Plan Review Details - Permit 16091062
Plan Review Stops For Permit 16091062
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-10-04 Cont ID  
Sent By tklarge Date 2016-10-04 Time 03:13 Rev Time 0.00
Received By tklarge Date 2016-10-04 Time 03:02 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By tklarge Date 2016-10-03 Time 06:42 Rev Time 0.00
Received By tklarge Date 2016-10-03 Time 06:27 Sent To  
Notes
2016-10-03 06:42:421)SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE DRYER
 AND THE RANGE PER THE 2014 FBC-FUEL GAS CODE SEC.304.1
 OR 2014 FBC-RES. SEC. G 2407.
 2) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, AND FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR
 2014 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE
 LISTED AND LABELED. THE INSTALLATION MANUALS FOR ALL
 GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME
 OF INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 3) SHOW THE LOCATION AND DISTANCE OF ANY OPERABLE
 WINDOWS AND DOORS FROM THE TANKLESS WATER HEATER. THE
 LOCATION OF THE TANKLESS WATER HEATER SHALL COMPLY WITH
 THE MANUFACTURER'S INSTALLATION INSTRUCTONS.
 4) SHOW THE TYPE OF PIPE AND PIPE SIZE ON THE
 CONSUMER'S SIDE OF THE GAS METER.
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-04 Cont ID  
Sent By tklarge Date 2016-10-04 Time 03:13 Rev Time 0.00
Received By tklarge Date 2016-10-04 Time 03:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-03 Cont ID  
Sent By tklarge Date 2016-10-03 Time 06:42 Rev Time 0.00
Received By tklarge Date 2016-09-29 Time 11:19 Sent To  
Notes
2016-09-30 11:19:54PLUMB <5K