20 09:15:42 | CCOLE'S DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-10-04 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-10-04 |
Time |
12:14 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-10-03 |
Time |
14:04 |
Sent To |
|
|
Notes |
2016-10-03 14:04:35 | SUBMITTAL ROUTED TO CCOLE |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2018-04-02 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-04-02 |
Time |
13:19 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-04-02 |
Time |
13:19 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2017-07-21 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-07-21 |
Time |
10:16 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-07-21 |
Time |
09:37 |
Sent To |
|
|
Notes |
2017-07-21 10:22:59 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT SUBMITTAL #16100003 | | 7/21/17 | | | | 1) THE X-VENT BOXES ARE APPROVED. | | | | 2) THE SUBMITTED SPECS FOR THE DRYER MODEL #GUD27ESSJWW | | SHOWS A MAXIMUM EXHAUST DUCT LENGTH OF 56 FT. USING A | | 4" DUCT AND 4" TERMINATION, HOWEVER THE UNITS PLANS ARE | | SPECIFYING MINIMUMS OF 64 FT. TO 200 FT. DEPENDING ON | | THE UNIT. PLEASE INDICATE BY UNIT NUMBER WHERE THESE | | DRYERS ARE TO BE INSTALLED. PROVIDE UNIT NUMBERS TAT | | CORRELATE TO THE NUMBERS SHOWN ON THE PLANS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-10-04 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-10-04 |
Time |
12:16 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-10-04 |
Time |
12:14 |
Sent To |
|
|
Notes |
2016-10-04 12:22:08 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16100003 | | 10/4/16 | | | | 1) XVENT BOX SUBMITTALS: PLEASE REVIEW SECTION 501.3,2 | | PRINTED BELOW AND VERIFY COMPLIANCE. | | | | 501.3.2 EXHAUST OPENING PROTECTION. | | EXHAUST OPENINGS THAT TERMINATE OUTDOORS SHALL BE | | PROTECTED WITH CORROSION-RESISTANT SCREENS, LOUVERS OR | | GRILLES. OPENINGS IN SCREENS, LOUVERS AND GRILLES SHALL | | BE SIZED NOT LESS THAN 1/4 INCH (6 MM) AND NOT LARGER | | THAN 1/2 INCH (13 MM). OPENINGS SHALL BE PROTECTED | | AGAINST LOCAL WEATHER CONDITIONS. LOUVERS THAT PROTECT | | EXHAUST OPENINGS IN STRUCTURES LOCATED IN | | HURRICANE-PRONE REGIONS, AS DEFINED IN THE FLORIDA | | BUILDING CODE, BUILDING, SHALL COMPLY WITH AMCA | | STANDARD 550. OUTDOOR OPENINGS LOCATED IN EXTERIOR | | WALLS SHALL MEET THE PROVISIONS FOR EXTERIOR WALL | | OPENING PROTECTIVES IN ACCORDANCE WITH THE FLORIDA | | BUILDING CODE, BUILDING. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |