Plan Review Details - Permit 16090612
Plan Review Stops For Permit 16090612
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-19 Cont ID  
Sent By cthroop Date 2016-10-19 Time 10:04 Rev Time 0.00
Received By cthroop Date 2016-10-19 Time 10:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-28 Cont ID  
Sent By cthroop Date 2016-09-28 Time 12:15 Rev Time 0.00
Received By cthroop Date 2016-09-28 Time 12:14 Sent To E
Notes
2016-09-28 12:16:37BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. VALUE APPEARS LOW.
 2. PROVIDE DESIGN WIND LOADS.
  
 VALUATION ? BASED ON THE MARSHALL-SWIFT VALUATION
 SERVICE YOUR STATED VALUE APPEARS LOW.
  
 CITY OF WPB CHPT. 1
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY
 DELAY THE APPLICATION PROCESS.
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-19 Cont ID  
Sent By mvaldes Date 2016-10-19 Time 08:53 Rev Time 0.00
Received By mvaldes Date 2016-10-19 Time 08:45 Sent To B
Notes
2016-10-19 08:53:25ROUTED TO CT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-28 Cont ID  
Sent By mvaldes Date 2016-09-28 Time 17:21 Rev Time 0.00
Received By mvaldes Date 2016-09-28 Time 17:15 Sent To  
Notes
2016-09-28 17:21:30REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE A PROPOSED SIGN ELECTRICAL DETAIL TO INCLUDE
 THE FOLLOWING : ( BLOCK NOTE ISN'T SUFFICIENT )
  
 1A] NEC 600.5 A MINIMUM 20 AMP DEDICATED BRANCH CIRCUIT
 ( IF EXISTING PLEASE MARK ON PLANS )
  
 1B] NEC 600.6 PROVIDE A DISCONNECT EITHER WITHIN-SIGHT
 OR AS AN INTERGAL PART OF THE SIGN.
  
 1C] NEC 600.7 SHOW AN EQUIPMENT GROUNDING CONDUCTOR
 ROUTED ALONG WITH THE SUPPLY BRANCH CIRCUIT FOR THE
 SIGN BONDING CONNECTIONS.
  
 2] FBC-E_C405.2.4 EXTERIOR LIGHTING CONTROLS. LIGHTING
 NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS.
  
 3] PROVIDE AN OWNER SIGNED CONTRACT BECAUSE VALUE SEEMS
 TO BE TOO LOW FBC-109

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-19 Cont ID  
Sent By cthroop Date 2016-10-19 Time 10:04 Rev Time 0.00
Received By cthroop Date 2016-10-11 Time 10:35 Sent To  
Notes
2016-10-12 10:35:37RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-28 Cont ID  
Sent By mvaldes Date 2016-09-28 Time 17:22 Rev Time 0.00
Received By mvaldes Date 2016-09-16 Time 11:01 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-10-14 Cont ID  
Sent By njwira Date 2016-10-14 Time 15:20 Rev Time 0.00
Received By njwira Date 2016-10-12 Time 14:51 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-09-27 Cont ID  
Sent By mvaldes Date 2016-09-28 Time 17:22 Rev Time 0.00
Received By njwira Date 2016-09-16 Time 14:01 Sent To E
Notes
2016-09-27 13:50:45REQUIRES A TREE ALTERATION PERMIT TO REMOVE TREES