Plan Review Details - Permit 16081034
Plan Review Stops For Permit 16081034
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-12-09 Cont ID  
Sent By jwitmer Date 2016-12-09 Time 16:49 Rev Time 0.00
Received By jwitmer Date 2016-12-09 Time 16:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-11-07 Cont ID  
Sent By jwitmer Date 2016-11-07 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2016-11-05 Time 11:00 Sent To  
Notes
2016-11-07 08:25:48BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16081034
 ADD: 2580 METROCENTRE BLVD. SUITE 3, 4 & 5
 CONT: ANDERSON MOORE CONSTRUCTION
 TEL: 753-7400
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. NOV. 07/2016
 ACTION: DENIED
  
 1)COMPLIED. ADDITIONAL DIRECTIONAL EXITS SIGNS RED
 LINED ON THE PLANS.
  
 2)COMPLIED.
  
 3) SHEET A-1 SHOWS THE TENANT SPACE IS APPROXIMATELY
 8,500 SQUARE FEET IN AREA AND APPEARS TO BE A MIXED USE
 OCCUPANCY BETWEEN A BUSINESS AND A2 (BREAK ROOM)/A3
 ASSEMBLY (WAITING ROOM & CONFERENCE ROOM) OCCUPANCY OF
 APPROXIMATELY 1,150 SQ. FT. WHICH IS OVER 10 % OF THE
 TENANT FLOOR AREA. THE DESIGNER OF RECORD WILL NEED TO
 IDENTIFY HOW THE MIXED USE OCCUPANCY IS GOING TO BE
 CLASSIFIED? AS SEPARATED UNDER 508.3.3 OR NONSEPARATED
 OCCUPANCIES UNDER 508.3.
 PLEASE ALSO NOTE FOR BOTH THE FLOOR PLAN AND REFLECTED
 CEILING PLANS BOTH PLANS ARE DRAWN IN 1/8 INCH SCALE
 WHEREAS THE PLANS ARE LABELED 1/4 INCH SCALE.
 DISCREPANCY IN PLANS. 107.2.1.3.
  
 4-6) COMPLIED.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-12 Cont ID  
Sent By jwitmer Date 2016-09-12 Time 14:35 Rev Time 0.00
Received By jwitmer Date 2016-09-12 Time 12:59 Sent To  
Notes
2016-09-12 14:35:38BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16081034
 ADD: 2580 METROCENTRE BLVD. SUITE 3, 4 & 5
 CONT: ANDERSON MOORE CONSTRUCTION
 TEL: 753-7400
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 1) WITHIN THE SET OF PLANS THERE IS NO PLAN WITH
 PROJECT INFORMATION, CODE ANALYSIS AND LIFE SAFETY
 PLAN.
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1:
  
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS/ 107.3.5.1.1 BUILDING:
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503). PROVIDE SQUARE FOOTAGE OF BUILDING.
 FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE
 THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 FIRE SUPPRESSION SYSTEMS REQUIRED? YES OR NO, THEY
 SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS/ PRE-ENGINEERED SYSTEMS
 LIFE SAFETY PLAN SHALL INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE ACCESS CODE
 SIGNS SHALL BE PROVIDED IN ACCORDANCE WITH 216 AND
 SHALL COMPLY WITH 703.
  
 2) SINCE THERE IS NO CODE INFORMATION PROVIDED NO LIFE
 SAFETY PLAN FOR WHICH WAY THE OCCUPANTS WILL BE
 TRAVELING TO REACH AN EXIT NOR THE QUANTITY OF
 OCCUPANTS EACH CORRIDOR WILL BE HANDLING COMPLIANCE
 CANNOT BE DETERMINED FOR 2014 FBC-B TABLE 1018.1
 BUSINESS CORRIDORS WITH AN OCCUPANT LOAD GREATER THAN
 30 IN A NON-SPRINKLERED BUILDING WOULD REQUIRE 1 HOUR
 FIRE RATED CORRIDORS AND OPENING PROTECTIVES IN
 ACCORDANCE WITH FBC-B TABLE 716.5.
 3) SHEET A-1 SHOWS THE TENANT SPACE IS APPROXIMATELY
 8,500 SQUARE FEET IN AREA AND APPEARS TO BE A MIXED USE
 OCCUPANCY BETWEEN A BUSINESS AND A2/A3 ASSEMBLY
 OCCUPANCY OF APPROXIMATELY 1,150 SQ. FT. WHICH IS OVER
 10 % OF THE TENANT FLOOR AREA. THE DESIGNER OF RECORD
 WILL NEED TO IDENTIFY HOW THE MIXED USE OCCUPANCY IS
 GOING TO BE CLASSIFIED? AS SEPARATED UNDER 508.3.3 OR
 NONSEPARATED OCCUPANCIES UNDER 508.3.
  
 4) THERE ARE NO SECTIONS FOUND ON SHEET A1 FOR AN
 ACCESSIBLE FRONT OFFICE CHECK IN NOR ANY FOR CHECKING
 OUT. FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. 904.3.3 CHECK WRITING SURFACES.
 WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY
 WITH 902.3.
  
 5A) SHEET A1 THE STAFF SHOWER IN THE BATHROOM 118
 MEASURES 38 X38 INCHES. PLEASE PROVIDE COMPLIANCE WITH
 THE ACCESS. CODE FOR THE REQUIRED SIZE 36 X 36 INCHES
 SEE 608.2.
  
 5B) THE PLAN DOES NOT SHOW THE CONTROL VALVE WALL NOR
 THE SEAT WALL NOR REQUIRED CLEARANCES. SEE ACCESS. CODE
 608.2.1 AND FIGURE 608.2.1. PLEASE ALSO PROVIDE
 COMPLIANCE FOR GRAB BAR PLACEMENT SEE SECTION 608.3 AND
 FIGURE 608.3.1 AND CONTROLS FIGURE 608.5.1.
  
 6) SHEET A1 WILL ALSO NEED TO SHOW COMPLIANCE FOR THE A
 SHOWER IN THE BATHROOM 113 FOR A STANDARD ROLL IN
 SHOWER IN COMPLIANCE WITH 608.3.2, & 608.6.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-12-06 Cont ID  
Sent By rlecky Date 2016-12-06 Time 12:24 Rev Time 0.00
Received By rlecky Date 2016-12-06 Time 11:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-11-02 Cont ID  
Sent By vperez Date 2016-11-02 Time 17:52 Rev Time 0.00
Received By vperez Date 2016-11-02 Time 17:52 Sent To  
Notes
2016-11-02 17:48:352ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 PREVIOUS COMMENT NOT ADDRESSED:
  
 8. PER NEC 220.87 PROVIDE 1 YEAR MAXIMUM DEMAND DATA
 REPORT TO VERIFY IF EXISTING SERVICE IS SUFFICIENT TO
 CARRY NEW SERVICE ADDED.
 COMMENTS:
  
 1. LABEL ALL MAINS 1OF5, 2OF5 ETC. NEC 230.71
 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 3. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
2016-08-30 14:00:56ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: OLAOLU REAL ESTATE
 JOB ADDRESS: 2580 METRO CENTRE BLVD.
 DESCRIPTION: INTERIOR RENOVATION
 MASTER PERMIT: 16081034
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. NEC 600.5 STATES THAT EACH COMMERCIAL BUILDING AND
 EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED
 OUTLET IN AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO
 EACH TENANT SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE
 HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED
 ACCESSIBLE TO PEDESTRIANS. I DO NOT SEE THIS ON ANY OF
 THE DOORS ON EITHER THE POWER OR LIGHTING PLAN.
 2. NEC 210.62 CALLS FOR AT LEAST ONE RECEPTACLE OUTLET
 TO BE INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW
 FOR EVERY 12 LINEAR FT. OR MAJOR PORTION THEREOF AREA
 MEASURED HORIZONTALLY. THIS APPLIES TO THE STORE FRONT
 AREAS OF THIS BLDG.
 3. ROOMS 136, 142, 145, 150, 158, 159, 160 & 161 SHALL
 COMPLY WITH NEC 517 PART III.
 4. AUTOMATIC CONTROL FOR RECEPTACLES AS INDICATED IN
 FBC-E 405.7.1 IS REQUIRED.
 5. DISCONNECTS CONFORMING WITH NEC 440.12 IS REQUIRED
 FOR THE CONDENSING UNITS.
 6. NEC 314.27(D): BOXES USED FOR THE SOLE SUPPORT OF
 CEILING FANS SHALL BE MARKED BY THE MANUFACTURER AS
 SUITABLE FOR THE PURPOSE, AND INDICATE THE WEIGHT
 LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT PADDLE
 FANS HEAVIER THAN 70 LBS.
 7. EMERGENCY LIGHTING IS REQUIRED FOR THE ROOMS
 MENTIONED ABOVE IN COMMENT #3.
 8. PROVIDE MAXIMUM DEMAND DATA FOR 1 YEAR AS REQUIRED
 BY NEC 220.87 TO DETERMINE THAT THE EXISTING SERVICE IS
 CAPABLE OF ABSORBING THE ADDED DEMAND.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY
 .
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-30 Cont ID  
Sent By albarran Date 2016-08-30 Time 14:00 Rev Time 0.00
Received By albarran Date 2016-08-29 Time 19:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-11-28 Cont ID  
Sent By pleduc Date 2016-11-28 Time   Rev Time 0.00
Received By pleduc Date 2016-11-28 Time 11:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-10-31 Cont ID  
Sent By pleduc Date 2016-10-31 Time   Rev Time 0.00
Received By pleduc Date 2016-10-31 Time 15:16 Sent To  
Notes
2016-10-31 16:11:43THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF
 THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE
 INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND
 ALL OTHER APPLICABLE CODES OR STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-09-01 Cont ID  
Sent By pleduc Date 2016-09-01 Time   Rev Time 0.00
Received By pleduc Date 2016-09-01 Time 13:14 Sent To  
Notes
2016-09-01 14:11:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO INDICATION OF COMPLIANCE WITH A FIRE
 CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 PLEASE REVIEW, ENSURE COMPLAINCE AND PROVIDE THE
 APPLICABLE NOTE.
  
  
 2) THERE IS NO INDICATION OF THE PROPOSED OCCUPANCY
 CLASSIFICATION.
  
 NFPA 1
  
 CHAPTER 6 CLASSIFICATION OF OCCUPANCY
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR
 STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2
 THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AHJ WHERE THERE IS A
 QUESTION OF PROPER CLASSIFICATION IN ANY INDIVIDUAL
 CASE. [101:6.1.1.1]
  
 PLEASE PROVIDE DETAILS AS TO THE NATURE OF THE PROJECT
 BUSINESS AND THE OCCUPANCY CLASSIFICATION.
  
  
 3) PLEASE PROVIDED A COMPLETE LIFE SAFETY PLAN THAT
 ILLUSTRATES OCCUPANT LOADS, TRAVEL DISTANCES, COMMON
 PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS,
 EMERGENCY LIGHTING, SITE PLAN ENSURING EXITS LEAD TO A
 PUBLIC WAY, AND FIRE EXTINGUISHER LOCATIONS. ALL IN
 ACCORDANCE WITH THE REQUIRERMENTS OF THE FLORIDA FIRE
 PREVENTION CODE, 5TH EDITION.
  
  
 4) THERE IS NO INDICATION OF ANY EXSITING OR PROPOSED
 LIFE SAFETY SYSTEMS, I.E. FIRE ALARM AND FIRE
 SPRINKLER.
  
 PLEASE PROVIDE NOTE OF EITHER IS EXISITNG.
  
 IF NEW SYSTEMS ARE PROPOSED PLEASE INCLUDE 61G REQUIRED
 INFO OR DRAWINGS.
  
  
 5) PLEASE PROVIDE PLAN SHEET REVISION CLOUDS OR
 NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-12-14 Cont ID  
Sent By gjohnson Date 2016-12-14 Time 11:37 Rev Time 0.00
Received By gjohnson Date 2016-11-22 Time 08:07 Sent To  
Notes
2016-11-23 08:08:11C22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-08 Cont ID  
Sent By gjohnson Date 2016-11-08 Time 10:45 Rev Time 0.00
Received By gjohnson Date 2016-10-27 Time 13:52 Sent To  
Notes
2016-10-28 13:52:55C05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-23 Cont ID  
Sent By gjohnson Date 2016-09-23 Time 12:15 Rev Time 0.00
Received By gjohnson Date 2016-08-24 Time 11:11 Sent To  
Notes
2016-08-25 11:11:46C05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-09-12 Cont ID  
Sent By jwitmer Date 2016-09-12 Time 14:35 Rev Time 0.00
Received By jwitmer Date 2016-09-12 Time 12:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-12-02 Cont ID  
Sent By ccole Date 2016-12-02 Time 07:54 Rev Time 0.00
Received By ccole Date 2016-12-02 Time 07:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-11-03 Cont ID  
Sent By ccole Date 2016-11-03 Time 10:30 Rev Time 0.00
Received By ccole Date 2016-11-03 Time 08:26 Sent To  
Notes
2016-11-03 10:45:422ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16081034
 11/3/16
  
 1) THE O/A INTAKES MUST MEET THE PROVISIONS FOR
 EXTERIOR WALL OPENING PROTECTIVES IN ACCORDANCE WITH
 FBC-14 BUILDING- SEE SECTION 401.5 FBC-14 MECHANICAL
 AND 1609 FBC-14 BUILDING. IF USING LOUVERS, PROVIDE A
 FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA, AND PROVIDE
 DOUMENTATION OF COMPLIANCE WITH AMCA 550.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-30 Cont ID  
Sent By ccole Date 2016-08-30 Time 16:09 Rev Time 0.00
Received By ccole Date 2016-08-30 Time 16:09 Sent To  
Notes
2016-08-30 16:38:321ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16081034
 8/30/16
  
 1) THE SELECTED AC SYSTEMS ARE OVERSIZED IN COOLING AND
 HEATING CAPACITIES PER THE SUBMITTED WHOLE AREA
 CALCULATION- REFER TO SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION.
  
 2) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF AHU'S #1-6 PER SECTION 606.2.1. THIS
 REQUIREMENT MAY BE WAIVED IF MANUFACTURER'S
 SPECIFICATIONS INDICATE THE UNITS DO NOT HAVE THE
 CAPACITY TO PRODUCE OVER 2000 CFMS EACH.
  
 3) EXHAUST VENTILATION IS REQUIRED FOR THE LAB AND
 RECIRCULATION OF THE AIR IS PROHIBITED EXCEPT WHERE THE
 RESULTING AIR STREAM CONSISTS OF NOT MORE THAN 10% AIR
 RECIRCULATED FROM THE SPACE- SEE TABLE 403.3 AND
 FOOTNOTE G.
  
 4 ) REFER TO TABLE 403.3 AND PROVIDE COMPLETE
 VENTILATION CALCULATIONS FOR THE PROPOSED OCCUPANCY
 INCLUDING THE EXAM ROOMS, THE INFUSION ROOM, THE LAB,
 THE PHARMACY, THE STORAGE ROOMS, AND CORRIDORS.
  
 5) PROVIDE CONDENSATE DISPOSAL DETAILS FOR AHU #5.
  
 6) PROVIDE EQUIPMENT SCHEDULES FOR THE MOTORIZED
 DAMPERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-12-14 Cont ID  
Sent By gjohnson Date 2016-12-14 Time 11:36 Rev Time 0.00
Received By gjohnson Date 2016-12-14 Time 11:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-11-08 Cont ID  
Sent By gjohnson Date 2016-11-08 Time 10:42 Rev Time 0.00
Received By gjohnson Date 2016-11-08 Time 10:26 Sent To  
Notes
2016-11-08 10:45:032ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 2ND REQUEST
 HAVE NOT COMPLIED
  
 1.SHOW ACCESSIBILITY COMPLIANCE FOR SHOWERS TO COMPLY
 WITH FBC ACC
 608.3 GRAB BARS.
 GRAB BARS SHALL COMPLY WITH 609 AND SHALL BE PROVIDED
 IN ACCORDANCE WITH 608.3. WHERE MULTIPLE GRAB BARS ARE
 USED, REQUIRED HORIZONTAL GRAB BARS SHALL BE INSTALLED
 AT THE SAME HEIGHT ABOVE THE FINISH FLOOR.
 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES (455 MM) FROM THE CONTROL WALL.
 608.3.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 WHERE A SEAT IS PROVIDED IN STANDARD ROLL-IN TYPE
 SHOWER COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THE
 BACK WALL AND THE SIDE WALL OPPOSITE THE SEAT. GRAB
 BARS SHALL NOT BE PROVIDED ABOVE THE SEAT. WHERE A SEAT
 IS NOT PROVIDED IN STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THREE
 WALLS. GRAB BARS SHALL BE INSTALLED 6 INCHES (150 MM)
 MAXIMUM FROM ADJACENT WALLS.
 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
 608.4 SEATS.
 A FOLDING OR NON-FOLDING SEAT SHALL BE PROVIDED IN
 TRANSFER TYPE SHOWER COMPARTMENTS. A FOLDING SEAT SHALL
 BE PROVIDED IN ROLL-IN TYPE SHOWERS REQUIRED IN
 TRANSIENT LODGING GUEST ROOMS WITH MOBILITY FEATURES
 COMPLYING WITH 806.2. SEATS SHALL COMPLY WITH 610.
 610.3 SHOWER COMPARTMENT SEATS.
 WHERE A SEAT IS PROVIDED IN A STANDARD ROLL-IN SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE SIDE WALL ADJACENT TO THE CONTROLS,
 AND SHALL EXTEND FROM THE BACK WALL TO A POINT WITHIN 3
 INCHES (75 MM) OF THE COMPARTMENT ENTRY. WHERE A SEAT
 IS PROVIDED IN AN ALTERNATE ROLL-IN TYPE SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE FRONT WALL OPPOSITE THE BACK WALL, AND
 SHALL EXTEND FROM THE ADJACENT SIDE WALL TO A POINT
 WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. IN
 TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM THE
 BACK WALL TO A POINT WITHIN 3 INCHES (75 MM) OF THE
 COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL COMPLY
 WITH 610.3.1 OR 610.3.2.
 610.3.1 RECTANGULAR SEATS.
 THE REAR EDGE OF A RECTANGULAR SEAT SHALL BE 2 1/2
 INCHES (64 MM) MAXIMUM AND THE FRONT EDGE 15 INCHES
 (380 MM) MINIMUM AND 16 INCHES (405 MM) MAXIMUM FROM
 THE SEAT WALL. THE SIDE EDGE OF THE SEAT SHALL BE 11/2
 INCHES (38 MM) MAXIMUM FROM THE ADJACENT WALL.
 610.3.2 L-SHAPED SEATS.
 THE REAR EDGE OF AN L-SHAPED SEAT SHALL BE 2 1/2 INCHES
 (64 MM) MAXIMUM AND THE FRONT EDGE 15 INCHES (380 MM)
 MINIMUM AND 16 INCHES (405 MM) MAXIMUM FROM THE SEAT
 WALL. THE REAR EDGE OF THE ?L? PORTION OF THE SEAT
 SHALL BE 11/2 INCHES (38 MM) MAXIMUM FROM THE WALL AND
 THE FRONT EDGE SHALL BE 14 INCHES (355 MM) MINIMUM AND
 15 INCHES (380 MM) MAXIMUM FROM THE WALL. THE END OF
 THE ?L? SHALL BE 22 INCHES (560 MM) MINIMUM AND 23
 INCHES MAXIMUM (585 MM) FROM THE MAIN SEAT WALL.
  
 2. SHOW CLEAR FLOOR SPACE FOR SHOWERS . PER FBC ACC .
 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES
 (915 MM) BY 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS
 MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND
 SHALL HAVE A 36 INCH (915 MM) WIDE MINIMUM ENTRY ON THE
 FACE OF THE SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES
 (915 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG
 MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE
 PROVIDED.
 608.2.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 30
 INCHES (760 MM) WIDE MINIMUM BY 60 INCHES (1525 MM)
 DEEP MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER
 POINTS OF OPPOSING SIDES AND SHALL HAVE A 60 INCHES
 (1525 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT.
  
 3. SHOWER IN STAFF TOILET RM 118 SHALL BE 36" X 36" PER
 FBC ACC 608.2.1
  
 4. SHOW ACCESSIBILITY COMPLIANCE FOR WATER FOUNTAIN FBC
 ACC
 602.2 CLEAR FLOOR SPACE.
 UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 602.4 SPOUT HEIGHT.
 SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-09-23 Cont ID  
Sent By gjohnson Date 2016-09-23 Time 10:18 Rev Time 0.00
Received By gjohnson Date 2016-09-23 Time 10:18 Sent To  
Notes
2016-09-23 12:15:061ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.SHOW ACCESSIBILITY COMPLIANCE FOR SHOWERS TO COMPLY
 WITH FBC ACC
 608.3 GRAB BARS.
 GRAB BARS SHALL COMPLY WITH 609 AND SHALL BE PROVIDED
 IN ACCORDANCE WITH 608.3. WHERE MULTIPLE GRAB BARS ARE
 USED, REQUIRED HORIZONTAL GRAB BARS SHALL BE INSTALLED
 AT THE SAME HEIGHT ABOVE THE FINISH FLOOR.
 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES (455 MM) FROM THE CONTROL WALL.
 608.3.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 WHERE A SEAT IS PROVIDED IN STANDARD ROLL-IN TYPE
 SHOWER COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THE
 BACK WALL AND THE SIDE WALL OPPOSITE THE SEAT. GRAB
 BARS SHALL NOT BE PROVIDED ABOVE THE SEAT. WHERE A SEAT
 IS NOT PROVIDED IN STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THREE
 WALLS. GRAB BARS SHALL BE INSTALLED 6 INCHES (150 MM)
 MAXIMUM FROM ADJACENT WALLS.
 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
 608.4 SEATS.
 A FOLDING OR NON-FOLDING SEAT SHALL BE PROVIDED IN
 TRANSFER TYPE SHOWER COMPARTMENTS. A FOLDING SEAT SHALL
 BE PROVIDED IN ROLL-IN TYPE SHOWERS REQUIRED IN
 TRANSIENT LODGING GUEST ROOMS WITH MOBILITY FEATURES
 COMPLYING WITH 806.2. SEATS SHALL COMPLY WITH 610.
 610.3 SHOWER COMPARTMENT SEATS.
 WHERE A SEAT IS PROVIDED IN A STANDARD ROLL-IN SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE SIDE WALL ADJACENT TO THE CONTROLS,
 AND SHALL EXTEND FROM THE BACK WALL TO A POINT WITHIN 3
 INCHES (75 MM) OF THE COMPARTMENT ENTRY. WHERE A SEAT
 IS PROVIDED IN AN ALTERNATE ROLL-IN TYPE SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE FRONT WALL OPPOSITE THE BACK WALL, AND
 SHALL EXTEND FROM THE ADJACENT SIDE WALL TO A POINT
 WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. IN
 TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM THE
 BACK WALL TO A POINT WITHIN 3 INCHES (75 MM) OF THE
 COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL COMPLY
 WITH 610.3.1 OR 610.3.2.
 610.3.1 RECTANGULAR SEATS.
 THE REAR EDGE OF A RECTANGULAR SEAT SHALL BE 2 1/2
 INCHES (64 MM) MAXIMUM AND THE FRONT EDGE 15 INCHES
 (380 MM) MINIMUM AND 16 INCHES (405 MM) MAXIMUM FROM
 THE SEAT WALL. THE SIDE EDGE OF THE SEAT SHALL BE 11/2
 INCHES (38 MM) MAXIMUM FROM THE ADJACENT WALL.
 610.3.2 L-SHAPED SEATS.
 THE REAR EDGE OF AN L-SHAPED SEAT SHALL BE 2 1/2 INCHES
 (64 MM) MAXIMUM AND THE FRONT EDGE 15 INCHES (380 MM)
 MINIMUM AND 16 INCHES (405 MM) MAXIMUM FROM THE SEAT
 WALL. THE REAR EDGE OF THE ?L? PORTION OF THE SEAT
 SHALL BE 11/2 INCHES (38 MM) MAXIMUM FROM THE WALL AND
 THE FRONT EDGE SHALL BE 14 INCHES (355 MM) MINIMUM AND
 15 INCHES (380 MM) MAXIMUM FROM THE WALL. THE END OF
 THE ?L? SHALL BE 22 INCHES (560 MM) MINIMUM AND 23
 INCHES MAXIMUM (585 MM) FROM THE MAIN SEAT WALL.
  
 2. SHOW CLEAR FLOOR SPACE FOR SHOWERS . PER FBC ACC .
 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES
 (915 MM) BY 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS
 MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND
 SHALL HAVE A 36 INCH (915 MM) WIDE MINIMUM ENTRY ON THE
 FACE OF THE SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES
 (915 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG
 MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE
 PROVIDED.
 608.2.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 30
 INCHES (760 MM) WIDE MINIMUM BY 60 INCHES (1525 MM)
 DEEP MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER
 POINTS OF OPPOSING SIDES AND SHALL HAVE A 60 INCHES
 (1525 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT.
  
 3. SHOWER IN STAFF TOILET RM 118 SHALL BE 36" X 36" PER
 FBC ACC 608.2.1
  
 4. SHOW ACCESSIBILITY COMPLIANCE FOR WATER FOUNTAIN FBC
 ACC
 602.2 CLEAR FLOOR SPACE.
 UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 602.4 SPOUT HEIGHT.
 SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 5.. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1
  
 6. ALL PUBLIC LAVATORY'S SHALL HAVE TEMPERED WATER
 SHALL BE DELIVERED BY A TEMPERATURE LIMITING DEVICE.
 PER FBC PL
 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 607.1.1 TEMPERATURE LIMITING MEANS.
 A THERMOSTAT CONTROL FOR A WATER HEATER SHALL NOT SERVE
 AS THE TEMPERATURE LIMITING MEANS FOR THE PURPOSES OF
 COMPLYING WITH THE REQUIREMENTS OF THIS CODE FOR
 MAXIMUM ALLOWABLE HOT OR TEMPERED WATER DELIVERY
 TEMPERATURE AT FIXTURES.
  
 7. SHT. P-5 DETAIL FOR WATER HEATER SHOWS PAN DRAIN
 INTO A MOP SINK ONLY THERE'S NO MOP SINK. THIS SIZE
 HEATER WOULD HAVE TO BE ON A PLATFORM IN ORDER TO DRAIN
 INTO ANY KIND OF MOP SINK OR FLOOR SINK . PLEASE
 CLARIFY SHALL COMPLY WITH
 FBC PL 504.7.2 PAN DRAIN TERMINATION.
 THE PAN DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE OVER
 A SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR FLOOR
 DRAIN OR EXTEND TO THE EXTERIOR OF THE BUILDING AND
 TERMINATE NOT LESS THAN 6 INCHES (152 MM) AND NOT MORE
 THAN 24 INCHES (610 MM) ABOVE THE ADJACENT GROUND
 SURFACE.
  
 8. SHT. P-3 THE 3" SANITARY PIPE CONNECTING THE STAFF
 TOILET ROOM 118 AND THE 2 SINKS SHALL CONNECT DOWN
 STREAM OF THE ADA TOILET ROOM 113. PER FBC 912.1
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy