Plan Review Details - Permit 16090660
Plan Review Stops For Permit 16090660
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2017-05-17 Cont ID  
Sent By tklarge Date 2017-05-17 Time 09:40 Rev Time 0.00
Received By tklarge Date 2017-05-17 Time 09:15 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-05-10 Cont ID  
Sent By tklarge Date 2017-04-26 Time 09:54 Rev Time 0.00
Received By tklarge Date 2017-04-26 Time 12:28 Sent To  
Notes
2017-04-26 13:45:191) SUBMIT TWO COPIES OF ALL DOCUMENTS BEING SUBMITTED
 FOR A PERMIT INCLUDING ANOTHER SIGNED & SEALED DRAWING
 FOR THE ANCHORING OF THE LP TANK. WPB AMEND. TO FBC
 SEC.107.1.
 2) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
 3) SHOW THE LENGTHS OF ALL CUT SECTIONS OF PIPE PER
 2014 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2014
 FBC-RES SEC. G2413.
 4) SHOW THE TYPE OF MATERIAL AND PIPE SIZES TO THE
 EXISTING DRYER AND COOKTOP. 2014 FGC SECS. 401.3 &
 401.4. THE EXISTING SYSTEM BTU LOAD MUST BE ADDED TO
 THE NEW BTU LOAD TO ENSURE THE ENTIRE EXISTING SYSTEM
 IS SIZED PROPERLY FOR THE TOTAL BTU LOAD.
 5) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3.
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-09-21 Cont ID  
Sent By tklarge Date 2016-09-21 Time 06:50 Rev Time 0.00
Received By tklarge Date 2016-09-21 Time 05:09 Sent To  
Notes
2016-09-21 06:49:591) A SEPARATE PERMIT IS REQUIRED FROM A PLUMBING
 CONTRACTOR FOR THE INSTALLATION OF THE WATER LINES TO
 THE TANKLESS WATER HEATER. F.S. 489.105.
 2) THE WIND LOAD ENGINEERING FOR THE ANCHORING OF THE
 LP TANK IS OUTDATED. THE DOCUMENTS REFER TO THE 2010
 FBC. THE CODE IN EFFECT IS THE 2014 FBC.
 3) THE WIND LOAD ENGINEERING SHALL BE SIGNED AND SEALED
 BY THE DESIGN PROFESSIONAL OF RECORD PER THE FL. ADMIN.
 CODE RULE 61G15-23.002. COPIES HAVE BEEN SUBMITTED. TWO
 COPIES ARE REQUIRED.
 4) THE SUBMITTED WIND LOAD ENGINEERING IS FOR A JOB IN
 VERO BEACH. SUBMIT SIGNED AND SEALED ENGINEERING FOR
 THE ADDRESS WHERE THE WORK IS TO BE DONE.
 5) THE TANKLESS WATER HEATER SHALL BE LISTED AND
 LABELED PER THE 2014 FL. GAS CODE. SEC.301.3, NFPA 58
 SEC. 5.20.1.
 6) INDICATE ON THE SURVEY THE DISTANCE OF THE TANKLESS
 WATER HEATER IN RELATION TO OPERABLE DOORS AND WINDOWS
 OF THE STRUCTURE. THE LOCATION OF THE TANKLESS WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. 2014 FGC SEC. 303.1.
 7) INDICATE ON THE GAS PLAN THAT THE PE PIPE FROM THE
 SECOND STAGE REGULATOR TO THE TANKLESS WATER HEATER IS
 UNDERGROUND.
 8) INDICATE THE TYPE OF PIPE AND SIZE OF THE
 ABOVEGROUND GAS PIPE TO THE WATER HEATER.
 9) PORTIONS OF THE SUBMITTED SHEET FOR THE REGULATORS
 ARE ILLEGIBLE. SUBMIT LEGIBLE COPIES. WPB AMEND. TO FBC
 SEC. 107.2.1.
 10) REMOVE THE PREVIOUS PERRMIT NUMBER THAT IS STAMPED
 ON THE SURVEY. THIS PERMIT NUMBER IS NOT APPLICABLE TO
 THIS INSTALLATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-17 Cont ID  
Sent By tklarge Date 2017-05-17 Time 09:40 Rev Time 0.00
Received By tklarge Date 2017-05-12 Time 13:07 Sent To  
Notes
2017-05-15 13:07:13RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-10 Cont ID  
Sent By tklarge Date 2017-05-10 Time 09:54 Rev Time 0.00
Received By tklarge Date 2017-04-26 Time 12:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-21 Cont ID  
Sent By tklarge Date 2016-09-21 Time 06:50 Rev Time 0.00
Received By tklarge Date 2016-09-19 Time 12:45 Sent To  
Notes
2016-09-19 12:45:49PLUMB -$5000


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved