 BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. CORRECT CODE SUMMARY ON PG. A-1
 2. LABEL PLANS WITH REQUIRED CEILING INSULATION FROM
 ENERGY SUBMITTAL (R30).
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-12-06 Cont ID  
Sent By skennedy Date 2016-12-06 Time 15:22 Rev Time 0.00
Received By skennedy Date 2016-12-06 Time 15:22 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-11-30 Cont ID  
Sent By skennedy Date 2016-11-30 Time 14:32 Rev Time 0.00
Received By skennedy Date 2016-11-30 Time 14:32 Sent To  
Notes
2016-11-30 14:32:56FAILED TO ALLOW RE-SUB WITHOUT REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-18 Cont ID  
Sent By vperez Date 2016-10-18 Time 09:37 Rev Time 0.00
Received By vperez Date 2016-10-18 Time 09:37 Sent To  
Notes
2016-10-18 09:37:07INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND
 LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC
 RATINGS. FBC 107.3.5
 2. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS
 FOR LOW VOLTAGE SYSTEMS. FBC 107.3.5
 3. SHOW EXTERIOR RECEPTACLE AT REAR PROTECTED BY GFCI
 DEVICE. FBC RES E3902.3
 4. PLEASE NOTE THAT ALL CIRCUITS? DESIGNATION AT THE
 PANELBOARDS MUST INDICATE WHAT AREA SPECIFICALLY OF THE
 HOUSE IT?S SERVICING. GENERAL LIGHTING DOES NOT MEET
 THESE REQUIREMENTS. EXAMPLE, LABEL BEDROOM 1, BEDROOM 2
 ETC.?NEC 408.4 FIELD ID REQUIRED. FBC 107.3.5
 5. PROVIDE A NOTE TO INDICATE REQUIRED TAMPER RESISTANT
 RECEPTACLE THROUGHOUT. FBC RES E4002.14
 6. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO
 INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS.
 7. ELECTRICAL SHEET TO BE SIGNED AND SEALED BY DESIGNER
 OF RECORD. FBC 107.3.5
 8. EXTERIOR RECEPTACLES TO BE GFCI PROTECTED, LABEL AT
 THE PANEL CIRCUIT #26 FBC RES E3902.3
 9. ADDRESS SPACING FOR COUNTERTOP RECEPTACLES IN
 KITCHEN PER FBC RES E3901.4 LEFT OF RANGE.
 10. SHOW LIGHTING OUTLET AT THE ATTIC ACCESS LOCATION
 PER FBC RES E3903.4 SHOW ATTIC LOCATION
 11. PROVIDE A NOTE TO PROVIDE AFCI PROTECTION PER FBC
 RES E3902.12
 12. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-12-07 Cont ID  
Sent By spalmer Date 2016-12-07 Time 15:25 Rev Time 0.00
Received By spalmer Date 2016-12-07 Time 15:24 Sent To  
Notes
2016-12-02 14:39:25R09

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-30 Cont ID  
Sent By skennedy Date 2016-11-30 Time 14:33 Rev Time 0.00
Received By skennedy Date 2016-11-08 Time 11:07 Sent To  
Notes
2016-11-09 11:07:26R07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-04 Cont ID  
Sent By ccole Date 2016-11-04 Time 08:35 Rev Time 0.00
Received By ccole Date 2016-09-30 Time 11:43 Sent To  
Notes
2016-10-03 11:43:19R07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-11-30 Cont ID  
Sent By skennedy Date 2016-11-30 Time 14:32 Rev Time 0.00
Received By skennedy Date 2016-11-30 Time 14:32 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-10-27 Cont ID  
Sent By cthroop Date 2016-10-27 Time 15:00 Rev Time 0.00
Received By cthroop Date 2016-10-27 Time 14:29 Sent To  
Notes
2016-10-27 15:13:18BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-12-06 Cont ID  
Sent By skennedy Date 2016-12-06 Time 15:14 Rev Time 0.00
Received By skennedy Date 2016-12-06 Time 15:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-11-21 Cont ID  
Sent By ccole Date 2016-11-21 Time 18:01 Rev Time 0.00
Received By ccole Date 2016-11-21 Time 07:31 Sent To  
Notes
2016-11-21 18:04:262ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16091117
 11/21/16
  
 1) COMMENT #8 FROM THE 1ST REVIEW ABOUT THE DIRECTIONAL
 ORIENTATIONS FOR THE ROOMS, WALLS, WINDOW GLASS ETC. IN
 THE MANUAL J STILL EXISTS. PLEASE COMPLY.
  
 2) COMMENTS #10 A, B, & C FROM THE 1ST REVIEW STILL
 EXIST. PLEASE COMPLY
  
 3) FORM R405-2014 LISTS THE AC SYSTEM AT 16 SEER BUT
 THE NEW AC SCHEDULE INDICATES A 14 SEER SYSTEM.
  
 4) PLEASE REMOVE THE FOUNDATION PLAN FROM THE MA-2 PLAN
 SHEET. THE FOUNDATION DRAWING REQUIRES A SIGNATURE AND
 SEAL BY A FL. LICENSED ENGINEER OR ARCHITECT.
  
 5) A SEALED ENCLOSURE IS REQUIRED FOR THE AIR HANDLER
 RETURN IF IT IS TO BE LOCATED IN THE UTILITY ROOM- SEE
 SECTION R403.2.2 FBC-14 ENERGY CONSERVATION AND SECTION
 M1602.2 (3) FBC-14 RESIDENTIAL.
  
 6) THE 9" TRANSFER DUCT FROM BEDROOM 1 IS UNDERSIZED.
 THE MINIMUM SIZE MUST BE 10" PER SECTION M1602.4 FBC-14
 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-04 Cont ID  
Sent By ccole Date 2016-11-04 Time 07:34 Rev Time 0.00
Received By ccole Date 2016-11-03 Time 17:25 Sent To  
Notes
2016-11-04 08:15:041ST REVIEW FBC-2014 RESIDENTIAL, ENERGY CONSERVATION
 PERMIT #16091117
 10/31/16
  
 1) THE AC PLAN ON A-2 AND THE AC SIZING CALCULATIONS
 MUST BEAR THE SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
 PLEASE NOTE THAT ONLY FL. LICENSED DESIGN PROFESSIONALS
 OR INSTALLING AC CONTRACTORS ARE PERMITTED TO DRAW AC
 PLANS PER SECTION 105.3.1.2
  
 2) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN-
 SECTION R403.6.1 FBC-14 ENERGY CONSERVATION
  
 3) INDICATE THE BRANCH DUCT AND DIFFUSER SIZES- ONLY
 THE MAIN TRUCKS HAVE BEEN SIZED- SECTION 107.3.5.1.4.
  
 4) SHOW THE CONDENSATE PIPING RUN AND DISPOSAL
 LOCATION- SECTION M1411.3 FBC- RESIDENTIAL.
  
 5) SHOW THE DRYER VENT RUN AND TERMINATION LOCATION.
 INDICATE THE TYPE AND SIZE OF VENT AND VENT CAP-
 SECTION M1502.
  
 6) INDICATE THE TYPE OF KITCHEN EXHAUST TO BE INSTALLED
 AND PROVIDE SPECIFICATIONS- REFER TO SECTION M1503-
 M1507 FBC-RESIDENTIAL.
  
 7) PROVIDE A NUMBER FOR EACH BEDROOM- 1,2,3, OR 4 ON
 THE FLOOR PLAN SO THE PLAN MATCHES THE MANUAL J
 WORKSHEETS.
  
 8) THE DIRECTIONAL ORIENTATIONS SHOWN IN THE MANUAL J
 WORKSHEETS FOR WINDOWS AND DOORS DO NOT APPEAR TO MATCH
 THEIR DIRECTIONAL ORIENTATIONS ON THE PLAN.
  
 9) SHOW THE LOCATION OF THE AC CONDENSER AND PROVIDE
 DETAILS FOR INSTALLATION OF THE MOUNTING PAD AND
 ANCHORING THE CONDENSER- SECTIONS M1305.1.4.1, AND
 M1401.4.
  
 10) ENERGY FORM R405-2014:
  
 A) PLEASE FILL IN ALL THE REQUESTED INFORMATION AT THE
 TOP OF PAGE 1- OWNER, BUILDER NAME, PERMIT OFFICE,
 PERMIT NUMBER, JURISDICTION. CORRECT THE CLIMATE ZONE 2
 DESIGNATION TO 1A PER TABLE R301.1.
  
 B) THE SUBMITTED ENERGY FORM IS INDICATING A "WORST
 CASE" COMPLIANCE, HOWEVER A WORST CASE COMPLIANCE IS
 USED FOR MODEL HOMES AND NOT FOR INDIVIDUAL RESIDENCES
 AS NOTED IN SECTION R405.4.2 EXCEPTION, ENERGY
 CONSERVATION. PLEASE CORRECT PAGE 1 AND PAGE 4, AND
 REVISE THE WINDOW ORIENTATIONS SO THEY MATCH WITH THE
 ORIENTATIONS TO BE SHOWN ON THE CORRECTED MANUAL J
 WORKSHEETS.
  
 C) COMPLETE THE AIR BARRIER AND INSULATION INSPECTION
 CHECKLIST AND ALL REQUIRED INFORMATION AT THE TOP OF
 THE PAGE- OWNER, BUILDER NAME, PERMIT OFFICE, PERMIT
 NUMBER, JURISDICTION.
  
 11) PLEASE SUBMIT TWO SETS OF CORRECTED PLANS PER
 SECTION 107.1 WPB AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-11-29 Cont ID  
Sent By gjohnson Date 2016-11-29 Time 16:46 Rev Time 0.00
Received By gjohnson Date 2016-11-29 Time 16:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-10-24 Cont ID  
Sent By gjohnson Date 2016-10-24 Time 14:37 Rev Time 0.00
Received By gjohnson Date 2016-10-24 Time 14:16 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2016-10-27 Cont ID  
Sent By cthroop Date 2016-10-27 Time 15:00 Rev Time 0.00
Received By cthroop Date 2016-10-27 Time 14:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-12-07 Cont ID  
Sent By   Date 2016-12-07 Time   Rev Time 0.00
Received By awooten Date 2016-12-07 Time 14:38 Sent To  
Notes
2016-12-07 14:38:39***ZONING PROVISO***
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE FOLLOWING CONDITIONS SHALL BE ADDRESSED:
  
 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN,
 SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REIEW.
 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.
  
 PLEASE CONTACT ALANA WOOTEN 561-822-1449 WITH ANY
 QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2016-10-13 Cont ID  
Sent By awooten Date 2016-10-12 Time   Rev Time 0.00
Received By awooten Date 2016-10-12 Time 09:17 Sent To  
Notes
2016-10-13 09:17:16*****ZONING FAILED******
  
 LANDSCAPING:
  
 GENERAL LANDSCAPING STANDARDS FOR SINGLE-FAMILY
 DWELLING UNITS SHALL BE AS FOLLOWS:
  
 A. SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
 PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PLAN WITH TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 A CONDITIONAL APPROVAL CAN BE ISSUED THROUGH THE ZONING
 AND PLANNING DIVISION. AS A PART OF THE APPROVAL THE
 OWNER MUST AGREE TO THE FOLLOWING:
  
 1) PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 FOR THE NEW SINGLE FAMILY RESIDENCE AT _______:
 A. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN
 IN COMPLIANCE WITH THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR) ARTICLE XIV, SHALL BE SUBMITTED TO
 THE BUILDING DIVISION FOR REVIEW.
 B. AN IRRIGATION PERMIT SHALL BE SUBMITTED TO THE
 BUILDING DIVISION FOR REVIEW.
 C. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION (502).
 D. THE IRRIGATION SHALL BE INSTALLED IN ACCORDANCE WITH
 THE APPROVED IRRIGATION PERMIT AND PASS A PLUMBING
 FINAL INSPECTION (703).
  
 PLEASE CONTACT THE PLANNING DIVISION AT (561) 822-1435
 FOR MORE INFORMATION.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 PLEASE LET ME KNOW IF YOU HAVE ANY QUESTIONS.
  