Plan Review Details - Permit 16090221
Plan Review Stops For Permit 16090221
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-11-18 Cont ID  
Sent By rmcdouga Date 2016-11-18 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2016-11-17 Time 19:04 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-04 Cont ID  
Sent By rmcdouga Date 2016-10-04 Time 17:00 Rev Time 0.00
Received By rmcdouga Date 2016-10-04 Time 07:08 Sent To  
Notes
2016-10-04 15:12:57PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH FBC-R 310.1 EMERGENCY ESCAPE
 AND RESCUE WINDOWS IN BEDROOM NUMBER 3.
  
 2) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE ROOF TILE. IF AN ADHESIVE WILL BE USED,
 SUBMIT TWO COPIES OF THE PRODUCT APPROVAL FOR THE
 ADHESIVE. FBC 107.2.1 & FAC RULE 9N-3.
  
 3) THE ENERGY CALCULATIONS FOR THE MAIN HOUSE LISTS THE
 NUMBER OF OCCUPANTS AS 6 IN THE MASTER BEDROOM AREA AND
 10 IN THE MAIN AREA FOR A TOTAL OF 16. A FOUR BEDROOM
 HOUSE WILL TYPICALLY HAVE 8 OCCUPANTS. FBC ENERGY
 CONSERVATION R405
  
 4) THE ENERGY CALCULATION FORMS FOR THE GUEST HOUSE
 LISTS THE HEAT SYSTEM AS 21.3 KBTU/HR (6.2 KW) AND THE
 EQUIPMENT SCHEDULE ON THE HVAC PLANS SPECIFIES 8 KW FOR
 THE HEAT. PLEASE CLARIFY.
  
 5) THIS PROPERTY IS ZONED SF7, THE GUEST HOUSE MAY NOT
 BE ALLOWED TO HAVE A FULL KITCHEN AS INDICATED ON THE
 PLANS. CHECK WITH THE WEST PALM BEACH ZONING DIVISION.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-11-18 Cont ID  
Sent By vperez Date 2016-11-18 Time 15:32 Rev Time 0.00
Received By vperez Date 2016-11-18 Time 15:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-16 Cont ID  
Sent By vperez Date 2016-09-16 Time 08:38 Rev Time 0.00
Received By vperez Date 2016-09-16 Time 08:38 Sent To  
Notes
2016-09-16 10:00:47INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND
 LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC
 RATINGS. FBC 107.3.5
 2. REVISE SERVICE CONDUCTORS, UNDERSIZED FOR A 400AMP
 SERVICE. FBC RES E3603
 3. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS
 FOR LOW VOLTAGE SYSTEMS AND POOL. FBC 107.3.5
 4. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 PER FBC RES E3609.3
 5. GROUNDING ELECTRODE CONDUCTOR IS UNDERSIZED FOR
 400AMP SERVICE. #2 REQUIRED PER NEC 250.66. FBC RES
 E3603
 6. PLEASE SHOW THE FEEDER CONDUCTOR SIZES AND EQUIPMENT
 GROUNDING CONDUCTOR REQUIRED WITH THESE FEEDERS. FBC
 107.3.5
 7. PLEASE NOTE THAT THE RISER DIAGRAM DOES NOT MATCH
 THE FLOOR PLAN LAYOUT OF PANEL LOCATION. IF 400A PANEL
 IS LOCATED IN GARAGE SHOWN AS A 200AMP PANEL, CORRELATE
 AND CORRECT. IF THERE IS A MAIN CB, AS SHOWN OUTSIDE
 PLEASE SHOW ON RISER DIAGRAM. LABEL EQUIPMENT AS RATED
 FOR SERVICE ENTRANCE AND PROPER NEMA 3R RATING. FBC
 107.3.5
 8. CLARIFY BUS RATING FOR PANEL P SHOWN AT 60AMP; IS IT
 100 AMP POOL PANEL? TYPICAL. FBC 107.3.5
 9. AT THE RISER DIAGRAM SHOW CONDUCTOR SIZE FOR PANEL
 B. FBC RES E3603
 10. SHOW EXTERIOR RECEPTACLE AT REAR PROTECTED BY GFCI
 DEVICE. FBC RES E3902.3
 11. RECEPTACLE AT WALL SPACE IN KITCHEN AREA WITHIN 6FT
 OF SINK TO BE LABELED AS GFCI PROTECTED. FBC RES
 E3902.7
 12. RECEPTACLE AT WALL SPACE IN WET BAR AREA WITHIN 6FT
 OF SINK TO BE LABELED AS GFCI PROTECTED. FBC RES
 E3902.7
 13. SHOW JACUZZI AND GARAGE DOOR OPENER DEVICES TO BE
 PROTECTED BY GFCI BREAKER TO BE READILY ACCESSIBLE. A
 NOTE WILL SUFFICE.
 14. PLEASE NOTE THAT ALL CIRCUITS? DESIGNATION AT THE
 PANELBOARDS MUST INDICATE WHAT AREA SPECIFICALLY OF THE
 HOUSE IT?S SERVICING. GENERAL LIGHTING DOES NOT MEET
 THESE REQUIREMENTS. EXAMPLE, LABEL BEDROOM 1, BEDROOM 2
 ETC.?NEC 408.4 FIELD ID REQUIRED. FBC 107.3.5
 15. PROVIDE A NOTE TO INDICATE REQUIRED TAMPER
 RESISTANT RECEPTACLE THROUGHOUT. FBC RES E4002.14
 16. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO
 INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS.
 17. PLEASE SHOW ON PANELBOARD 20A CIRCUITS REQUIRED FOR
 DINING ROOM RECEPTACLES AND BATHROOM RECEPTACLES. FBC
 RES E3703.2 AND 4
 18. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-09-30 Cont ID  
Sent By gjohnson Date 2016-09-30 Time 15:30 Rev Time 0.00
Received By gjohnson Date 2016-09-30 Time 15:30 Sent To  
Notes
2016-09-30 15:32:07GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
  
 GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-18 Cont ID  
Sent By vperez Date 2016-11-18 Time 15:32 Rev Time 0.00
Received By vperez Date 2016-11-18 Time 15:32 Sent To  
Notes
2016-11-02 13:05:16R17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-04 Cont ID  
Sent By rmcdouga Date 2016-10-04 Time 17:00 Rev Time 0.00
Received By rmcdouga Date 2016-09-08 Time 12:51 Sent To  
Notes
2016-09-08 12:51:58R11
 **TRAVELLING WITH 16090226**

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2016-11-22 Cont ID  
Sent By rmcdouga Date 2016-11-22 Time 14:47 Rev Time 0.00
Received By rmcdouga Date 2016-11-22 Time 14:47 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By rmcdouga Date 2016-10-03 Time 17:24 Rev Time 0.00
Received By rmcdouga Date 2016-10-03 Time 17:24 Sent To  
Notes
2016-10-03 17:25:19BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-11-17 Cont ID  
Sent By rmcdouga Date 2016-11-17 Time 17:36 Rev Time 0.00
Received By rmcdouga Date 2016-11-17 Time 16:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-10-04 Cont ID  
Sent By rmcdouga Date 2016-10-04 Time 07:08 Rev Time 0.00
Received By rmcdouga Date 2016-10-04 Time 07:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-11-08 Cont ID  
Sent By gjohnson Date 2016-11-08 Time 11:51 Rev Time 0.00
Received By gjohnson Date 2016-11-08 Time 11:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-09-30 Cont ID  
Sent By gjohnson Date 2016-09-30 Time 14:23 Rev Time 0.00
Received By gjohnson Date 2016-09-30 Time 08:57 Sent To  
Notes
2016-09-30 15:28:371ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT S-1 THE MASTER-BATH TUB AND BIDET ARE MISSING
 FROM TH RISER DIAGRAM AND FLAT FLOOR PLAN ALL FIXTURES
 SHALL BE SHOWN ON PLANS. PER WPB AMEND. TO FBC 107.2.1
  
 2. SHT. S-1 THE WAT THE MASTER BATH TOILET IS VENTED ON
 THE RISER IT WILL HAVE A VENT IN THE MIDDLE OF THE
 FLOOR , THE VENT FOR THE LAVATORY CAN SERVE THE
 BATHROOM GROUP PROVIDE ALL THE FIXTURES ARE CONNECTED
 ON THE SAME BRANCH DRAIN .
 PER FBC RES P3108.1
  
 3. THE KITCHEN, LAUNDRY AND WET BAR OFF DINNING ROOM
 SHALL ALL CONNECT TO BUILDING DRAIN DOWN STREAM OF
 POWDER ROOM BATHROOM GROUP. PER PER FBC RES P3108.1
  
 4. THE RISER DIAGRAM DOES NOT MATCH FLAT FLOOR PLAN
 PLEASE CLARIFY. PER WPB AMEND. TO FBC 107.2.1
  
 5. PLEASE PROVIDE A WATER RISER DIAGRAM/ PER WPB AMEND
 TO FBC 107.3.5.3
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2016-11-18 Cont ID  
Sent By rmcdouga Date 2016-11-18 Time 09:20 Rev Time 0.00
Received By rmcdouga Date 2016-11-18 Time 09:20 Sent To  
Notes
2016-11-18 09:23:32NOA NO. 11-0321.03, EAGLE ROOFING PRODUCTS LLC,
 CAPISTRANO CONCRETE TILE

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2016-11-10 Time   Rev Time 0.00
Received By awooten Date 2016-11-10 Time 08:22 Sent To  
Notes
2016-11-10 16:40:37*****ZONING PROVISO***
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE FOLLOWING CONDITIONS SHALL BE ADDRESSED:
  
 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN,
 SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW.
 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.

Review Stop Z ZONING
Rev No 1 Status F Date 2016-09-20 Cont ID  
Sent By nwair Date 2016-09-20 Time 15:30 Rev Time 0.00
Received By awooten Date 2016-09-16 Time 15:15 Sent To  
Notes
2016-09-20 15:30:31********ZONING REVIEW FAILED***********************
  
 THE DRIVEWAY WILL BE UNDER A SEPARATE PERMIT.
  
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPING ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR.
  
 SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION PLANS
 SHOWING COMPLIANCE WITH LANDSCAPE CODE:
  
 SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
  
 ******FOR ZONING REVIEW OF GUEST HOUSE SEE PERMIT #
 16090226*********
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 ALANA WOOTEN, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1449
 E-MAIL: [email protected]
  