Plan Review Details - Permit 16090394
Plan Review Stops For Permit 16090394
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-24 Cont ID  
Sent By jwitmer Date 2016-10-24 Time 08:38 Rev Time 0.00
Received By jwitmer Date 2016-10-24 Time 07:31 Sent To  
Notes
2016-10-24 08:06:00BUILDING PROVISO: 2014 FBC-ACCESSIBILITY CODE-
 ENTRANCES NOT ACCESSIBLE REQUIRE SIGNAGE.
 216.4.3 DIRECTIONAL SIGNS. SIGNS REQUIRED BY SECTION
 1003.2.13.6 OF THE INTERNATIONAL BUILDING
 CODE (2000 EDITION) OR SECTION 1007.7 OF THE
 INTERNATIONAL BUILDING CODE (2003 EDITION)
 (INCORPORATED BY REFERENCE, SEE ?REFERENCED STANDARDS?
 IN CHAPTER 1) TO PROVIDE DIRECTIONS TO
 ACCESSIBLE MEANS OF EGRESS SHALL COMPLY WITH 703.5.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-13 Cont ID  
Sent By jwitmer Date 2016-10-13 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2016-10-13 Time 06:56 Sent To  
Notes
2016-10-13 07:39:52BUILDING PLAN REVIEW
 W. P. B. REVISION: 16090394
 W. P. B. PERMIT: 15090611
 ADD: 4912 S DIXIE
 CONT: LEIGHTON MCGINN
 TEL: (561)373-3902 / KARI
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. OCT. 13/ 2016
 ACTION: DENIED
  
 1) SHEET SP-1 & A1.1 BOTH SHOW DOOR 102A HANDRAILS AT
 THE LANDING AND STAIRS. BETWEEN THE DOOR AND HANDRAIL
 AT THE LATCH SIDE OF THE DOOR PLEASE PROVIDE COMPLIANCE
 WITH THE 2014 ACCESSIBILITY CODE SECTION 404.2.4 ALSO
 SEE FIGURE 404.2.4.1.(A).
  
 2) SHEET SP-1 & A1.1 THE ACCESSIBLE PARKING NOW SHOWS A
 RAMP TO DOOR 108. TO GAIN ACCESS FROM THE ACCESSIBLE
 PARKING SPACE ONE HAS TO CROSS THE 10 X 25 FOOT LOADING
 ZONE. PLEASE REVIEW 2014 ACCESS. CODE 208.3.1. ( FL.
 SPECIFIC/ GRAY BOX)
 ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE ROUTE THAT
 IS AT LEAST 44 INCHES (1118 MM) WIDE AND SO THAT USERS
 ARE NOT COMPELLED TO WALK OR WHEEL BEHIND PARKED
 VEHICLES EXCEPT BEHIND HIS OR HER OWN VEHICLE.
  
 3) DOOR 100B THE LANDING IS TO NARROW FOR THE DOOR
 SWING, SEE:
 3A) 2014 ACCESS. CODE SECTION 404.2.4.1 AND FIGURE (E)
 54 INCHES.
 3B) 2014 FBC-B 1005.7.1 DOORS. DOORS, WHEN FULLY
 OPENED, SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN 7 INCHES. DOORS IN ANY POSITION SHALL NOT REDUCE
 THE REQUIRED WIDTH BY MORE THAN ONE-HALF. 36 + 22= 58
 INCHES.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-11-17 Cont ID  
Sent By vperez Date 2016-11-17 Time 17:27 Rev Time 0.00
Received By vperez Date 2016-11-17 Time 17:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-11-02 Cont ID  
Sent By mvaldes Date 2016-11-02 Time 15:57 Rev Time 0.00
Received By mvaldes Date 2016-11-02 Time 14:07 Sent To  
Notes
2016-11-02 16:00:34REVISION 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] A GROUNDED CONDUCTOR SHALL NOT BE CONNECTED TO
 NORMALLY NON-CURRENT-CARRYING METAL PARTS OF EQUIPMENT,
 TO EQUIPMENT GROUNDING CONDUCTOR(S), OR BE RECONNECTED
 TO GROUND ON THE LOAD SIDE OF THE SERVICE DISCONNECTING
 MEANS. PLEASE SEPERATE NUETRAL FROM GROUND AT PANEL "C"
 AS PER NEC 250.24(A)(5).

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-27 Cont ID  
Sent By albarran Date 2016-09-27 Time 18:31 Rev Time 0.00
Received By albarran Date 2016-09-27 Time 16:00 Sent To  
Notes
2016-09-27 18:32:18ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 4912 S. DIXIE HWY.
 DESCRIPTION: REVISION TO MASTER.
 MASTER PERMIT: 15090611
 REVISION NUMBER: 16090394
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. SHEET E0.1: CORRECT NOTE PART I, C1 TO READY NEC
 2011.
 2. SHEET E2.1: FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL:
 DAYLIGHT ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN
 THE DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF
 GENERAL AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE
 WITH EITHER SECTION C405.2.2.3.1 OR SECTION
 C405.2.2.3.2.
 3. SHEET E2.1: EXIT LIGHT MISSING AT THE WEST DOOR.
 4. SHEET E2.2: FBC-R404.1 LIGHTING EQUIPMENT
 (MANDATORY). A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS.
 5. SHEET E3.1: NEC 210.62 SHOW WINDOWS. AT LEAST ONE
 RECEPTACLE OUTLET SHALL BE INSTALLED WITHIN 18? OF THE
 TOP OF A SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR
 PORTION THEREOF AREA MEASURED HORIZONTALLY.
 6. SHEET E3.2: IF ROOM 200 (KITCHEN) IS TO BE A KITCHEN
 AS PART OF THIS PERMIT, PROPER OUTLET PLACEMENT AND
 SPACING WILL BE REQUIRED ON DRAWINGS. IF IT IS NOT PART
 OF THIS SCOPE, A NOTE WILL BE ADDED TO EXCLUDE THE
 KITCHEN FROM THIS PERMIT.
 7. SHEET E6.1: FBC-ER3609.3 NEC 250.94 BONDING FOR
 OTHER SYSTEMS. THE INTER-SYSTEM BONDING TERMINAL
 PRESCRIBED SHALL BE INSTALLED.
 8. SHEET E6.1: FBC-RE3601.6.2 NEC 240.24 LOCATION IN OR
 ON PREMISES. (A) & (B) PANELS SHALL BE LOCATED SUCH
 THAT OVER CURRENT DEVICES ARE ACCESSIBLE AND THAT
 OCCUPANTS SHALL HAVE ACCESS TO OCP DEVICES. THIS
 APPLIES TO PANEL C WITH MDP NOT ACCESSIBLE.
 9. SHEET E6.1: YOU SHALL INCLUDE WITH THE RISER DIAGRAM
 COMPLETE LOAD CALCS AS REQUIRED BY CODE.
 10. FBC-R303.9 REQUIRED HEATING. WHEN THE WINTER DESIGN
 TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C),
 EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING
 FACILITIES CAPABLE OF MAINTAINING A MINIMUM ROOM
 TEMPERATURE OF 68?F (20?C) AT A POINT 3 FEET (914 MM)
 ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS
 IN ALL HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE
 INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS
 SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS
 SECTION.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-10-21 Cont ID  
Sent By pleduc Date 2016-10-21 Time   Rev Time 0.00
Received By pleduc Date 2016-10-21 Time 12:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-09-16 Cont ID  
Sent By pleduc Date 2016-09-16 Time   Rev Time 0.00
Received By pleduc Date 2016-09-16 Time 09:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-17 Cont ID  
Sent By vperez Date 2016-11-17 Time 17:27 Rev Time 0.00
Received By vperez Date 2016-11-17 Time 17:27 Sent To  
Notes
2016-11-16 14:21:12RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-15 Cont ID  
Sent By cpuell Date 2016-11-15 Time 13:43 Rev Time 0.00
Received By cpuell Date 2016-10-19 Time 12:43 Sent To  
Notes
2016-10-20 12:43:24C25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-13 Cont ID  
Sent By jwitmer Date 2016-10-13 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2016-09-13 Time 12:34 Sent To  
Notes
2016-09-14 12:35:04C25

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-09-23 Cont ID  
Sent By ccole Date 2016-09-23 Time 16:16 Rev Time 0.00
Received By ccole Date 2016-09-23 Time 16:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-10-29 Cont ID  
Sent By gjohnson Date 2016-10-29 Time 11:55 Rev Time 0.00
Received By gjohnson Date 2016-10-29 Time 11:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-10-11 Cont ID  
Sent By gjohnson Date 2016-10-11 Time 06:15 Rev Time 0.00
Received By tklarge Date 2016-10-11 Time 04:41 Sent To  
Notes
2016-10-12 08:59:201) SHT. P2.1 - THERE IS A DRYWELL THAT APPEARS TO BE
 LOCATED UNDER AN EXTERIOR RAMP. CLARIFY.
 2) SHOW THE FUTURE WATER LINE TO THE SECOND FLOOR ON
 THE WATER RISER.
 3) THE TEMPERATURE OF THE HOT WATER FROM THE
 INSTANTANEOUS WATER HEATER SHALL BE CONTROLLED BY A
 TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070
 AND SHALL LIMIT THE TEMPERATURE TO 110 DEGREES. FPC
 607.1.2.
 4) SHT. P5.1 - SUBMIT AN EXPANDED SANITARY RISER
 DIAGRAM FOR REVIEW. IT APPEARS AS THOUGH THE DRINKING
 FOUNTAIN MAY BE INSTALLED ON A WET VENT.
 5) THE SINK IN THE WORK ROOM APPEARS TO BE INSTALLED ON
 A HORIZONTAL WET VENT. ONLY THE FIXTURES LOCATED IN A
 BATHROOM GROUP SHALL DISCHARGE INTO A HORIZONTAL WET
 VENT PER FPC SEC.912.1. REFER TO THE DEFINITION OF
 BATHROOM GROUP IN FPC SEC. 202.
 6) THE RISER DIAGRAM SHOWS A FLAT, DRY VENT FOR THE TWO
 FLOOR DRAINS IN THE PAPER MAKING AREA. THE VENT SHALL
 CONNECT TO THE HORIZONTAL DRAIN ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE. FPC SEC.905.3.
 7) THE WASHING MACHINE SHALL BE INSTALLED ON A 3 INCH
 STACK. FPC SEC. 406.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-11-15 Cont ID  
Sent By ajones Date 2016-11-15 Time 16:56 Rev Time 0.00
Received By ajones Date 2016-11-15 Time 16:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-09-21 Cont ID  
Sent By ajones Date 2016-09-21 Time 16:30 Rev Time 0.00
Received By ajones Date 2016-09-21 Time 16:30 Sent To  
Notes
2016-09-21 16:31:349/21/16- SEPERATE PERMITS REQUIRED FOR PARKING LOT AND
 LANDSCAPING