Plan Review Stops For Permit 16090226 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2016-11-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-11-18 |
Time |
10:27 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-11-18 |
Time |
10:27 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-10-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-10-04 |
Time |
17:55 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-10-04 |
Time |
17:55 |
Sent To |
|
|
Notes |
2016-10-04 17:28:27 | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SHOW COMPLIANCE WITH FBC-R 310.1 EMERGENCY ESCAPE | | AND RESCUE WINDOWS IN BEDROOM NUMBER 3. | | | | 2) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED | | TO INSTALL THE ROOF TILE. IF AN ADHESIVE WILL BE USED, | | SUBMIT TWO COPIES OF THE PRODUCT APPROVAL FOR THE | | ADHESIVE. FBC 107.2.1 & FAC RULE 9N-3. | | | | 3) THE ENERGY CALCULATIONS FOR THE MAIN HOUSE LISTS THE | | NUMBER OF OCCUPANTS AS 6 IN THE MASTER BEDROOM AREA AND | | 10 IN THE MAIN AREA FOR A TOTAL OF 16. A FOUR BEDROOM | | HOUSE WILL TYPICALLY HAVE 8 OCCUPANTS. FBC ENERGY | | CONSERVATION R405 | | | | 4) THE ENERGY CALCULATION FORMS FOR THE GUEST HOUSE | | LISTS THE HEAT SYSTEM AS 21.3 KBTU/HR (6.2 KW) AND THE | | EQUIPMENT SCHEDULE ON THE HVAC PLANS SPECIFIES 8 KW FOR | | THE HEAT. PLEASE CLARIFY. | | | | 5) THIS PROPERTY IS ZONED SF7, THE GUEST HOUSE MAY NOT | | BE ALLOWED TO HAVE A FULL KITCHEN AS INDICATED ON THE | | PLANS. CHECK WITH THE WEST PALM BEACH ZONING DIVISION. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-11-18 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-11-18 |
Time |
16:09 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-11-18 |
Time |
16:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-09-16 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-09-16 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-09-16 |
Time |
10:01 |
Sent To |
|
|
Notes |
2016-09-16 10:03:48 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 | | COMMENTS: | | | | | | 1-PLEASE NOTE THAT ALL CIRCUITS? DESIGNATION AT THE | | PANELBOARDS MUST INDICATE WHAT AREA SPECIFICALLY OF THE | | HOUSE IT?S SERVICING. GENERAL LIGHTING DOES NOT MEET | | THESE REQUIREMENTS. EXAMPLE, LABEL BEDROOM 1, BEDROOM 2 | | ETC.?NEC 408.4 FIELD ID REQUIRED. FBC 107.3.5 | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-11-18 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2016-11-18 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2016-11-01 |
Time |
13:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-10-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-10-04 |
Time |
17:55 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-09-08 |
Time |
12:52 |
Sent To |
|
|
Notes |
2016-09-08 12:53:03 | R11 | | **TRAVELLING WITH 16090221** |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2016-11-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-11-22 |
Time |
14:48 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-11-22 |
Time |
14:48 |
Sent To |
|
|
Notes |
2016-11-22 14:49:29 | MU-2016-28763 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2016-10-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-10-04 |
Time |
17:29 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-10-04 |
Time |
17:29 |
Sent To |
|
|
Notes |
2016-10-04 17:29:00 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2016-11-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-11-18 |
Time |
10:39 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-11-18 |
Time |
10:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2016-10-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-10-04 |
Time |
17:30 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-10-04 |
Time |
17:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2016-11-08 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-11-08 |
Time |
11:54 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-11-07 |
Time |
13:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2016-09-30 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-09-30 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-09-30 |
Time |
14:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2016-11-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-11-18 |
Time |
10:27 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-11-18 |
Time |
10:27 |
Sent To |
|
|
Notes |
2016-11-18 10:27:24 | NOA NO. 11-0321.03, EAGLE ROOFING PRODUCTS LLC, | | CAPISTRANO CONCRETE TILE |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2016-11-15 |
Time |
|
Rev Time |
0.00 |
Received By |
awooten |
Date |
2016-11-10 |
Time |
09:00 |
Sent To |
|
|
Notes |
2016-11-15 09:01:05 | *****ZONING PROVISO*** | | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY, | | THE FOLLOWING CONDITIONS SHALL BE ADDRESSED: | | | | 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN, | | SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. | | 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED | | LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL | | LANDSCAPE INSPECTION. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2016-09-20 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2016-09-20 |
Time |
15:33 |
Rev Time |
0.00 |
Received By |
awooten |
Date |
2016-09-20 |
Time |
15:31 |
Sent To |
|
|
Notes |
2016-09-20 15:32:52 | ********ZONING REVIEW FAILED*********************** | | | | THIS PROPERTY IS LOCATED IN SF-7 ZONING DISTRICT, WHICH | | IS A SINGLE FAMILY DISTRICT. THE GUEST HOUSE IS NOT | | PERMITTED TO HAVE A KITCHEN DUE TO THE FACT IT WOULD BE | | CONSIDERED ANOTHER UNIT, WHICH IS NOT PERMITTED IN A | | SINGLE FAMILY DISTRICT. | | | | PLEASE REMOVE KITCHEN FROM PLANS. | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | PLANNING DEPARTMENT WEBSITE AT | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | CONTACT ME. | | | | ALANA WOOTEN, ASSOCIATE PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: 561-822-1449 | | E-MAIL: [email protected] | | |
|
|