2016-09-06 06:26:28INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE CLARIFY MAIN BREAKER SIZE AS #3 CONDUCTOR IS
 UNDERSIZED FOR A 125AMP PANELBOARD. IF 100AMP MCB IS
 EXISTING SHOW ON PLANS. NEC 310.15B16
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  