Plan Review Details - Permit 16090422
Plan Review Stops For Permit 16090422
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-11-10 Cont ID  
Sent By jwitmer Date 2016-11-10 Time 10:17 Rev Time 0.00
Received By jwitmer Date 2016-11-10 Time 10:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-22 Cont ID  
Sent By jwitmer Date 2016-09-22 Time 08:20 Rev Time 0.00
Received By jwitmer Date 2016-09-22 Time 08:20 Sent To  
Notes
2016-09-22 08:20:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16090422
 ADD: 1914 MERRY PLACE UNIT 2 OF 3
 CONT: WEST PALM BEACH HOUSING AUTHORITY
 TEL: 561-676-8442
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. SEPT. 22/ 2016
 ACTION: DENIED
  
 1) PLEASE NOTE (3) SEPARATE BUILDING PERMITS SUBMITTED
 AND ONLY (3) SETS OF PLANS WERE SUBMITTED. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 SECTION 107 SUBMITTAL DOCUMENTS. 107.1 SUBMITTAL
 DOCUMENTS CONSISTING OF CONSTRUCTION DOCUMENTS,
 GEOTECHNICAL REPORT AND OTHER DATA SHALL BE SUBMITTED
 IN TWO OR MORE SETS WITH EACH PERMIT APPLICATION.
  
 2) SITE PLANS WILL NEED TO IDENTIFY NORTH AND WHICH
 UNITS ARE NORTH, SOUTH AND WEST AS INDICATED ON THE
 PERMIT APPLICATION. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3) PLEASE DECLARE COMPLIANCE WITH 2014 FBC-B 503.1.2
 BUILDINGS ON SAME LOT. TWO OR MORE BUILDINGS ON THE
 SAME LOT SHALL BE REGULATED AS SEPARATE BUILDINGS OR
 SHALL BE CONSIDERED AS PORTIONS OF ONE BUILDING IF THE
 BUILDING HEIGHT OF EACH BUILDING AND THE AGGREGATE
 BUILDING AREA OF THE BUILDINGS ARE WITHIN THE
 LIMITATIONS OF TABLE 503 AS MODIFIED BY SECTIONS 504
 AND 506. THE PROVISIONS OF THIS CODE APPLICABLE TO THE
 AGGREGATE BUILDING SHALL BE APPLICABLE TO EACH
 BUILDING.
  
 4) THERE IS A PLAN 11X17 OF THE 3 UNITS RAISED DECK,
 STAIRS, RAMP WITH HAND RAILS AND GUARDRAILS. NO ONE HAS
 TAKEN RESPONSIBILITY FOR THIS PLAN ?
 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE.
  
 5) THERE IS A PLAN 11X17 OF THE 3 UNITS RAISED DECK,
 STAIRS, RAMP WITH HAND RAILS AND GUARDRAILS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (7) MEANS OF EGRESS
 STAIRS CONSTRUCTION/LOADING/GEOMETRY AND PROTECTION
 HAND RAILS/ GUARDRAILS
 RAMPS CONSTRUCTION/LOADING/GEOMETRY AND PROTECTION HAND
 RAILS/ GUARDRAILS
 (10) 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY STAIRS & RAMPS
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-11-03 Cont ID  
Sent By rlecky Date 2016-11-03 Time 11:11 Rev Time 0.00
Received By rlecky Date 2016-11-03 Time 10:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-15 Cont ID  
Sent By albarran Date 2016-09-15 Time 16:25 Rev Time 0.00
Received By albarran Date 2016-09-15 Time 16:25 Sent To  
Notes
2016-09-15 16:25:39ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME: TEMPORARY OFFICES AT MERRY PLACE
 JOB ADDRESS: 1914 MERRY PLACE
 DESCRIPTION: TEMPORARY STATE APPROVED MODULAR OFFICE
 SPACE. INCLUDING PLUMB, ELECTRIC, HVAC, FOUNDATION
 BLOCKING AND TIE-DOWN.
 MASTER PERMIT: 16090422
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
 1. ELECTRICAL SUB PERMIT REQUIRED.
 2. YOU SHALL SUBMIT A SITE PLANS INDICATING THE
 LOCATION OF THE ELECTRICAL POWER SOURCE WHETHER IT IS
 FROM A UTILITY POLE OR A TRANSFORMER. MARK ON THAT THE
 LOCATION OF THE TERMINAL RACK WITH THE METER AND
 SERVICE DISCONNECTS. MARK THE PROPOSED ROUTE FOR THE
 FEEDERS.
 3. MARK ON THE PLAN THE PROPOSED ROUTE FROM THE
 TERMINAL RACK TO THE EXISTING SERVICE PANEL OF THE
 UNIT.
 4. PROVIDE AN ELECTRICAL RISER DIAGRAM OF THE COMPLETE
 INSTALLATION FROM THE SOURCE TO THE INDIVIDUAL UNIT.
 INDICATE AS PART OF THE RISER THE RACEWAY AND CONDUCTOR
 TYPES.
 5. FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER
 OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM
 OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR
 A MAXIMUM OF 3% VOLTAGE DROP. PROVIDE LOAD CALCS FOR
 THE SERVICE AND FEEDERS TAKING INTO ACCOUNT THE VARIOUS
 DISTANCES FOR VOLTAGE DROP CONSIDERATIONS.
 6. NEC 110.27(B): IN LOCATIONS WHERE ELECTRICAL
 EQUIPMENT IS LIKELY TO BE EXPOSED TO PHYSICAL DAMAGE,
 ENCLOSURES OR GUARDS SHALL BE ARRANGED AND OF SUCH
 STRENGTH AS TO PREVENT SUCH DAMAGE. BOLLARDS MAY BE
 NECESSARY.
 7. NEC 110.16: ELECTRICAL EQUIPMENT IN OTHER THAN
 DWELLING UNITS LIKELY TO REQUIRE SERVICE WHILE
 ENERGIZED SHALL BE FIELD MARKED TO WARN AGAINST
 POTENTIAL ARC-FAULT HAZARDS.
 8. NEC 110.24: THE MAXIMUM AVAILABLE FAULT CURRENT
 SHALL BE DURABLY MARKED AND DATED ON ALL NON-DWELLING
 ELECTRICAL APPARATUS.
 9. 1006.1 ILLUMINATION REQUIRED. THE MEANS OF EGRESS,
 INCLUDING THE EXIT DISCHARGE, SHALL BE ILLUMINATED AT
 ALL TIMES THE BUILDING SPACE SERVED BY THE MEANS OF
 EGRESS IS OCCUPIED.
 10. ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION
 UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL
 INSPECTOR. NO SITE TUBES WILL BE ACCEPTED
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-11-01 Cont ID  
Sent By pleduc Date 2016-11-01 Time   Rev Time 0.00
Received By pleduc Date 2016-11-01 Time 08:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-09-19 Cont ID  
Sent By pleduc Date 2016-09-19 Time   Rev Time 0.00
Received By pleduc Date 2016-09-19 Time 13:30 Sent To  
Notes
2016-09-19 13:30:27THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SEPARATION DISTANCES OF THE PROPOSED TRAILERS
 ARE NOT INDICATED AND APPEAR TO NOT MEET THE MINIMUM
 SEPARATION DISTANCES IN NFPA 241. THE PROPOSED
 CONFIGURATION IS CONSIDERED A LARGE CONSTRUCTION
 SUPPORT COMPLEX. FIRE SPRINKLER PROTECTION WOULD BE
 REQUIRED TO REDUCE THE DISTANCES BY 75%.
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS;
  
 TABLE 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 A.4.2.2 WHERE LOCATED 9M(30 FT) OR MORE FROM THE
 STRUCTURE AND CONSTRUCTED OF COMBUSTIBLE MATERIALS, IT
 IS RECOMMENDED THAT TEMPORARY SUPPORT BUILDINGS BE
 DIVIDED INTO SMALL, DETACHED UNITS TO MINIMIZE FIRE
 LOSS. LARGE CONSTRUCTION SUPPORT
 COMPLEXES SHOULD BE PROTECTED WITH ADEQUATE FIRE
 PROTECTION (E.G., AUTOMATIC SPRINKLERS, YARD HYDRANTS,
 HOSE, AND EXTINGUISHERS) AS REQUIRED BY THE AUTHORITY
 HAVING JURISDICTION.
  
  
 PLEASE PROVIDE FOR THE MINIMUM SPEARATION DISTANCES OR
 PROVIDE FIRE SPRINKLER PROTECTION IN EACH TRAILER.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-15 Cont ID  
Sent By cpuell Date 2016-11-15 Time 17:35 Rev Time 0.00
Received By cpuell Date 2016-10-26 Time 13:00 Sent To  
Notes
2016-10-28 13:01:19B28
 *TRAVELLING WITH 16090418 & 16090425*

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-03 Cont ID  
Sent By cpuell Date 2016-10-03 Time 14:12 Rev Time 0.00
Received By cpuell Date 2016-09-13 Time 13:18 Sent To  
Notes
2016-09-14 13:18:25B23
 *TRAVELLING WITH 16090418 & 16090425*

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2016-11-03 Cont ID  
Sent By ccole Date 2016-11-03 Time 08:05 Rev Time 0.00
Received By ccole Date 2016-11-03 Time 08:05 Sent To  
Notes
2016-11-03 08:06:062ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16090422
 11/3/16
  
 1) THE REQUESTED DUPLICATE SET OF PLANS DOES NOT BEAR
 THE LISTING AGENCY APPROVAL LABEL, AND THE TWO PLAN
 SETS DO NOT MATCH- THE PLANS ARE ARRANGED AND DATED
 DIFFERENTLY, AND THE SUBMITTED DUPLICATE SET HAS AN
 ADDITIONAL A1.1 SHEET.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-20 Cont ID  
Sent By ccole Date 2016-09-20 Time 11:56 Rev Time 0.00
Received By ccole Date 2016-09-20 Time 11:56 Sent To  
Notes
2016-09-20 11:57:011ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090422
 9/20/16
  
 1) PLANS MUST BE SUBMITTED IN TWO OR MORE SETS WITH
 EACH PERMIT APPLICATION- SECTION 107.1 WPB AMENDMENTS
 TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-11-07 Cont ID  
Sent By gjohnson Date 2016-11-07 Time 14:52 Rev Time 0.00
Received By gjohnson Date 2016-11-07 Time 14:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-09-28 Cont ID  
Sent By gjohnson Date 2016-09-28 Time 12:13 Rev Time 0.00
Received By gjohnson Date 2016-09-28 Time 12:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-11-15 Cont ID  
Sent By ajones Date 2016-11-15 Time 16:57 Rev Time 0.00
Received By ajones Date 2016-11-15 Time 16:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-09-29 Cont ID  
Sent By ajones Date 2016-09-29 Time 17:33 Rev Time 0.00
Received By ajones Date 2016-09-28 Time 13:56 Sent To  
Notes
2016-09-29 17:33:139/29/16- FAILED. WHO ARE THE TEMPORARY OFFICES FOR? HOW
 LONG IS TEMPORARY?
  
 ANGELLA VANN
 561-371-8177
 [email protected]