Plan Review Details - Permit 16090944
Plan Review Stops For Permit 16090944 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-10-04 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2016-10-04 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2016-10-04 |
Time |
13:32 |
Sent To |
|
|
Notes |
2016-10-04 13:33:16 | TALKED TO CONTRACTOR (BILL AHO FROM A&H SERVICES) AND | | HAROLD MOSER. FILED INSPECTION REQUIRED TO VERIFY | | BALANCED RETURN AIR. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-09-28 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2016-09-28 |
Time |
09:05 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2016-09-26 |
Time |
10:04 |
Sent To |
|
|
Notes |
2016-09-27 10:04:15 | REVISION ROUTED TO JGOMEZ |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2016-10-04 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2016-10-04 |
Time |
13:37 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2016-10-04 |
Time |
13:35 |
Sent To |
|
|
Notes |
2016-10-04 13:41:36 | TALKED TO CONTRACTOR (BILL AHO FROM A&H SERVICES) AND | | HAROLD MOSER. FILED INSPECTION REQUIRED TO VERIFY | | BALANCED RETURN AIR. JG. | | | | | | MECHANICAL REVIEW APPROVED WITH PROVISO: | | | | 1- SINCE MASTER BEDROOM TRANSFER DUCT SIZE SPECIFIED ON | | PLANS DOESN'T COMPLY WITH THE EXCEPTIONS OF SEC. | | M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014), THEN, | | FIELD VERIFICATION REQUIRED FOR THE BALANCED RETURN | | AIR. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-09-28 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2016-09-28 |
Time |
09:30 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2016-09-28 |
Time |
09:05 |
Sent To |
|
|
Notes |
2016-09-28 09:38:42 | RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- SIZE OF TRANSFER DUCT SHOWN FOR THE MASTER BEDROOM | | DOESN'T COMPLY WITH THE BALANCED RETURN AIR SEC. | | M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS | | REQUIRED. NOTE: NEED TO CONSIDER ALL THE SUPPLY AIR | | INTO THE MASTER BEDROOM, INCLUDING BATHROOM AND | | CLOSETS. SEE EXCEPTION #3 ON SEC. M1602.4 | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | 2- SPECIFY SIZE OF TRANSFER DUCT FOR BEDROOM #2. SEC. | | M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|
|
|