Plan Review Details - Permit 16080978
Plan Review Stops For Permit 16080978
Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-08-25 Cont ID  
Sent By tklarge Date 2016-08-25 Time 06:45 Rev Time 0.00
Received By tklarge Date 2016-08-25 Time 06:18 Sent To  
Notes
2016-08-25 06:45:48 
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 DRYER, TANKLESS WATER HEATERS, STOVE AND FIREPLACE PER
 THE 2014 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES.
 SEC. G 2407.
 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 4) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE
 WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS.
 5) SUBMIT COPIES OF THE SIZING TABLES BEING USED TO
 DESIGN THE SYSTEM OR REFERENCE THE SPECIFIC TABLES ON
 THE PLANS. A REVIEW COULD NOT BE DONE ON THE PIPNG
 SYSTEM DUE TO THE LACK OF THIS INFORMATION.
 6) SHOW THE MEASUREMENT (LENGTH) OF THE PIPING FROM THE
 SECOND STAGE REGULATOR TO THE APPLIANCE.2014 FGC SEC.
 402.4.1.
 7) SUBMIT MANUF. SPECIFICATIONS FOR THE SECOND STAGE
 REGULATORS. HOW WILL THEY BE VENTED?
 8) SUPPLY THE CORRESPONDING EHD FOR EACH SIZE THE
 WARDFLEX PIPE.FBC SEC. 107.2.1.
 9) THE FUTURE OUTLET FOR THE FIREPLACE SHALL BE VALVED
 AND CAPPED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-25 Cont ID  
Sent By tklarge Date 2016-08-25 Time 06:46 Rev Time 0.00
Received By tklarge Date 2016-08-23 Time 14:29 Sent To  
Notes
2016-08-23 14:29:29ROUTED TO PLUMBING INBOX