Plan Review Details - Permit 16090944
Plan Review Stops For Permit 16090944
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-04 Cont ID  
Sent By jgomez Date 2016-10-04 Time 13:35 Rev Time 0.00
Received By jgomez Date 2016-10-04 Time 13:32 Sent To  
Notes
2016-10-04 13:33:16TALKED TO CONTRACTOR (BILL AHO FROM A&H SERVICES) AND
 HAROLD MOSER. FILED INSPECTION REQUIRED TO VERIFY
 BALANCED RETURN AIR. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-28 Cont ID  
Sent By jgomez Date 2016-09-28 Time 09:05 Rev Time 0.00
Received By jgomez Date 2016-09-26 Time 10:04 Sent To  
Notes
2016-09-27 10:04:15REVISION ROUTED TO JGOMEZ

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-10-04 Cont ID  
Sent By jgomez Date 2016-10-04 Time 13:37 Rev Time 0.00
Received By jgomez Date 2016-10-04 Time 13:35 Sent To  
Notes
2016-10-04 13:41:36TALKED TO CONTRACTOR (BILL AHO FROM A&H SERVICES) AND
 HAROLD MOSER. FILED INSPECTION REQUIRED TO VERIFY
 BALANCED RETURN AIR. JG.
  
  
 MECHANICAL REVIEW APPROVED WITH PROVISO:
  
 1- SINCE MASTER BEDROOM TRANSFER DUCT SIZE SPECIFIED ON
 PLANS DOESN'T COMPLY WITH THE EXCEPTIONS OF SEC.
 M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014), THEN,
 FIELD VERIFICATION REQUIRED FOR THE BALANCED RETURN
 AIR.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-28 Cont ID  
Sent By jgomez Date 2016-09-28 Time 09:30 Rev Time 0.00
Received By jgomez Date 2016-09-28 Time 09:05 Sent To  
Notes
2016-09-28 09:38:42RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- SIZE OF TRANSFER DUCT SHOWN FOR THE MASTER BEDROOM
 DOESN'T COMPLY WITH THE BALANCED RETURN AIR SEC.
 M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS
 REQUIRED. NOTE: NEED TO CONSIDER ALL THE SUPPLY AIR
 INTO THE MASTER BEDROOM, INCLUDING BATHROOM AND
 CLOSETS. SEE EXCEPTION #3 ON SEC. M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 2- SPECIFY SIZE OF TRANSFER DUCT FOR BEDROOM #2. SEC.
 M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]