Plan Review Details - Permit 16090860
Plan Review Stops For Permit 16090860
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-05-03 Cont ID  
Sent By jwitmer Date 2017-05-03 Time 11:44 Rev Time 0.00
Received By jwitmer Date 2017-05-03 Time 11:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-03-23 Cont ID  
Sent By jwitmer Date 2017-03-23 Time 14:03 Rev Time 0.00
Received By jwitmer Date 2017-03-23 Time 12:26 Sent To  
Notes
2017-03-23 14:02:58BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16090860
 ADD: 1301 SUMMIT BLVD/ LORIKEET BIRD EXHIBIT
 CONT: GAST
 TEL: 561-281-1001
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. MARCH 23/2017
 ACTION: DENIED
  
 1) 2ND REQUEST. THE (3) SUBMITTED SOILS REPORTS WERE
 COPIES OF SIGNED AND SEALED REPORTS. PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE
 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER
 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
  
 PLEASE NOTE THIS PROJECT IS LOCATED IN A QUESTIONABLE
 SOILS AREA, PLEASE PROVIDE SIGNED & SEALED ORIGINAL
 SOILS REPORTS MINIMUM OF 2 REPORTS. 2014 FBC-B W/ 2016
 SUPPLEMENTS, 1803.5.2 QUESTIONABLE SOIL.
  
 2) 2ND REQUEST. THIS PROPERTY IS ALSO LOCATED IN A
 FLOOD ZONE. FBC BUILDING 1612 AND CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A 7" FLOOD ZONE, BFE ELEVATION 12 FEET NGVD. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED. THE CITY OF
 WEST PALM BEACH IS STILL USING THE 1929 NGVD ELEVATION
 DATUM. NO FIS FOR THIS LOCATION.
 IMPORTANT CHANGE!!!!
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL (1FOOT) FREEBOARD OF ELEVATION.
 CITY ORDINANCE CHANGE SEPT. 12/2016. PLEASE ALSO NOTE
 FOR FUTURE WORK IN THE CITY?S FLOOD ZONE AREAS, THE
 CITY COMMISSION & MAYOR WILL BE CHANGING THE FREEBOARD
 REQUIREMENTS TO (2 FOOT) FREEBOARD IN THE UPCOMING
 MONTHS. ALSO ON ALL FLOOD ZONE CERTIFICATES THE
 LATITUDE AND LONGITUDE ARE TO BE FILLED OUT WITH THE
 FRONT CENTER OF THE STRUCTURE BEING THE POINT GIVEN.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (2.1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF
 THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH
 FLOOR HEIGHT. 107.2.5.1 DESIGN FLOOD ELEVATIONS.
 107.3.5.1.1(1) MINIMUM PLAN REVIEW COMMERCIAL
 BUILDINGS. FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN
 FLOOD ELEVATIONS.
  
 (2.2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. REQUIRED
 INSPECTIONS. 110.3.( 1.2.) IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT,
 AND PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE
 ELEVATION CERTIFICATION, REQUIRED IN SECTION 1612.5,
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL.
  
 (2.3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS. REQUIRED INSPECTIONS. 110.3.( 6.) FINAL
 INSPECTION. TO BE MADE AFTER THE BUILDING IS COMPLETED
 AND READY FOR OCCUPANCY.6.1. LOWEST FLOOR ELEVATION. IN
 FLOOD HAZARD AREAS, AS PART OF THE FINAL INSPECTION, A
 FINAL CERTIFICATION OF THE LOWEST FLOOR ELEVATION SHALL
 BE SUBMITTED TO THE AUTHORITY HAVING JURISDICTION.
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 3) COMPLIED.
  
 4A) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4B) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (C) PANEL WALLS:, WALL LOUVERS,
 (D) COMPLIED. ROOFING PRODUCTS AND ASSEMBLIES
  
 5) COMPLIED. IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-22 Cont ID  
Sent By jwitmer Date 2016-10-22 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2016-10-21 Time 15:27 Sent To  
Notes
2016-10-22 09:14:06BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16090860
 ADD: 1301 SUMMIT BLVD/ LORIKEET BIRD EXHIBIT
 CONT: GAST
 TEL: 561-281-1001
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: SAT. OCT 22/2016
 ACTION: DENIED
  
 1) PLEASE NOTE THIS PROJECT IS LOCATED IN A
 QUESTIONABLE SOILS AREA, PLEASE PROVIDE SIGNED & SEALED
 ORIGINAL SOILS REPORTS MINIMUM OF 2 REPORTS. 2014 FBC-B
 W/ 2016 SUPPLEMENTS, 1803.5.2 QUESTIONABLE SOIL.
  
 2) THIS PROPERTY IS ALSO LOCATED IN A FLOOD ZONE. FBC
 BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A 7" FLOOD
 ZONE, BFE ELEVATION 12 FEET NGVD. A FLOOD ELEVATION
 CERTIFICATE WILL BE REQUIRED. THE CITY OF WEST PALM
 BEACH IS STILL USING THE 1929 NGVD ELEVATION DATUM. NO
 FIS FOR THIS LOCATION.
 IMPORTANT CHANGE!!!!
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL (1FOOT) FREEBOARD OF ELEVATION.
 CITY ORDINANCE CHANGE SEPT. 12/2016. PLEASE ALSO NOTE
 FOR FUTURE WORK IN THE CITY?S FLOOD ZONE AREAS, THE
 CITY COMMISSION & MAYOR WILL BE CHANGING THE FREEBOARD
 REQUIREMENTS TO (2 FOOT) FREEBOARD IN THE UPCOMING
 MONTHS. ALSO ON ALL FLOOD ZONE CERTIFICATES THE
 LATITUDE AND LONGITUDE ARE TO BE FILLED OUT WITH THE
 FRONT CENTER OF THE STRUCTURE BEING THE POINT GIVEN.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (2.1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF
 THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH
 FLOOR HEIGHT. 107.2.5.1 DESIGN FLOOD ELEVATIONS.
 107.3.5.1.1(1) MINIMUM PLAN REVIEW COMMERCIAL
 BUILDINGS. FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN
 FLOOD ELEVATIONS.
  
 (2.2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. REQUIRED
 INSPECTIONS. 110.3.( 1.2.) IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT,
 AND PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE
 ELEVATION CERTIFICATION, REQUIRED IN SECTION 1612.5,
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL.
  
 (2.3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS. REQUIRED INSPECTIONS. 110.3.( 6.) FINAL
 INSPECTION. TO BE MADE AFTER THE BUILDING IS COMPLETED
 AND READY FOR OCCUPANCY.6.1. LOWEST FLOOR ELEVATION. IN
 FLOOD HAZARD AREAS, AS PART OF THE FINAL INSPECTION, A
 FINAL CERTIFICATION OF THE LOWEST FLOOR ELEVATION SHALL
 BE SUBMITTED TO THE AUTHORITY HAVING JURISDICTION.
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
 3A) SHEET A-101 ON THE RIGHT SIDE OF THIS SHEET THE
 PLANS HAVE AN EGRESS LEGEND FOR MAIN EGRESS PLAN AND
 THE SECONDARY EGRESS PLAN. PLEASE NOTE THE PLANS DO NOT
 INDICATE ANY MAIN OR SECONDARY EGRESS REQUIREMENTS.
 FBC-B TABLE 1014.3 FOR AN ASSEMBLY OCCUPANCY COMMON
 PATH OF TRAVEL IS 75 FEET WITHOUT FIRE SPRINKLERS. NOTE
 IF 2 EGRESSES ARE REQUIRED BECAUSE THE COMMON PATH OF
 TRAVEL IS EXCEEDED THEN THEY MUST BE ? THE DIAGONAL
 DISTANCE APART. SEE 1015.2.1. FBC-B 2014 W/2016
 UPDATES.
  
 3B) SHEET A-101 DETAIL # 4 & SHEET S4.0 DETAILS 6-10
 ALL SHOW SPACED PURLINS AND NOT SOLID PLYWOOD
 SHEATHING. FBC-B REQUIRES STRUCTURAL ROOF SHEATHING.
  
 3C) SHEET A-101 DETAIL # 4 & SHEET S4.0 DETAILS 6-10 DO
 NOT INDICATE THE TYPE OF METAL ROOF SYSTEM IS TO BE
 APPLIED. SHEET A-200 NOTE #1 INDICATES THE ROOF SYSTEM
 IS TO BE A METAL CORRUGATED GALVANIZED METAL ROOF
 SYSTEM, NO MENTION OF GAUGE, PRODUCT APPROVAL IF THIS
 SYSTEM IS ARCHITECTURAL REQUIRING SOLID ROOF SHEATHING
 BENEATH OR IF THIS ROOFING SYSTEM IS A STRUCTURAL ROOF
 PANEL SYSTEM. NOTE IF THE SYSTEM IS TO BE A STRUCTURAL
 ROOF PANEL SYSTEM AND IS TO BE ATTACHED TO WOOD FRAMING
 MEMBERS THE VALUES FOR THE FASTENERS IN THE PRODUCT
 APPROVAL WILL ALSO NEED REFLECT TESTING IN THE SAME
 TYPE OF SPECIES OF LUMBER AND GRADE. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3D) SHEET A-101 DETAIL # 4 & SHEET S4.0 DETAILS 6-10,
 THERE IS A DISCREPANCY IN PLANS, THE SHEET A-101 DETAIL
 # 4 SHOWS 2 X4 PURLINS WITHIN THE BUILDING, SPACING
 UNKNOWN WHEREAS THE S-4.0 SHEET DETAILS 6-10 ALL SHOW 2
 INCH DIAMETER PURLINS, SPACING UNKNOWN. PLEASE SHOW
 COMPLIANCE WITH 2308.10.5 PURLINS OF THE FBC-B THE
 MAXIMUM SPAN OF 2-INCH BY 4-INCH (51 MM BY 102 MM)
 PURLINS SHALL BE 4 FEET (1219 MM). THE MAXIMUM SPAN OF
 THE 2-INCH BY 6-INCH (51 MM BY 152 MM) PURLIN SHALL BE
 6 FEET (1829 MM), BUT IN NO CASE SHALL THE PURLIN BE
 SMALLER THAN THE SUPPORTED RAFTER.
  
 3E) SHEET S4 DETAIL # 7 IS SHOWING A GABLE PORTION OF
 ROOF FRAMING AND SHED TYPE FRAMING THAT ATTACH TO A 8
 INCH HORIZONTAL WOOD BEAM. PLEASE SEE THE SHED ROOF
 FRAMING 4 INCH DIAMETER FRAMING MEMBERS ARE ATTACHED TO
 THE 8 INCH WOOD BEAM WITH ? X 8 INCH LAG SCREWS,
 WHEREAS THE GABLE END ROOF FRAMING IS CUT TO SIT ON TOP
 OF THE SHED ROOF FRAMING MEMBERS TAPERED TO NOTHING AND
 SCREWED INTO THE SHED ROOF FRAMING MEMBERS WITH 4 INCH
 WOOD SCREWS, THE DIAMETER UNKNOWN? THE GABLE ROOF
 FRAMING MEMBER SHOULD TIE IN DIRECTLY TO THE 8 INCH
 WOOD BEAM( EQUIVALENT TO THE DOUBLE TOP PLATE) NOT A
 TAPERED CUT WITH LESS VALUE IN THE FRAMING. SEE 2014
 FBC-B 2308.10.1.
  
 3F) PLEASE PROVIDE THE VALUE OF THE 8 INCH LAG SCREW
 FOR WITHDRAW (UPLIFT) VALUES FOR THE TYPE OF WOOD
 PURPOSED. PLEASE PROVIDE THE REQUIRED VALUES TO RESIST
 UPLIFT FOR EACH OF THE FRAMING MEMBERS SINCE THESE ARE
 NOT TRUSSES BUT ROOF RAFTERS/ JOIST THAT APPEAR WILL BE
 CUT ON THE JOB. SHOW COMPLIANCE WITH
 FBC-B 2308.10.1 WIND UPLIFT. THE ROOF CONSTRUCTION
 SHALL HAVE RAFTER AND TRUSS TIES TO THE WALL BELOW.
 RESULTANT UPLIFT LOADS SHALL BE TRANSFERRED TO THE
 FOUNDATION USING A CONTINUOUS LOAD PATH. THE RAFTER OR
 TRUSS TO WALL CONNECTION SHALL COMPLY WITH TABLES
 2304.9.1 AND 2308.10.
  
 3G) SHEET S4 DETAILS 9 & 10 ARE MISSING A RIDGE BOARD
 INCOMPLIANCE WITH FBC-B 2308.10.4. 2308.10.4 CEILING
 JOIST AND RAFTER FRAMING. RAFTERS SHALL BE FRAMED
 DIRECTLY OPPOSITE EACH OTHER AT THE RIDGE. THERE SHALL
 BE A RIDGE BOARD AT LEAST 1-INCH (25 MM) NOMINAL
 THICKNESS AT RIDGES AND NOT LESS IN DEPTH THAN THE CUT
 END OF THE RAFTER. AT VALLEYS AND HIPS, THERE SHALL BE
 A SINGLE VALLEY OR HIP RAFTER NOT LESS THAN 2-INCH (51
 MM) NOMINAL THICKNESS AND NOT LESS IN DEPTH THAN THE
 CUT END OF THE RAFTER.
  
 4A) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4B) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (C) PANEL WALLS:, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-14 Cont ID  
Sent By rlecky Date 2017-03-14 Time 11:41 Rev Time 0.00
Received By rlecky Date 2017-03-14 Time 10:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-29 Cont ID  
Sent By albarran Date 2016-09-29 Time 20:00 Rev Time 0.00
Received By albarran Date 2016-09-29 Time 19:05 Sent To  
Notes
2016-09-29 20:01:02ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB ADDRESS: 1301 SUMMIT BLVD.
 DESCRIPTION: CONSTRUCTION OF LORIKEET BIRD EXHIBIT TO
 INCLUDE SITE WORK CMU STRUCTURES, MECHANICAL,
 ELECTRICAL, ROOFING, ANIMAL CAGING
 MASTER PERMIT: 16090860
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL
 EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO
 REQUIRE SERVICE WHILE ENERGIZED SHALL BE FIELD MARKED
 TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS.
 2. NEC 110.24: THE MAXIMUM AVAILABLE FAULT CURRENT
 SHALL BE DURABLY MARKED AND DATED ON ALL NON-DWELLING
 ELECTRICAL APPARATUS.
 3. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT
 SHALL NOT BE CONTROLLED BY AUTOMATIC MEANS ONLY.
 4. NEC 215.5 DIAGRAMS OF FEEDERS. A RISER DIAGRAM
 SHOWING FEEDER DETAILS ALONG WITH RESPECTIVE LOAD CALCS
 SHALL BE PROVIDED. THIS DIAGRAM SHALL INCLUDE CONDUCTOR
 SIZING AND INSULATION TYPE. FURTHERMORE, IT SHALL BE
 SITE SPECIFIC. THE SUBMITTED RISER DIAGRAM IS
 INCOMPLETE.
 5. PROVIDE LOAD CALCS AND CIRCUIT DIRECTORY FOR PANEL X
 AND INCLUDE THAT IN THE ABOVE MENTIONED SERVICE LOAD
 CALCS.
 6. FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER
 OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM
 OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR
 A MAXIMUM OF 3% VOLTAGE DROP. SUBMIT VOLTAGE DROP
 CALCULATIONS FOR ALL FEEDERS. SHOW THE VARIOUS
 DISTANCES ON THE PLAN.
 7. FBC-EC405.2.4 EXTERIOR LIGHTING. LIGHTING NOT
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTO SENSOR
 AND A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH.
 LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR PHOTO
 SENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS.
 8. FBC-EC405.2.2.2 OCCUPANCY SENSORS. OCCUPANCY SENSORS
 SHALL BE INSTALLED IN ALL CLASSROOMS,
 CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK
 ROOMS, PRIVATE OFFICES, RESTROOMS, STORAGE ROOMS AND
 JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEET
 (28 M2) OR LESS ENCLOSED BY FLOOR-TO-CEILING HEIGHT
 PARTITIONS. THESE AUTOMATIC CONTROL DEVICES SHALL BE
 INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS WITHIN 30
 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND SHALL
 EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO
 AUTOMATICALLY TURN THE LIGHTING ON TO NOT MORE THAN 50
 PERCENT POWER.
 9. CORRECT PANEL DP CIRCUIT DIRECTORY TO INCLUDE PANEL
 LH.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-10-12 Cont ID  
Sent By pleduc Date 2016-10-12 Time   Rev Time 0.00
Received By pleduc Date 2016-10-05 Time 16:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-03 Cont ID  
Sent By   Date 2017-05-03 Time   Rev Time 0.00
Received By lmarchan Date 2017-04-21 Time 14:57 Sent To  
Notes
2017-04-24 14:57:33RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-23 Cont ID  
Sent By ccole Date 2017-03-23 Time 17:15 Rev Time 0.00
Received By ccole Date 2017-03-09 Time 16:45 Sent To  
Notes
2017-03-09 16:45:16C40

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-28 Cont ID  
Sent By jroach Date 2016-10-28 Time 11:56 Rev Time 0.00
Received By jroach Date 2016-09-22 Time 12:45 Sent To  
Notes
2016-09-26 12:45:34C36

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-03-23 Cont ID  
Sent By jwitmer Date 2017-03-23 Time 14:03 Rev Time 0.00
Received By jwitmer Date 2017-03-23 Time 14:03 Sent To  
Notes
2017-03-23 14:05:48PALM BEACH COUNTY IMPACT FEES
 RECEIPT NUMBER 2016-1130-198
 TRACKING NUMBER MU-2016-027298-0000
 AMOUNT $227.72.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-10-22 Cont ID  
Sent By jwitmer Date 2016-10-22 Time 09:16 Rev Time  
Received By jwitmer Date 2016-10-22 Time 07:00 Sent To  
Notes
2016-10-22 09:15:08BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-23 Cont ID  
Sent By ccole Date 2017-03-23 Time 17:15 Rev Time 0.00
Received By ccole Date 2017-03-23 Time 17:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-04 Cont ID  
Sent By ccole Date 2016-10-04 Time 07:22 Rev Time 0.00
Received By ccole Date 2016-10-04 Time 07:22 Sent To  
Notes
2016-10-04 07:28:441ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090860
 10/4/16
  
 1) SUBMIT A FL. PRODUCT APPROVAL AND/OR A MIAMI-DADE
 NOA FOR THE FAN LOUVER AND HOOD- DCA RULE 9N-03.
 PROVIDE ATTACHMENT DETAILS FOR THE FAN SUPPORT BRACKET.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status P Date 2017-05-03 Cont ID  
Sent By jwitmer Date 2017-05-03 Time 11:41 Rev Time 0.00
Received By jwitmer Date 2017-05-03 Time 11:41 Sent To  
Notes
2017-05-03 11:44:08A7 FLOOD ZONE, BASE FLOOD OF 12.0' + 1-0" FREEBOARD
 REQUIRED, SUBMITTED CONSTRUCTION DRAWING ELEVATION
 CERTIFICATE FINISH FLOOR TO BE 13.5' NGVD.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2017-03-23 Cont ID  
Sent By jwitmer Date 2017-03-23 Time 14:06 Rev Time 0.00
Received By jwitmer Date 2017-03-23 Time 14:06 Sent To  
Notes
2017-03-23 14:07:00NATIONAL FLOOD INSURANCE PROGRAM (NFIP)
 W. P. B. PERMIT: 16090860
 ADD: 1301 SUMMIT BLVD/ LORIKEET BIRD EXHIBIT
 CONT: GAST
 TEL: 561-281-1001
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. MARCH 23/2017
 ACTION: DENIED
  
 1) THIS PROPERTY IS ALSO LOCATED IN A FLOOD ZONE. FBC
 BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A 7" FLOOD
 ZONE, BFE ELEVATION 12 FEET NGVD. A FLOOD ELEVATION
 CERTIFICATE WILL BE REQUIRED. THE CITY OF WEST PALM
 BEACH IS STILL USING THE 1929 NGVD ELEVATION DATUM. NO
 FIS FOR THIS LOCATION.
 IMPORTANT CHANGE!!!!
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL (1FOOT) FREEBOARD OF ELEVATION.
 CITY ORDINANCE CHANGE SEPT. 12/2016. PLEASE ALSO NOTE
 FOR FUTURE WORK IN THE CITY?S FLOOD ZONE AREAS, THE
 CITY COMMISSION & MAYOR WILL BE CHANGING THE FREEBOARD
 REQUIREMENTS TO (2 FOOT) FREEBOARD IN THE UPCOMING
 MONTHS. ALSO ON ALL FLOOD ZONE CERTIFICATES THE
 LATITUDE AND LONGITUDE ARE TO BE FILLED OUT WITH THE
 FRONT CENTER OF THE STRUCTURE BEING THE POINT GIVEN.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (2.1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF
 THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH
 FLOOR HEIGHT. 107.2.5.1 DESIGN FLOOD ELEVATIONS.
 107.3.5.1.1(1) MINIMUM PLAN REVIEW COMMERCIAL
 BUILDINGS. FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN
 FLOOD ELEVATIONS.
  
 (2.2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. REQUIRED
 INSPECTIONS. 110.3.( 1.2.) IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT,
 AND PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE
 ELEVATION CERTIFICATION, REQUIRED IN SECTION 1612.5,
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL.
  
 (2.3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS. REQUIRED INSPECTIONS. 110.3.( 6.) FINAL
 INSPECTION. TO BE MADE AFTER THE BUILDING IS COMPLETED
 AND READY FOR OCCUPANCY.6.1. LOWEST FLOOR ELEVATION. IN
 FLOOD HAZARD AREAS, AS PART OF THE FINAL INSPECTION, A
 FINAL CERTIFICATION OF THE LOWEST FLOOR ELEVATION SHALL
 BE SUBMITTED TO THE AUTHORITY HAVING JURISDICTION.
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2016-10-22 Cont ID  
Sent By jwitmer Date 2016-10-22 Time 09:27 Rev Time 0.00
Received By jwitmer Date 2016-10-22 Time 07:00 Sent To  
Notes
2016-10-22 09:17:30NATIONAL FLOOD INSURANCE PROGRAM (NFIP)
 W. P. B. PERMIT: 16090860
 ADD: 1301 SUMMIT BLVD/ LORIKEET BIRD EXHIBIT
 CONT: GAST
 TEL: 561-281-1001
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: SAT. OCT 22/2016
 ACTION: DENIED
  
 1) THIS PROPERTY IS ALSO LOCATED IN A FLOOD ZONE. FBC
 BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A 7" FLOOD
 ZONE, BFE ELEVATION 12 FEET NGVD. A FLOOD ELEVATION
 CERTIFICATE WILL BE REQUIRED. THE CITY OF WEST PALM
 BEACH IS STILL USING THE 1929 NGVD ELEVATION DATUM. NO
 FIS FOR THIS LOCATION.
 IMPORTANT CHANGE!!!!
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL (1FOOT) FREEBOARD OF ELEVATION.
 CITY ORDINANCE CHANGE SEPT. 12/2016. PLEASE ALSO NOTE
 FOR FUTURE WORK IN THE CITY?S FLOOD ZONE AREAS, THE
 CITY COMMISSION & MAYOR WILL BE CHANGING THE FREEBOARD
 REQUIREMENTS TO (2 FOOT) FREEBOARD IN THE UPCOMING
 MONTHS. ALSO ON ALL FLOOD ZONE CERTIFICATES THE
 LATITUDE AND LONGITUDE ARE TO BE FILLED OUT WITH THE
 FRONT CENTER OF THE STRUCTURE BEING THE POINT GIVEN.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (2.1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF
 THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH
 FLOOR HEIGHT. 107.2.5.1 DESIGN FLOOD ELEVATIONS.
 107.3.5.1.1(1) MINIMUM PLAN REVIEW COMMERCIAL
 BUILDINGS. FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN
 FLOOD ELEVATIONS.
  
 (2.2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. REQUIRED
 INSPECTIONS. 110.3.( 1.2.) IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT,
 AND PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE
 ELEVATION CERTIFICATION, REQUIRED IN SECTION 1612.5,
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL.
  
 (2.3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS. REQUIRED INSPECTIONS. 110.3.( 6.) FINAL
 INSPECTION. TO BE MADE AFTER THE BUILDING IS COMPLETED
 AND READY FOR OCCUPANCY.6.1. LOWEST FLOOR ELEVATION. IN
 FLOOD HAZARD AREAS, AS PART OF THE FINAL INSPECTION, A
 FINAL CERTIFICATION OF THE LOWEST FLOOR ELEVATION SHALL
 BE SUBMITTED TO THE AUTHORITY HAVING JURISDICTION.
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-10-22 Cont ID  
Sent By tklarge Date 2016-10-22 Time 10:32 Rev Time 0.00
Received By tklarge Date 2016-10-22 Time 09:30 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-03-23 Cont ID  
Sent By jwitmer Date 2017-03-23 Time 14:07 Rev Time 0.00
Received By jwitmer Date 2017-03-23 Time 14:07 Sent To  
Notes
2017-03-23 14:08:51ROOFING PRODUCT APPROVAL FL14645-R2
 METAL SALES MANUFACTURING CORPORATION

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-10-22 Cont ID  
Sent By jwitmer Date 2016-10-22 Time 09:16 Rev Time 0.00
Received By jwitmer Date 2016-10-22 Time 09:15 Sent To  
Notes
2016-10-22 09:15:58THIS REVIEW NO ROOFING PRODUCT APPROVALS WERE
 SUBMITTED.

Review Stop Z ZONING
Rev No 2 Status P Date 2017-03-06 Cont ID  
Sent By jroach Date 2017-03-06 Time 13:51 Rev Time 0.00
Received By jroach Date 2017-03-06 Time 13:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-10-28 Cont ID  
Sent By jroach Date 2016-10-28 Time 11:56 Rev Time 0.00
Received By jroach Date 2016-10-28 Time 10:37 Sent To  
Notes
2016-10-28 11:56:16ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 10.28.2016
 PERMIT NO.: 16090860
 ADDRESS: 1301 SUMMIT BOULEVARD
 CONTRACTOR/CONTACT: ALLEN GAST
 TELEPHONE NO.: 561.281.1001
 SCOPE OF REVIEW: LORIKEET BIRD EXHIBIT
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO THE PALM BEACH ZOO'S LEASE AGREEMENT
 WITH THE CITY OF WEST PALM BEACH, INDIVIDUAL STRUCTURES
 OR IMPROVEMENTS IN EXCESS OF $5,000 ARE TO BE SUBMITTED
 TO THE CITY COMMISSION FOR PRIOR APPROVAL AS SUCH
 IMPROVEMENTS WOULD OCCUR ON CITY-OWNED PROPERTY.
  
 2. BEFORE COMMENCING THE IMPROVEMENTS, THE ZOO SHALL
 PROVIDE THE CITY?S RISK MANAGER WITH CERTIFICATES OF
 INSURANCE EVIDENCING THAT ANY CONTRACTOR(S) PERFORMING
 THE IMPROVEMENTS CARRIES COMMERCIAL GENERAL LIABILITY
 INSURANCE (INCLUDING, WITHOUT LIMITATION, CONTRACTOR?S
 LIABILITY COVERAGE), WRITTEN ON AN OCCURRENCE BASIS
 WITH A MINIMUM COMBINED SINGLE LIMIT OF $2,000,000,
 ALONG WITH WORKERS COMPENSATION INSURANCE AS REQUIRED
 BY LAW, AND INCLUDING THE CITY OF WEST PALM BEACH AS AN
 ADDITIONAL INSURED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved