Plan Review Details - Permit 16090593
Plan Review Stops For Permit 16090593
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-09-28 Cont ID  
Sent By shill Date 2016-09-28 Time 12:04 Rev Time 0.00
Received By shill Date 2016-09-28 Time 10:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-09-23 Cont ID  
Sent By vperez Date 2016-09-23 Time 10:49 Rev Time 0.00
Received By vperez Date 2016-09-23 Time 10:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-09-20 Cont ID  
Sent By wjolin Date 2016-09-20 Time 12:36 Rev Time 0.00
Received By wjolin Date 2016-09-20 Time 12:36 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-10-22 Cont ID  
Sent By tklarge Date 2016-10-22 Time 04:50 Rev Time 0.00
Received By tklarge Date 2016-10-22 Time 04:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-10-24 Cont ID  
Sent By cpuell Date 2016-10-24 Time 09:13 Rev Time 0.00
Received By cpuell Date 2016-10-19 Time 12:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-17 Cont ID  
Sent By cpuell Date 2016-10-17 Time 08:47 Rev Time 0.00
Received By cpuell Date 2016-10-13 Time 10:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-03 Cont ID  
Sent By lmarchan Date 2016-10-03 Time 14:17 Rev Time 0.00
Received By lmarchan Date 2016-09-16 Time 09:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-09-26 Cont ID  
Sent By ccole Date 2016-09-26 Time 16:16 Rev Time 0.00
Received By ccole Date 2016-09-26 Time 16:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-10-22 Cont ID  
Sent By tklarge Date 2016-10-22 Time 04:15 Rev Time 0.00
Received By tklarge Date 2016-10-22 Time 03:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-10-15 Cont ID  
Sent By tklarge Date 2016-10-15 Time 05:51 Rev Time 0.00
Received By tklarge Date 2016-10-15 Time 02:56 Sent To  
Notes
2016-10-15 05:05:071) SHT. P413 - THE ADDED OUTDDOOR KITCHEN IS NOT SHOWN
 ON THE SANITARY RISER DIAGRAM BUT IS SHOWN ON SHTS.P100
 C & P101 C CLARIFY.
 2) EXPLAIN WHAT PROCESS IS TAKING PLACE AT THE "OUTDOOR
 KITCHEN." THE WASTE FROM THIS AREA MAY BE REQUIRED TO
 DISCHARGE TO THE GREASY WASTE. THE PLUMBING DRAWINGS DO
 NOT SHOW WHERE THE DRAINAGE LINE FOR THIS AREA CONNECTS
 OR WHAT TYPE OF WASTE IS DISCHARGING INTO THIS LINE.
 3) SHT. P413. THE DRAIN LINE FOR THE POOL STORAGE ROOM
 AND THE DRINKING FOUNTAINS IS NOT SHOWN ON THE GRAVITY
 RISER DIAGRAM BUT IS SHOWN ON SHTS. P100 C & 101 C.
 CLARIFY.
 4) SHT. P100 C REFERS TO SHT. P100 B FOR MATCLINE.
 THERE IS NO SHT. P100 B IN THIS SET. CLARIFY.
 5) SHT. P101 B - DELTA 22 DATED 9/16/16 - INDICATES
 THIS CHANGE RELATES TO BULLETIN NO. 10 YET THE OTHER
 SHEETS NOTE THAT DELTA 22 RELATES TO BULLETIN #22. THE
 SAME THING OCCURS ON SHT. P 103 A AND DELTA 22 IS NOT
 EVEN LISTED ON SHT. P104 A. PLEASE CLARIFY AS THIS IS
 VERY CONFUSING IN MAKING A DETRMINATION AS TO WHAT
 CHANGES AND WHERE HAVE BEEN MADE TO THE PLANS.
 6) SHT. P 201 C - INDICATES A CHANGE HAS BEEN MADE TO
 THIS SHEET BUT IT IS NOT LISTED IN THE NARRATIVE UNDER
 BULLETIN NO. 22. CLARIFY.
 7) SHTS. P 210 A & P210 B - SHOW THE ADDED HOT WATER
 RECIRCULATION LINE BY CLOUDING AND THE DELTA NUMBER.
 WPB AMEND TO FBC SEC. 107.2.1.
 8) SHT. P 402 - DELTA 22 DATED 9/16/16 - INDICATES THIS
 CHANGE RELATES TO BULLETIN NO. 10 YET THE OTHER SHEETS
 NOTE THAT DELTA 22 RELATES TO BULLETIN #22. PLEASE
 CLARIFY AS THIS IS VERY CONFUSING IN MAKING A
 DETRMINATION AS TO WHAT CHANGES AND WHERE HAVE BEEN
 MADE TO THE PLANS.
 9) SHT. P413 - WC-3 OF THE 4 INCH BUILDING DRAIN
 REQUIRES AN INDIVIDUAL VENT. AS DRAWN, IT DOES NOT
 COMPLY WITH FPC SEC.909.1 FOR FIXTURES PERMITTED ON A
 WET VENT. THE WRONG WATER CLOSET WAS GIVEN A VENT. SEE
 WC-3 IN TOILET ROOM #168.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By tklarge Date 2016-10-03 Time 13:23 Rev Time 0.00
Received By tklarge Date 2016-09-30 Time 05:37 Sent To  
Notes
2016-10-03 13:23:531) THE WATER SUPPLY VALVES FOR THE STACKED WASHER/
 DRYER SHALL BE PROVIDED WITH ACCESS PER 2010 FPC
 SEC.606.3.
 2) SHT. P101A - THE NOTES ON THE RIGHT SIDE OF THE PLAN
 ARE COVERED BY THE DESIGN TEAM NAMES. PROVIDE A SHEET
 WHERE THE NOTES ARE VISIBLE. WPB AMEND. TO FBC SEC.
 107.2.1.
 3) THE DESCRIPTION OF THE PLUMBING CHANGES IN THE
 NARRATIVE IS VERY VAGUE. PLEASE PROVIDE A CLEAR
 DESCRIPTION OF THE CHANGES MADE TO THE PLUMBING SYSTEM
 ON THE APPLICABLE SHEETS. WPB AMEND. TO FBC SEC.
 107.2.1.
 4) ALL OB-1 FIXTURES ON THE RISERS SHALL DISCHARGE INTO
 A 3 INCH STACK PER 2010 FPC SEC.406.3.
 5) SHT. P403 - RISERS #7,8,9,11,12 & 15 FOR THE FIRST
 AND SECOND FLOORS APPEAR TO HAVE FLAT, DRY VENTS
 CONNECTED TO THE STACKS. IF CONNECTED AT A 45 DEGREE
 ANGLE, IT WOULD COMPLY WITH THE PLUMBING CODE. A NOTE
 CAN BE PLACED ON THE PLANS STATING THE VENTS ARE
 CONNECTED AT A 45DEGREE ANGLE.
 6) SHT. P403 - THE WASHING MACHINE ON RISER #12 CANNOT
 DISCHARGE INTO A WET VENT PERR SEC.909.1 OF 2010 FPC. A
 VENT ON THE BATHTUB WILL CORRECT THIS ISSUE.
 7) SHT. P413 - WC-3 OF THE 4 INCH BULDDING DRAIN
 REQUIRES AN INDIVIDUAL VENT. AS DRAWN, IT DOES NOT
 COMPLY WITH FPC SEC.909.1 FOR FIXTURES PERMITTED ON A
 WET VENT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-10-22 Cont ID  
Sent By tklarge Date 2016-10-22 Time 04:50 Rev Time 0.00
Received By tklarge Date 2016-10-22 Time 04:50 Sent To  
Notes
***NONE***