Plan Review Details - Permit 16081062
Plan Review Stops For Permit 16081062
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-08 Cont ID  
Sent By mvaldes Date 2016-09-08 Time 08:56 Rev Time 0.00
Received By mvaldes Date 2016-09-08 Time 08:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-31 Cont ID  
Sent By mvaldes Date 2016-08-31 Time 16:01 Rev Time 0.00
Received By mvaldes Date 2016-08-31 Time 15:16 Sent To  
Notes
2016-08-31 16:04:58REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1] CLARIFY IF THE GENERATOR IS EQUIPPED WITH AN
 INTERGAL DISCONNECT OR IS IT WITHIN SIGHT. NEC 445.18
  
 2] PROVIDE MANUFACTURE SPECS OF THE TRANSFER-SWITCH TO
 VERIFY IF ITS A SEPERATELY OR NON-SEPERATELY DERIVED
 SYSTEM. FBC 107

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-08 Cont ID  
Sent By mvaldes Date 2016-09-08 Time 08:56 Rev Time 0.00
Received By mvaldes Date 2016-09-06 Time 08:47 Sent To  
Notes
2016-09-06 08:48:10MVALDES'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-31 Cont ID  
Sent By mvaldes Date 2016-08-31 Time 16:05 Rev Time 0.00
Received By mvaldes Date 2016-08-25 Time 11:43 Sent To  
Notes
2016-08-25 11:43:56ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2016-08-29 Cont ID  
Sent By njwira Date 2016-08-29 Time 16:31 Rev Time 0.00
Received By njwira Date 2016-08-25 Time 13:48 Sent To E
Notes
***NONE***