Plan Review Stops For Permit 16090221 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2016-11-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-11-18 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-11-17 |
Time |
19:04 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-10-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-10-04 |
Time |
17:00 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-10-04 |
Time |
07:08 |
Sent To |
|
|
Notes |
2016-10-04 15:12:57 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SHOW COMPLIANCE WITH FBC-R 310.1 EMERGENCY ESCAPE | | AND RESCUE WINDOWS IN BEDROOM NUMBER 3. | | | | 2) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED | | TO INSTALL THE ROOF TILE. IF AN ADHESIVE WILL BE USED, | | SUBMIT TWO COPIES OF THE PRODUCT APPROVAL FOR THE | | ADHESIVE. FBC 107.2.1 & FAC RULE 9N-3. | | | | 3) THE ENERGY CALCULATIONS FOR THE MAIN HOUSE LISTS THE | | NUMBER OF OCCUPANTS AS 6 IN THE MASTER BEDROOM AREA AND | | 10 IN THE MAIN AREA FOR A TOTAL OF 16. A FOUR BEDROOM | | HOUSE WILL TYPICALLY HAVE 8 OCCUPANTS. FBC ENERGY | | CONSERVATION R405 | | | | 4) THE ENERGY CALCULATION FORMS FOR THE GUEST HOUSE | | LISTS THE HEAT SYSTEM AS 21.3 KBTU/HR (6.2 KW) AND THE | | EQUIPMENT SCHEDULE ON THE HVAC PLANS SPECIFIES 8 KW FOR | | THE HEAT. PLEASE CLARIFY. | | | | 5) THIS PROPERTY IS ZONED SF7, THE GUEST HOUSE MAY NOT | | BE ALLOWED TO HAVE A FULL KITCHEN AS INDICATED ON THE | | PLANS. CHECK WITH THE WEST PALM BEACH ZONING DIVISION. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-11-18 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-11-18 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-11-18 |
Time |
15:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-09-16 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-09-16 |
Time |
08:38 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-09-16 |
Time |
08:38 |
Sent To |
|
|
Notes |
2016-09-16 10:00:47 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 | | COMMENTS: | | | | 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND | | LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC | | RATINGS. FBC 107.3.5 | | 2. REVISE SERVICE CONDUCTORS, UNDERSIZED FOR A 400AMP | | SERVICE. FBC RES E3603 | | 3. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS | | FOR LOW VOLTAGE SYSTEMS AND POOL. FBC 107.3.5 | | 4. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE | | PER FBC RES E3609.3 | | 5. GROUNDING ELECTRODE CONDUCTOR IS UNDERSIZED FOR | | 400AMP SERVICE. #2 REQUIRED PER NEC 250.66. FBC RES | | E3603 | | 6. PLEASE SHOW THE FEEDER CONDUCTOR SIZES AND EQUIPMENT | | GROUNDING CONDUCTOR REQUIRED WITH THESE FEEDERS. FBC | | 107.3.5 | | 7. PLEASE NOTE THAT THE RISER DIAGRAM DOES NOT MATCH | | THE FLOOR PLAN LAYOUT OF PANEL LOCATION. IF 400A PANEL | | IS LOCATED IN GARAGE SHOWN AS A 200AMP PANEL, CORRELATE | | AND CORRECT. IF THERE IS A MAIN CB, AS SHOWN OUTSIDE | | PLEASE SHOW ON RISER DIAGRAM. LABEL EQUIPMENT AS RATED | | FOR SERVICE ENTRANCE AND PROPER NEMA 3R RATING. FBC | | 107.3.5 | | 8. CLARIFY BUS RATING FOR PANEL P SHOWN AT 60AMP; IS IT | | 100 AMP POOL PANEL? TYPICAL. FBC 107.3.5 | | 9. AT THE RISER DIAGRAM SHOW CONDUCTOR SIZE FOR PANEL | | B. FBC RES E3603 | | 10. SHOW EXTERIOR RECEPTACLE AT REAR PROTECTED BY GFCI | | DEVICE. FBC RES E3902.3 | | 11. RECEPTACLE AT WALL SPACE IN KITCHEN AREA WITHIN 6FT | | OF SINK TO BE LABELED AS GFCI PROTECTED. FBC RES | | E3902.7 | | 12. RECEPTACLE AT WALL SPACE IN WET BAR AREA WITHIN 6FT | | OF SINK TO BE LABELED AS GFCI PROTECTED. FBC RES | | E3902.7 | | 13. SHOW JACUZZI AND GARAGE DOOR OPENER DEVICES TO BE | | PROTECTED BY GFCI BREAKER TO BE READILY ACCESSIBLE. A | | NOTE WILL SUFFICE. | | 14. PLEASE NOTE THAT ALL CIRCUITS? DESIGNATION AT THE | | PANELBOARDS MUST INDICATE WHAT AREA SPECIFICALLY OF THE | | HOUSE IT?S SERVICING. GENERAL LIGHTING DOES NOT MEET | | THESE REQUIREMENTS. EXAMPLE, LABEL BEDROOM 1, BEDROOM 2 | | ETC.?NEC 408.4 FIELD ID REQUIRED. FBC 107.3.5 | | 15. PROVIDE A NOTE TO INDICATE REQUIRED TAMPER | | RESISTANT RECEPTACLE THROUGHOUT. FBC RES E4002.14 | | 16. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO | | INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS. | | 17. PLEASE SHOW ON PANELBOARD 20A CIRCUITS REQUIRED FOR | | DINING ROOM RECEPTACLES AND BATHROOM RECEPTACLES. FBC | | RES E3703.2 AND 4 | | 18. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | QUESTIONS OR CONCERNS. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2016-09-30 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-09-30 |
Time |
15:30 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-09-30 |
Time |
15:30 |
Sent To |
|
|
Notes |
2016-09-30 15:32:07 | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | | | | | GAS PLAN REVIEW | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT | | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE | | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | 107.2.1. | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | FBC-R, SEC. G2404.3. | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | GAS SEC. 301.3. | | | | A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION. | | | | GAS PERMIT APPLICATION REQUIREMENTS | | | | EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL | | BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING | | IN THE CITY OF WEST PALM BEACH: | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB | | AMENDMENTS TO FBC SEC. 107.2.1. | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37). | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? | | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE | | SEC. 402.4.1. | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | PSI. | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | SEC. 502 THRU 505. | | | | 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP | | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF | | THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, | | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY | | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK | | PER NFPA 58, TABLE 3-2.2.2. | | | | 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS | | ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF | | THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS | | BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED | | PER NFPA 58 SECTION 3-2.2.7(H). | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-11-18 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-11-18 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-11-18 |
Time |
15:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-10-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-10-04 |
Time |
17:00 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-09-08 |
Time |
12:51 |
Sent To |
|
|
Notes |
2016-09-08 12:51:58 | R11 | | **TRAVELLING WITH 16090226** |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
N |
Date |
2016-11-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-11-22 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-11-22 |
Time |
14:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2016-10-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-10-03 |
Time |
17:24 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-10-03 |
Time |
17:24 |
Sent To |
|
|
Notes |
2016-10-03 17:25:19 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2016-11-17 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-11-17 |
Time |
17:36 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-11-17 |
Time |
16:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2016-10-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-10-04 |
Time |
07:08 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-10-04 |
Time |
07:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2016-11-08 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-11-08 |
Time |
11:51 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-11-08 |
Time |
11:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2016-09-30 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-09-30 |
Time |
14:23 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-09-30 |
Time |
08:57 |
Sent To |
|
|
Notes |
2016-09-30 15:28:37 | 1ST REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1. SHT S-1 THE MASTER-BATH TUB AND BIDET ARE MISSING | | FROM TH RISER DIAGRAM AND FLAT FLOOR PLAN ALL FIXTURES | | SHALL BE SHOWN ON PLANS. PER WPB AMEND. TO FBC 107.2.1 | | | | 2. SHT. S-1 THE WAT THE MASTER BATH TOILET IS VENTED ON | | THE RISER IT WILL HAVE A VENT IN THE MIDDLE OF THE | | FLOOR , THE VENT FOR THE LAVATORY CAN SERVE THE | | BATHROOM GROUP PROVIDE ALL THE FIXTURES ARE CONNECTED | | ON THE SAME BRANCH DRAIN . | | PER FBC RES P3108.1 | | | | 3. THE KITCHEN, LAUNDRY AND WET BAR OFF DINNING ROOM | | SHALL ALL CONNECT TO BUILDING DRAIN DOWN STREAM OF | | POWDER ROOM BATHROOM GROUP. PER PER FBC RES P3108.1 | | | | 4. THE RISER DIAGRAM DOES NOT MATCH FLAT FLOOR PLAN | | PLEASE CLARIFY. PER WPB AMEND. TO FBC 107.2.1 | | | | 5. PLEASE PROVIDE A WATER RISER DIAGRAM/ PER WPB AMEND | | TO FBC 107.3.5.3 | | | | | | | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2016-11-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-11-18 |
Time |
09:20 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-11-18 |
Time |
09:20 |
Sent To |
|
|
Notes |
2016-11-18 09:23:32 | NOA NO. 11-0321.03, EAGLE ROOFING PRODUCTS LLC, | | CAPISTRANO CONCRETE TILE |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2016-11-10 |
Time |
|
Rev Time |
0.00 |
Received By |
awooten |
Date |
2016-11-10 |
Time |
08:22 |
Sent To |
|
|
Notes |
2016-11-10 16:40:37 | *****ZONING PROVISO*** | | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY, | | THE FOLLOWING CONDITIONS SHALL BE ADDRESSED: | | | | 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN, | | SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. | | 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED | | LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL | | LANDSCAPE INSPECTION. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2016-09-20 |
|
|
Cont ID |
|
Sent By |
nwair |
Date |
2016-09-20 |
Time |
15:30 |
Rev Time |
0.00 |
Received By |
awooten |
Date |
2016-09-16 |
Time |
15:15 |
Sent To |
|
|
Notes |
2016-09-20 15:30:31 | ********ZONING REVIEW FAILED*********************** | | | | THE DRIVEWAY WILL BE UNDER A SEPARATE PERMIT. | | | | PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPING ON THE | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. | | | | SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION PLANS | | SHOWING COMPLIANCE WITH LANDSCAPE CODE: | | | | SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY | | DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT | | TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF | | OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY | | DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR | | EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF. | | | | ******FOR ZONING REVIEW OF GUEST HOUSE SEE PERMIT # | | 16090226********* | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | PLANNING DEPARTMENT WEBSITE AT | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | CONTACT ME. | | | | ALANA WOOTEN, ASSOCIATE PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: 561-822-1449 | | E-MAIL: [email protected] | | |
|
|