Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-01-10 Cont ID  
Sent By pvalenti Date 2022-01-10 Time 14:17 Rev Time 0.00
Received By pvalenti Date 2022-01-10 Time 12:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-11-09 Cont ID  
Sent By jwitmer Date 2021-11-09 Time 16:25 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-11-09 16:23:52BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080972-2014 FBC-BUILDING
 ADD: 2001 S. DIXIE HWY.
 CONT: BELACRIS CONSTRUCTION LLC
 TEL: 305-244-0277
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: WED. JUNE 23RD/2021
 ACTION: DENIED
  
  
 1-6) COMPLIED.
  
 7A) SEMI-COMPLIED. THANK YOU FOR WORKING ON THE SITE
 SPECIFIC/ LOCAL PRODUCT APPROVAL FORMS. I SPOKE WITH
 OUR ASSISTANT B. O. RICHARD GATHRIGHT ABOUT YOUR
 PROJECT AND PAPERWORK SUBMITTED. WE BOTH AGREED YOU
 SHOULD CIRCLE ON THE APPLICATION SITE SPECIFIC
 APPROVAL. SITE SPECIFIC APPROVALS ARE FOR CUSTOM MADE
 DOORS AND WINDOWS, ONE OF A KIND PRODUCTS NOT TO BE
 MASS PRODUCED. THIS WILL ALSO NEGATE THE THIRD-PARTY
 QUALITY ASSURANCE PROGRAM THAT WOULD BE REQUIRED BY
 EITHER A LOCAL OR STATE APPROVAL.
 THE OVERHEAD DOORS WITH GLAZING UNITS WILL ALSO NEED TO
 SATISFY THE CODE REQUIREMENT 2405.2.1 SLOPED GLAZING.
 MONO GLAZING SYSTEMS, LAMINATED GLASS MIN. 0.30 MIL.
 (0.76MM) POLYVINYL BUTYRAL, OR WIRE GLASS, HEAT
 STRENGTHENED GLASS OR FULLY TEMPERED GLASS. THE
 COMPLETION LETTER FROM ONMJ PAGE 2 OF 21 MENTIONS THE
 FIXED WINDOW PANELS NOTE B PROVIDES AN UPDATED NOA FOR
 THE FIXED GLASS PANELS, NOA 17-1219.26 SHEET 6 OF 11
 PROVIDES THE INNER POLYVINYL BUTYRAL LAYER TO BE 0.090
 (SENTRYGLASS BY KURARY) INCHES THICK PROVIDE THIS
 MEASUREMENT IN MILS PLEASE. PLEASE IDENTIFY THE TYPE OF
 GLAZING, A ? INCH HS, B 3/16 TEMP/ 3/16 HS, OR C 3/16
 TEMP/ 3/16 HS.
 THE OTHER ISSUE IS FOR SITE SPECIFIC OR LOCAL APPROVAL
 LINE 10 DOES REQUIRE NOT ONLY THE PRINTED NAME BUT
 SIGNATURE AND DATE.
  
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL OR
 PETER VALENTI 561-805-6673. THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-23 Cont ID  
Sent By jwitmer Date 2021-06-23 Time 09:01 Rev Time 0.00
Received By jwitmer Date 2021-06-22 Time 09:15 Sent To  
Notes
2021-06-23 09:05:59BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080972-2014 FBC-BUILDING
 ADD: 2001 S. DIXIE HWY.
 CONT: MAC ENTERPRISES
 TEL: 561-236-3627
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JUNE 23RD/2021
 ACTION: DENIED
  
 1) 2ND REQUEST. THERE ARE NO DRAWINGS (FLOOR PLAN) OF
 WHERE OPENINGS 121, 122, & 123 ARE IN LOCATION TO THE
 WINDOWS AND DOORS OF THE BUILDING. A NOTE STATES SEE
 RECORD SET OF PLANS. A FLOOR PLAN NEEDS TO BE SUBMITTED
 TO HAVE A COMPLETE PACKAGE AND NOT NEED TO REFER TO
 ANOTHER PERMIT.
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. W.P.B.
 ADMINISTRATIVE CODE/2020 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 1ST ROUND OF COMMENTS. SHEET A101 THE FIRST FLOOR THE
 AREA OF WORK IS ILLUSTRATED WITH A CIRCLE AROUND THE 3
 OPENINGS THAT ARE TO BE ALTERED FROM WINDOWS TO
 OVERHEAD DOOR CONCEPT. PLEASE NOTE THE ARCHITECTURAL
 PLANS WILL NEED TO BE UPDATED TO SHOW THE NEW OPENINGS
 AS OVERHEAD DOOR OPENINGS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (1) FLOOR PLAN
  
 2-6) COMPLIED.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-01-04 Cont ID  
Sent By shill Date 2021-01-04 Time 10:27 Rev Time 0.00
Received By shill Date 2018-04-24 Time 13:42 Sent To  
Notes
2021-01-04 10:27:38PLEASE RESUBMIT DOCUMENTS VIA PROJECTDOX
  
2018-05-01 14:46:47SUBMITTAL SENT TO ROBERT BROWN PER JW REQUEST FOR
 REVIEW OF SITE SPECIFIC ENGINEERING. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-04 Cont ID  
Sent By cthroop Date 2016-11-04 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2016-11-04 Time 06:15 Sent To  
Notes
2016-11-04 07:20:46BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080972
 ADD: 2001 S. DIXIE HWY.
 CONT: MAC ENTERPRISES
 TEL: 561-236-3627
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. NOV. 04/2016
 ACTION: DENIED
  
 1) SHEET A101 THE FIRST FLOOR THE AREA OF WORK IS
 ILLUSTRATED WITH A CIRCLE AROUND THE 3 OPENINGS THAT
 ARE TO BE ALTERED FROM WINDOWS TO OVERHEAD DOOR
 CONCEPT. PLEASE NOTE THE ARCHITECTURAL PLANS WILL NEED
 TO BE UPDATED TO SHOW THE NEW OPENINGS AS OVERHEAD DOOR
 OPENINGS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (1) FLOOR PLAN
 (8) STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 DESIGN LOADS
 WIND REQUIREMENTS
 BUILDING ENVELOPE
 STRUCTURAL CALCULATIONS
  
  
 2) THE ENGINEER OF RECORD FOR THE NEW OVERHEAD DOOR
 OPENINGS WILL NEED THE ARCHITECT OF RECORD TO REVIEW
 THE PACKAGE AND APPLY THEIR SHOP DRAWING SEAL OF
 APPROVAL ON THE DOCUMENTS.
  
 3) 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 3.2. RISK CATEGORY.
  
 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
  
 4) DOCUMENTS SUBMITTED FOR A LOCAL APPROVAL FOR A
 GLAZED OVERHEAD DOOR(3) ARE MISSING DOCUMENTS FOR A
 COMPLETE CODE COMPLIANT PACKAGE.
  
 4A) THE OVERHEAD DOOR PACKAGE ADDRESSES THE FRAMEWORK,
 HYDRAULICS AND ELECTRICAL BUT DOES NOT ADDRESS THE
 REQUIREMENTS FOR 2014 FBC-B SECTION 2405 SLOPED GLAZING
 AND SKYLIGHTS
 2405.1 SCOPE.
 THIS SECTION APPLIES TO THE INSTALLATION OF GLASS AND
 OTHER TRANSPARENT, TRANSLUCENT OR OPAQUE GLAZING
 MATERIAL INSTALLED AT A SLOPE MORE THAN 15 DEGREES
 (0.26 RAD) FROM THE VERTICAL PLANE, INCLUDING GLAZING
 MATERIALS IN SKYLIGHTS, ROOFS AND SLOPED WALLS.
  
 2405.2 ALLOWABLE GLAZING MATERIALS AND LIMITATIONS.
 SLOPED GLAZING SHALL BE ANY OF THE FOLLOWING MATERIALS,
 SUBJECT TO THE LISTED LIMITATIONS. SEE 2405.2 (1-2).
  
 4B) THE OVERHEAD DOOR PACKAGE ADDRESSES THE FRAMEWORK,
 HYDRAULICS AND ELECTRICAL BUT DOES NOT ADDRESS THE
 REQUIREMENTS FOR 2014 FBC-B 1710.5.1.1 EXCEPTION (2) 2.
 DOOR ASSEMBLIES INSTALLED WHERE THE OVERHANG (OH) RATIO
 IS EQUAL TO OR MORE THAN 1 NEED NOT BE TESTED FOR WATER
 INFILTRATION. THE OVERHANG RATIO SHALL BE CALCULATED BY
 THE FOLLOWING EQUATION:
  
 OH RATIO = OH LENGTH/OH HEIGHT
  
 WHERE:
  
 OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN
 OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE.
  
 OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM
 THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A
 DOOR.
  
 4C) THE OVERHEAD DOOR PACKAGE ADDRESSES THE FRAMEWORK,
 HYDRAULICS AND ELECTRICAL BUT DOES NOT ADDRESS THE
 REQUIREMENTS FOR 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS. IN WIND-BORNE DEBRIS REGIONS, GLAZED OPENINGS
 IN BUILDINGS SHALL BE IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT-RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ANSI/DASMA 115 (FOR GARAGE
 DOORS AND ROLLING DOORS) OR TAS 201, 202 AND 203, AAMA
 506. ASTM E 1996 AND ASTM E 1886 REFERENCED HEREIN, OR
 AN APPROVED IMPACT-RESISTANT STANDARD AS FOLLOWS: (1.)
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9144 MM) OF
 GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE
 TEST OF ASTM E 1996.
  
 5) POWERLIFT- SCHOOL PROJECT BY DAVID RICE P. E. IS A
 DIGITALLY SIGNED PAPER COPY. NEEDS AND ORIGINAL SEAL
 AND SIGNATURE, YOU CAN NOT PRINT OUT A DIGITALLY SIGNED
 SIGNATURE FOR SUBMISSION TO THE BUILDING DEPARTMENT.
 NOTE THIS DOCUMENT COULD HAVE BEEN SUBMITTED
 ELECTRONICALLY WHERE WE COULD HAVE VALIDATED THE
 SIGNATURE.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 6) LOCAL PRODUCT APPROVAL TO BE REVIEWED BY ROBERT
 BROWN B. O. ONCE THE PACKAGE IS COMPLETE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
2016-08-26 09:01:49 
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-11-18 Cont ID  
Sent By jleahy Date 2021-11-18 Time 14:43 Rev Time 0.00
Received By jleahy Date 2021-11-18 Time 14:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2021-06-17 Cont ID  
Sent By jleahy Date 2021-06-17 Time 08:32 Rev Time 0.00
Received By jleahy Date 2021-06-17 Time 08:29 Sent To  
Notes
2021-06-17 08:34:06NO ELECTRIC SHOWN JLEAHY
  
 ARE DOORS ELECTRIC? IF NOT JUST PUT A NOTE ON PERMIT
 APPLICATION NOT ELECTRIC.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-23 Cont ID  
Sent By jleahy Date 2018-04-23 Time 16:54 Rev Time 0.00
Received By jleahy Date 2018-04-23 Time 16:48 Sent To B
Notes
2018-04-23 16:54:29FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
  
  
 I DO NOT SEE ANY ELECTRICAL WORK INTHESE DRAWINGS,
 PLEASE VERIFY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-04 Cont ID  
Sent By vperez Date 2016-11-04 Time 14:39 Rev Time 0.00
Received By vperez Date 2016-11-04 Time 14:39 Sent To  
Notes
2016-11-04 14:40:28PLEASE CLARIFY THE ELECTRICAL SCOPE OF WORK FOR THIS
 PROJECT.
  
 VAL PEREZ
 *6717

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-01-10 Cont ID  
Sent By lmarchan Date 2022-01-10 Time 16:16 Rev Time 0.00
Received By lmarchan Date 2022-01-06 Time 06:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-11-18 Cont ID  
Sent By jleahy Date 2021-11-18 Time 14:47 Rev Time 0.00
Received By jleahy Date 2021-11-04 Time 08:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-06-23 Time 09:01 Rev Time 0.00
Received By cdecoeur Date 2021-06-16 Time 15:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-14 Cont ID  
Sent By lmarchan Date 2020-09-14 Time 14:01 Rev Time 0.00
Received By lmarchan Date 2018-04-16 Time 14:21 Sent To  
Notes
2018-04-17 14:22:11RESUB ROUTED TO ELECTRICAL INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-04 Cont ID  
Sent By cthroop Date 2016-11-04 Time 14:40 Rev Time 0.00
Received By vperez Date 2016-11-04 Time 14:40 Sent To  
Notes
2016-08-24 11:02:02BLDG MISC 1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-01-11 Cont ID  
Sent By dbattles Date 2022-01-11 Time 15:20 Rev Time 0.00
Received By dbattles Date 2022-01-11 Time 15:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-01-10 Cont ID  
Sent By pvalenti Date 2022-01-10 Time 14:18 Rev Time 0.00
Received By pvalenti Date 2022-01-10 Time 14:18 Sent To  
Notes
2022-01-10 14:19:58PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW DENIED:
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-01-07 Cont ID  
Sent By rmcdouga Date 2022-01-07 Time 09:06 Rev Time 0.00
Received By rmcdouga Date 2022-01-07 Time 08:27 Sent To  
Notes
2022-01-07 08:33:23LETTER FROM THOMAS TWOMEY ABOUT THE FIXED GLASS WINDOW
 SYSTEMS ON WEST SIDE OF BUILDING IS SIGNED AND SEALED
 AND WAS SENT TO STORAGE. THE ELECTRICAL SHEET E001 IS
 NOT SIGNED AND SEALED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-11-18 Cont ID  
Sent By jleahy Date 2021-11-18 Time 14:44 Rev Time 0.00
Received By jleahy Date 2021-11-18 Time 14:43 Sent To  
Notes
2021-11-18 14:47:29ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS NOT SIGNED BY PERSON OF RECORD. DIGITAL PLAN
 SUBMISSION REQUIRES DIGITAL SIGNATURE THAT IS
 VERIFIABLE.