Plan Review Stops For Permit 16081029 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2016-08-31 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-08-31 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-08-31 |
Time |
09:54 |
Sent To |
|
|
Notes |
2016-08-31 11:15:52 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | - PASSED WITH THE FOLLOWING PROVISO'S | | | | 1] ALL MAINS MUST BE GROUPED IN ACCORDANCE WITH NEC | | 230.72 | | | | 2] PROVIDE AN INTERSYSTEM BONDING TERMINAL PER NEC | | 250.94 |
|
|