Plan Review Details - Permit 16081192
Plan Review Stops For Permit 16081192
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-14 Cont ID  
Sent By skennedy Date 2016-09-14 Time 14:02 Rev Time 0.00
Received By skennedy Date 2016-09-14 Time 14:02 Sent To  
Notes
2016-09-14 13:57:10BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16081192
 ADD: 1200 S. FLAGLER DR. SUITE # 1503
 CONT: CAMBRIDGE
 TEL: 561-784-3722
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 09/14/2016
 ACTION: APPROVED AS NOTED HEREIN.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.4.3 CERTIFICATIONS BY CONTRACTORS
 AUTHORIZED.
  
 PLANS ARE NOT CLEAR AS TO WHAT TYPE OF BACKING BOARD
 WILL BE USED AROUND THE TUB SURROUND. PLEASE
 DEMONSTRATE TO THE INSPECTOR COMPLIANCE WITH:
 2014 FBC-B 2509.2 BASE FOR TILE. GLASS MAT
 WATER-RESISTANT GYPSUM BACKING PANELS, DISCRETE
 NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE SHEETS OR
 NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS BACKER
 UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR C 1325
 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING
 BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS:
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-02 Cont ID  
Sent By jwitmer Date 2016-09-02 Time 06:01 Rev Time 0.00
Received By jwitmer Date 2016-09-02 Time 05:31 Sent To  
Notes
2016-09-02 06:05:17BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16081192
 ADD: 1200 S. FLAGLER DR. SUITE # 1503
 CONT: CAMBRIDGE
 TEL: 561-784-3722
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. SEPT. 02/2016
 ACTION: DENIED
  
 1) THE CONTRACTOR HAS NOT TAKEN OWNERSHIP OF THE PLANS
 SUBMITTED. PLEASE NOTE THE CONTRACTOR CAN ONLY DRAW THE
 PLANS THEY HAVE A LICENSE FOR. THE QUALIFIER FOR
 CAMBRIDGE CONSTRUCTION MUST TAKE OWNERSHIP OF THE FLOOR
 PLAN BY PRINTING HIS OR HER NAME, SIGNING THE PLAN WITH
 THEIR SIGNATURE AND LICENSE NUMBER.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.4.3 CERTIFICATIONS BY CONTRACTORS
 AUTHORIZED.
  
 2) PLANS ARE SILENT TO WHAT TYPE OF BACKING BOARD WILL
 BE USED AROUND THE TUB SURROUND. PLEASE SHOW COMPLIANCE
 WITH:
 2014 FBC-B 2509.2 BASE FOR TILE. GLASS MAT
 WATER-RESISTANT GYPSUM BACKING PANELS, DISCRETE
 NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE SHEETS OR
 NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS BACKER
 UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR C 1325
 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING
 BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS:
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-09-12 Cont ID  
Sent By skennedy Date 2016-09-12 Time 09:18 Rev Time 0.00
Received By skennedy Date 2016-09-12 Time 09:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-12 Cont ID  
Sent By skennedy Date 2016-09-12 Time 09:19 Rev Time 0.00
Received By skennedy Date 2016-08-29 Time 13:24 Sent To  
Notes
2016-08-30 13:24:09B19

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-09-12 Cont ID  
Sent By skennedy Date 2016-09-12 Time 09:18 Rev Time 0.00
Received By skennedy Date 2016-09-12 Time 09:18 Sent To  
Notes
***NONE***