Plan Review Details - Permit 16090054
Plan Review Stops For Permit 16090054
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-23 Cont ID  
Sent By jwitmer Date 2016-09-23 Time 07:56 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-10 Cont ID  
Sent By jwitmer Date 2016-09-10 Time 09:15 Rev Time 0.00
Received By jwitmer Date 2016-09-10 Time 08:31 Sent To  
Notes
2016-09-10 09:18:50BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16090054
 ADD: 415 CLEMATIS ST. SUITE # 230
 CONT: CUTTING EDGE BUILDING
 TEL: 561-625-4545
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. SEPT. 10/ 2016
 ACTION: DENIED
  
 1) SHEET A.01 THE FLOOR PLANS INDICATE (2) PASS THRU
 WINDOWS AND COUNTERS, THE DETAILS FOR BOTH WINDOWS
 INDICATE A SECTION A04/01-2. THERE IS NO SHEET 4 NOR IS
 THERE ON THE SHEET INDEX ON THE COVERSHEET. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
 FBC-B SAFETY GLAZING 2406.1.
 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 2)SHEET A.01. IN THE X-RAY ROOM THERE IS ALSO A WINDOW
 DETAIL WINDOW A-04/03/4. THERE IS NO SHEET 4 NOR IS
 THERE ON THE SHEET INDEX ON THE COVERSHEET. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
 FBC-B 465 CONTROL OF RADIATION HAZARDS.
  
 3) SHEET A.01 THERE IS NO INFORMATION AS TO SAFE GUARDS
 FOR RADIATION CONTROL FOR THE FLOOR, WALLS NOR THE
 FLOOR/ CEILING ABOVE.
 465.5.1 SHIELDING.
 465.6 DOORS, INTERLOCKS, AND WARNING SYSTEMS.
 465.7 RADIATION MONITORING DEVICES.
  
 4) IN REVIEWING SHEET A.01 THERE IS A NOTE ON THE PLANS
 INDICATING SEE THE DOOR SCHEDULE SHEET A-2 . NO SUCH
 SHEET ,NO DOOR SCHEDULE, NOT ABLE TO CHECK THE WIDTH OF
 DOORS, FBC-B 1008.1.1. DOOR # 1 IS EXISTING /
 RELOCATED, DOOR # 19 IS NEW PLEASE PROVIDE THE FIRE
 RATING FOR EACH DOOR AND HARDWARE AS WELL AS A COMPLETE
 SCHEDULE FOR THE REMAINDER OF THE DOORS.
  
 5) SHEET A-03 THE RESTROOM ELEVATIONS SHOW THE WATER
 CLOSE GRAB BARS CENTER LINED AT 36 INCHES. PLEASE
 REVIEW THE 2014 FBC-ACCESS. CODE 609.4. THE HEIGHT OF
 THE GRAB BARS IS MEASURED FROM THE TOP OF THE GRASPING
 SURFACE NOT CENTERLINE.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-09-09 Cont ID  
Sent By vperez Date 2016-09-09 Time 11:43 Rev Time 0.00
Received By vperez Date 2016-09-09 Time 11:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-09-20 Cont ID  
Sent By pleduc Date 2016-09-20 Time   Rev Time 0.00
Received By pleduc Date 2016-09-20 Time 12:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-09-07 Cont ID  
Sent By pleduc Date 2016-09-07 Time   Rev Time 0.00
Received By pleduc Date 2016-09-07 Time 13:08 Sent To  
Notes
2016-09-07 14:06:59THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET LS 00 - THERE ARE INCORRECT REFERENCES
 INDICATED FOR THE FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
 AIR CONDITION WORK SHALL COMPLY WITH NFPA 90 A & B,
 2012 EDITION
 INSPECTION, TESTING & MAINTENANCE SHALL COMPLY WITH
 NFPA 25, 2011 EDITION.
  
 PLEASE ENSURE COMPLIANCE WITH THE APPLICABLE CODES AND
 IF REVISIONS ARE SUBMITTED PLEASE USE CLOUDED
 NOTATIONS.
  
  
 2) SHEET LS 00 - THERE IS NO INDICATION FOR FIRE
 SPRINKLER WORK.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-23 Cont ID  
Sent By jwitmer Date 2016-09-23 Time 07:56 Rev Time 0.00
Received By jwitmer Date 2016-09-16 Time 11:05 Sent To  
Notes
2016-09-16 11:06:05B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-13 Cont ID  
Sent By tklarge Date 2016-09-13 Time 04:51 Rev Time 0.00
Received By tklarge Date 2016-09-02 Time 15:25 Sent To  
Notes
2016-09-02 15:25:52B06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-09-10 Cont ID  
Sent By jwitmer Date 2016-09-10 Time 08:35 Rev Time  
Received By jwitmer Date 2016-09-10 Time 08:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-09-21 Cont ID  
Sent By ccole Date 2016-09-21 Time 13:28 Rev Time 0.00
Received By ccole Date 2016-09-21 Time 12:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-08 Cont ID  
Sent By ccole Date 2016-09-08 Time 07:50 Rev Time 0.00
Received By ccole Date 2016-09-07 Time 17:43 Sent To  
Notes
2016-09-08 07:51:051ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 EXISTING BUILDING CODES
 PERMIT #16090054
 9/8/16
  
 1) THE NEW CLINIC OCCUPANCY SHALL BE IN COMPLIANCE WITH
 THE FBC-14 ENERGY CONSERVATION CODE PER SECTIONS C101.2
 AND C101.4.4. SUBMIT DOCUMENTATION OF ENERGY
 COMPLIANCE- SEE SECTION C101.5.1.
  
 2) CLARIFY HOW THE AIR DISTRIBUTION PLAN WAS DESIGNED-
 PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH SECTION C403.2.1, AND VENTILATION
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.3 FBC-14
 MECHANICAL. PROVIDE A SCHEDULE ON THE PLAN INDICATING
 THE REQUIRED AND PROVIDED CFM'S OF OUTDOOR AIR.
  
 3) CLARIFY HOW O/A IS BEING PROVIDED TO THE SPACE, AND
 CONTROLLED- SEE SECTION C403.2.4.4
  
 4) REMOVE KEY NOTE #1 AT THE TRANSFER DUCT LOCATIONS
 AND REPLACE WITH KEY NOTE #3.
  
 5) PROVIDE A LAB EQUIPMENT SCHEDULE AND SEE TABLE
 403.3- AN EXHAUST SYSTEM MAY BE REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-09-13 Cont ID  
Sent By tklarge Date 2016-09-13 Time 04:51 Rev Time 0.00
Received By tklarge Date 2016-09-13 Time 04:12 Sent To  
Notes
***NONE***