Plan Review Details - Permit 16090794
Plan Review Stops For Permit 16090794
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-14 Cont ID  
Sent By tklarge Date 2016-10-14 Time 05:58 Rev Time 0.00
Received By tklarge Date 2016-10-11 Time 15:31 Sent To  
Notes
2016-10-11 15:31:53RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-24 Cont ID  
Sent By tklarge Date 2016-09-24 Time 02:48 Rev Time 0.00
Received By tklarge Date 2016-09-21 Time 09:36 Sent To  
Notes
2016-09-22 09:36:29ROUTED TO PLUMBING <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-10-14 Cont ID  
Sent By tklarge Date 2016-10-14 Time 05:58 Rev Time 0.00
Received By tklarge Date 2016-10-14 Time 05:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-09-24 Cont ID  
Sent By tklarge Date 2016-09-24 Time 02:48 Rev Time 0.00
Received By tklarge Date 2016-09-24 Time 02:18 Sent To  
Notes
2016-09-24 02:24:301) SUBMIT SIZING CALCULATIONS FOR THE SIZING OF THIS
 GREASE TRAP. 2014 FPC SEC.1003.2, 1003.3.4.
 2) THESE DEVICES ARE USUALLY EQUIPPED WITH FLOW CONTROL
 DEVICES THAT ARE VENTED. THIS IS NOT SHOWN ON THE
 PLANS. SUBMIT THE INSTALLATION DETAILS FROM THE
 INSTALLATION MANUAL FOR THIS DEVICE.WPB AMEND. TO FBC
 SEC.107.2.1, 1003.3.4.2.
 3) PLANS DONE IN PENCIL CANNOT BE ACCEPTED AS CHANGES
 CAN BE MADE AFTER APPROVAL OF THE PLANS.
 4) PLEASE CLARIFY THE TYPE OF FIXTURE DISCHARGING INTO
 THE GREASE INTERCEPTOR. IT APPEARS TO BE A 3
 COMPARTMENT SINK. IS IT NEW OR EXISTING? IF NEW, SUBMIT
 A WATER RISER ALSO. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 5) INDICATE ON THE PLANS IF THIS INTERCEPTOR IS
 REPLACING AN EXISTING UNIT OR IS IT A NEW
 INSTALLATION.IF THE INTERCEPTOR AND SINK ARE NEW SUBMIT
 A FLOOR PLAN SHOWING THE LOCATION OF THE SINK &
 INTERCEPTOR. WPB AMEND. TO FBC SEC.107.2.1,
 6) IF THE SINK IS NEW, INDICATE ON THE PLAN WHERE THE
 THE 2 INCH DRAIN IS CONNECTING TO THE EXISTING SANITARY
 SYSTEM.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  