Review Stop P PLUMBING
Rev No 3 Status P Date 2017-01-05 Cont ID  
Sent By tklarge Date 2017-01-05 Time 06:26 Rev Time 0.00
Received By tklarge Date 2017-01-05 Time 06:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-12-22 Cont ID  
Sent By tklarge Date 2016-12-22 Time 08:55 Rev Time 0.00
Received By tklarge Date 2016-12-22 Time 06:41 Sent To  
Notes
2016-12-22 08:59:18THE HOT WATER PIPING IS MISSING FROM THE WATER RISER
 DIAGRAM.WPB AMEND. TO FBC SEC. 107.3.5.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-10-04 Cont ID  
Sent By tklarge Date 2016-10-04 Time 12:30 Rev Time 0.00
Received By tklarge Date 2016-10-04 Time 05:15 Sent To  
Notes
2016-10-04 11:35:321) INDICATE ON THE PLAN WHAT PLUMBING/ PIPING IS
 EXISTING AND WHAT IS NEW. THE ORIGINAL PLANS SHOWED THE
 PLUMBING AS EXISTING. ONLY THE BREAK ROOM SINK AND
 DRINKING FOUNTAIN APPEARED TO BE NEW. CLARIFY.
 2) INDICATE THE WALL FINISH IN THE TOILET /BATHING
 ROOMS. COMPLY WITH FBC SEC. 1210.2.2.
 3) THE BREAKROOM SINK SHALL COMPLY WITH SECS. 212.2,
 212.3, 606 OF 2014 FAC.
 4) A SERVICE SINK IS REQUIRED PER THE FPC TABLE 403.1.
 THERE WAS A SERVICE SINK PREVIOUSLY IN THIS STRUCTURE
 AND IT HAS BEEN REMOVED, CREATING A VIOLATION.
 5) INDICATE ON THE PLAN IF THE WATER HEATER IS NEW OR
 AN EXISTING ONE BEING RELOCATED. WPB AMEND. TO FBC SEC.
 107.2.1.
 6) INDICATE ON THE PLAN THE PURPOSE OF THE HUB
 DRAIN.WHAT IS DRAINING INTO IT? IT WILL REQUIRE A TRAP
 PRIMER PER THE FPC SEC.1002.4.
 7) SUBMIT ELEVATION DETAILS OF THE SHOWERS. THEY SHALL
 COMPLY WITH FL. ACCESS. CODE SECS.608, 609, 610.
 8) SHOW THE SHOWER DIMENSIONS (LXW) ON THE PLANS.
 COMPLY WITH FAC SEC.608.2.1.
 9) THE APPLICATION STATES"PLUMBING AS PER PLANS." THE
 ORIGINAL PLANS DID NOT CONTAIN ANY PLUMBING DRAWINGS
 AND A PLUMBING REVIEW WAS NEVER PERFORMED ON THE PLANS.
 CLARIFY.
 10) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE TOILET
 ROOM/BATHING ROOMS.
 11) SHT. P-2 - RESTROOM REFERENCE NOTE #3 REFERS TO
 RESTROOMS # 104 & #106. THERE ARE NO SUCH RESTROOMS ON
 THE PLANS. CLARIFY.
 12) CLEANOUTS ARE REQUIRED IN THE WASTE STACKS PERR THE
 FPC SEC. 708.3.4.
 13) SIZE ALL THE VENTS ON THE SANITARY RISER DIAGRAM.
 14) THE WATER RISER IS INCOMPLETE.THERE ARE LINES
 MISSING (HOT WATER).
 15) SIZE ALL SECTIONS OF THE WATER RISER. WPB AMEND. TO
 FBC SEC. 107.2.1.
 16) THE MINIMUM SIZE OF THE COLD WATER SUPPLY TO THE
 WATER HEATER SHALL BE 3/4 INCH.
 17) THE WATER HEATER REQUIRES A PAN AND PAN DRAIN. THE
 PAN DRAIN SHALL TERMINATE IN ACCORDANCE WITH FPC
 SEC.504.7.2.
 18) SHOW THE FIXTURE CLEARANCES OF THE FIXTURES IN THE
 TOILET ROOMS. COMPLY WITH FAC CHAPTER 6 AND FPC SEC.
 405.
 19) PLACE THE TYPE OF OCCUPANCY AND OCCUPANT LOAD ON
 THE PLANS PER THE FBC SEC. 302 AND TABLE 1004.1.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW