Plan Review Details - Permit 16090600
Plan Review Stops For Permit 16090600
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-19 Cont ID  
Sent By cthroop Date 2016-10-19 Time 10:23 Rev Time 0.00
Received By cthroop Date 2016-10-19 Time 10:23 Sent To  
Notes
2016-10-19 10:24:55NO NOTES

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-28 Cont ID  
Sent By cthroop Date 2016-09-28 Time 12:08 Rev Time 0.00
Received By cthroop Date 2016-09-28 Time 12:08 Sent To E
Notes
2016-09-28 12:11:22BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. VALUE APPEARS LOW.
 2. PROVIDE CONNECTION DETAIL FOR SIGN TO STRUCTURE.
 3. PROVIDE DESIGN WIND LOADS.
  
 VALUATION ? BASED ON THE MARSHALL-SWIFT VALUATION
 SERVICE YOUR STATED VALUE APPEARS LOW.
  
 CITY OF WPB CHPT. 1
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY
 DELAY THE APPLICATION PROCESS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-19 Cont ID  
Sent By mvaldes Date 2016-10-19 Time 08:41 Rev Time 0.00
Received By mvaldes Date 2016-10-19 Time 08:39 Sent To B
Notes
2016-10-19 08:41:58ROUTED TO CT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-28 Cont ID  
Sent By mvaldes Date 2016-09-28 Time 17:10 Rev Time 0.00
Received By mvaldes Date 2016-09-28 Time 17:10 Sent To  
Notes
2016-09-28 17:10:21REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE A PROPOSED SIGN ELECTRICAL DETAIL TO INCLUDE
 THE FOLLOWING : ( BLOCK NOTE ISN'T SUFFICIENT )
  
 1A] NEC 600.5 A MINIMUM 20 AMP DEDICATED BRANCH CIRCUIT
 ( IF EXISTING PLEASE MARK ON PLANS )
  
 1B] NEC 600.6 PROVIDE A DISCONNECT EITHER WITHIN-SIGHT
 OR AS AN INTERGAL PART OF THE SIGN.
  
 1C] NEC 600.7 SHOW AN EQUIPMENT GROUNDING CONDUCTOR
 ROUTED ALONG WITH THE SUPPLY BRANCH CIRCUIT FOR THE
 SIGN BONDING CONNECTIONS.
  
 2] FBC-E_C405.2.4 EXTERIOR LIGHTING CONTROLS. LIGHTING
 NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS.
  
 3] PROVIDE AN OWNER SIGNED CONTRACT BECAUSE VALUE SEEMS
 TO BE TOO LOW FBC-109

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-19 Cont ID  
Sent By cthroop Date 2016-10-19 Time 10:23 Rev Time 0.00
Received By cthroop Date 2016-10-11 Time 10:37 Sent To  
Notes
2016-10-12 10:37:50RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-28 Cont ID  
Sent By mvaldes Date 2016-09-28 Time 17:10 Rev Time 0.00
Received By mvaldes Date 2016-09-16 Time 10:50 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2016-10-27 Cont ID  
Sent By njwira Date 2016-10-27 Time 15:16 Rev Time 0.00
Received By njwira Date 2016-10-27 Time 15:16 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2016-10-14 Cont ID  
Sent By njwira Date 2016-10-14 Time 15:30 Rev Time 0.00
Received By njwira Date 2016-10-12 Time 14:52 Sent To E
Notes
2016-10-14 15:31:30SIGN IS NOT ON THE APPROVED SIDE
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-09-27 Cont ID  
Sent By mvaldes Date 2016-09-28 Time 17:10 Rev Time 0.00
Received By njwira Date 2016-09-16 Time 13:55 Sent To E
Notes
2016-09-27 11:51:409/27/16- FAILED
  
 SIGN IS NOT INCLUDED IN PROPOSED DRAWING.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  