Plan Review Details - Permit 16081182
Plan Review Stops For Permit 16081182
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-06 Cont ID  
Sent By hmoser Date 2016-09-06 Time 11:02 Rev Time 0.00
Received By hmoser Date 2016-09-01 Time 13:07 Sent To  
Notes
2016-09-01 13:07:14RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-31 Cont ID  
Sent By hmoser Date 2016-08-31 Time 13:48 Rev Time 0.00
Received By hmoser Date 2016-08-29 Time 09:38 Sent To  
Notes
2016-08-30 09:38:25ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-09-06 Cont ID  
Sent By hmoser Date 2016-09-06 Time 11:01 Rev Time 0.00
Received By hmoser Date 2016-09-06 Time 11:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-31 Cont ID  
Sent By hmoser Date 2016-08-31 Time 13:47 Rev Time 0.00
Received By hmoser Date 2016-08-31 Time 13:09 Sent To  
Notes
2016-08-31 13:47:52PLAN DENIED
 1) PROVIDE CFM ON ALL SUPPLY AIR GRILLS.
 PER SECTION 107 FBC
 2) REFER TO SECTION M1602.4 BALANCED RETURN AIR.
 2014 RESIDENTIAL CODE.
 3) PROVIDE A CONDENSER TIE DOWN DETAIL FROM A ENGINEER
 OR THE EQUIPMENT MANUFACTURE . PER SECTION
 M1305.1.4.1 GROUND CLEARANCE AND M1401.4
 EXTERIOR INSTALLATION 2014 RESIDENTIAL CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  