Plan Review Details - Permit 16090364
Plan Review Stops For Permit 16090364
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-12-01 Cont ID  
Sent By tklarge Date 2017-12-01 Time 10:11 Rev Time 0.00
Received By tklarge Date 2017-12-01 Time 10:10 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-06 Cont ID  
Sent By cpuell Date 2017-11-06 Time 15:24 Rev Time 0.00
Received By cpuell Date 2017-11-02 Time 12:48 Sent To  
Notes
2017-11-03 12:48:40RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-24 Cont ID  
Sent By tklarge Date 2017-04-24 Time 06:57 Rev Time 0.00
Received By tklarge Date 2017-04-19 Time 10:06 Sent To  
Notes
2017-04-20 10:06:43RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-13 Cont ID  
Sent By tklarge Date 2016-09-13 Time 06:28 Rev Time 0.00
Received By tklarge Date 2016-09-12 Time 15:27 Sent To  
Notes
2016-09-12 15:28:21ROUTED TO PLUMB <5K

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-12-01 Cont ID  
Sent By tklarge Date 2017-12-01 Time 10:10 Rev Time 0.00
Received By tklarge Date 2017-12-01 Time 10:10 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-11-06 Cont ID  
Sent By thunt Date 2017-11-06 Time 14:35 Rev Time 0.00
Received By thunt Date 2017-11-06 Time 14:35 Sent To  
Notes
2017-11-06 14:43:4211/6/17 PLUMBING 3RD REVIEW**DENIED**
  
 THESE COMMENTS FROM THE 2ND REVIEW HAVE NOT BEEN
 ADDRESSED: IT IS RECOMMENDED YOU CONTACT THE PLAN
 REVIEW TO REVIEW COMMENTS.
  
 1) SUBMIT FACTORY SIZING CALCULATIONS SHOWING HOW YOU
 DETERMINED THE GB-35 WAS SIZED FOR THIS APPLICATION.
 FBC-P 1003.2
  
 2) THE MIN SIZE FOR THE REQUIRED TEST PORT IS 4".TTHE
 SEWER LINE CAN NOT THEN BE REDUCED TO 2" .FBC-P 704.2
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-04-24 Cont ID  
Sent By tklarge Date 2017-04-24 Time 06:57 Rev Time 0.00
Received By tklarge Date 2017-04-24 Time 06:57 Sent To  
Notes
2017-04-24 06:49:221) REMOVE ALL OLD DOCUMENTS FROM THE SUBMITTAL PACKAGE
 AND SUBMIT TWO COPIES OF THE GREASE INTERCEPTOR THAT IS
 GOING TO BE INSTALLED.(THERE ARE SPECS FOR A DORMONT
 UNIT AND ALSO A SCHIER UNIT. WHICH IS IT?) WPB AMEND.
 TO FBC SEC. 107.1.
 2) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER IF
 THAT IS THE PRODUCT THAT IS GOING TO BE INSTALLED. 2014
 FBC-PLUMBING SEC. 1003.2. CONTACT SCHIER REPRESENTATIVE
 LEE SCHNEEWEISS AT 800-538-4792.
 3) THE DISHWASHER AND THE SINK SHALL BE INDIRECTLY
 WASTED PER 2014 FBC-PLUMBING SECS.802.1.6 & 802.1.8.
 4) SUBMIT A PLAN VIEW SHOWING THE LOCATION OF THE
 GREASE INTERCEPTOR. THE PLAN CAN BE HAND DRAWN.WPB
 AMEND. TO FBC SEC. 107.2.1.
 5) A TEST PORT IS REQUIRED ON THE DISCHARGE SIDE OF THE
 GREASE INTERCEPTOR. THE MINIMUM SIZE OF THE TEST PORT
 SHALL BE 4 INCHES.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-09-13 Cont ID  
Sent By tklarge Date 2016-09-13 Time 06:27 Rev Time 0.00
Received By tklarge Date 2016-09-13 Time 06:09 Sent To  
Notes
2016-09-13 06:20:171) YOU HAVE SUBMITTED SPECIFICATIONS FOR FOUR DIFFERENT
 MODELS OF A GREASE TRAP? WHICH MODEL IS BEING
 INSTALLED? SUBMIT TWO COPIES OF SPECIFICATIONS ONLY FOR
 THE MODEL BEING INSTALLED. WPB AMEND. TO FBC SEC.
 107.1.
 2) SUBMIT SIZING CALCULATIONS FOR THE GREASE TRAP. 2014
 FPV SEC. 1003.2.
 3) SUBMIT SANITARY RISER FOR PIPING TO BE INSTALLED.
 SHOW ALL REQUIRED VENTS.
 4) ALL INDIRECT WASTE PIPING THAT EXCEEDS 30 INCHES IN
 DEVELOPED LENGTH MEASURED HORIZONTALLY SHALL BE TRAPPED
 OR 54 INCHES IN TOTAL DEVELOPED LENGTH SHALL BE
 TRAPPED.
 5) WILL ANY OF THE PIPING BE INSTALLED UNDER THE SLAB/
 IF SO, SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE
 GREASE TRAP.WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692