2016-09-02 06:05:17 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16081192 |
| ADD: 1200 S. FLAGLER DR. SUITE # 1503 |
| CONT: CAMBRIDGE |
| TEL: 561-784-3722 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. SEPT. 02/2016 |
| ACTION: DENIED |
| |
| 1) THE CONTRACTOR HAS NOT TAKEN OWNERSHIP OF THE PLANS |
| SUBMITTED. PLEASE NOTE THE CONTRACTOR CAN ONLY DRAW THE |
| PLANS THEY HAVE A LICENSE FOR. THE QUALIFIER FOR |
| CAMBRIDGE CONSTRUCTION MUST TAKE OWNERSHIP OF THE FLOOR |
| PLAN BY PRINTING HIS OR HER NAME, SIGNING THE PLAN WITH |
| THEIR SIGNATURE AND LICENSE NUMBER. |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.3.4.3 CERTIFICATIONS BY CONTRACTORS |
| AUTHORIZED. |
| |
| 2) PLANS ARE SILENT TO WHAT TYPE OF BACKING BOARD WILL |
| BE USED AROUND THE TUB SURROUND. PLEASE SHOW COMPLIANCE |
| WITH: |
| 2014 FBC-B 2509.2 BASE FOR TILE. GLASS MAT |
| WATER-RESISTANT GYPSUM BACKING PANELS, DISCRETE |
| NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE SHEETS OR |
| NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS BACKER |
| UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR C 1325 |
| AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| |
| 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING |
| BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS: |
| 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| COMPARTMENTS. |
| 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN |
| AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES |
| (305 MM) O.C. FOR 1/2-INCH THICK (12.7 MM) |
| WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16 |
| INCHES (406 MM) O.C. FOR 5/8-INCH THICK (15.9 MM) |
| WATER-RESISTANT GYPSUM BACKING BOARD. |
| |
| 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |