2016-09-12 10:57:23 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 16080940 |
| W. P. B. PERMIT: 16010466 |
| ADD: 2400 N FLAGLER DR. CURY PARK/ CITY PUMP/ LIFT |
| STATION ADDITION & RENOVATION/ ANTENNA TOWER & BASE |
| BLDG. RISK CATEGORY: IV/ 180 VULT/ MPH |
| CONT: FLORIDA DESIGN DRILLING CORP. |
| TEL: 561-844-2966 |
| E-MAIL: [email protected] |
| |
| THE CHAPTER 1 OF THE FLORIDA BUILDING CODE IS AN |
| ADMINISTRATIVE CODE. WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| REQUIRES 3 FLOOD ZONE CERTIFICATES, |
| |
| (1) WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS |
| 107.3.5.1.1 BUILDING |
| (1ST) SITE REQUIREMENTS- FLOOD HAZARD AREAS, FLOOD |
| ZONES, AND DESIGN FLOOD ELEVATIONS |
| |
| PLEASE NOTE THIS FLOOD ELEVATION CERTIFICATE IS |
| REQUIRED AS PART OF THE PLAN REVIEW REQUIREMENTS, THIS |
| IS A PROPOSED ELEVATION HEIGHTS AND MARKED ON THE |
| ELEVATION CERTIFICATE LINE C1. CONSTRUCTION DRAWINGS. |
| |
| (2ND) ELEVATION CERTIFICATE REQUIRED. 110.3 REQUIRED |
| INSPECTIONS. |
| A. BUILDING |
| 1. FOUNDATION |
| 1.2. IN FLOOD HAZARD AREAS, UPON PLACEMENT OF THE |
| LOWEST FLOOR, INCLUDING BASEMENT, |
| AND PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE |
| ELEVATION CERTIFICATION, REQUIRED IN |
| SECTION 1612.5, SHALL BE SUBMITTED TO THE BUILDING |
| OFFICIAL. |
| |
| ON 09/07/2016 A #114 INSPECTION WAS PASSED (SLAB) |
| DEPENDING ON WHAT SLAB WAS POURED THE 2ND ELEVATION |
| CERTIFICATE WOULD BE REQUIRED. |
| |
| (3RD ) ELEVATION CERTIFICATE REQUIRED. 110.3 110.6 |
| REQUIRED INSPECTIONS.FINAL. TO BE MADE AFTER THE |
| BUILDING IS COMPLETED AND READY FOR OCCUPANCY. |
| 6.1. LOWEST FLOOR ELEVATION. IN FLOOD HAZARD AREAS, AS |
| PART OF THE FINAL INSPECTION, A FINAL CERTIFICATION OF |
| THE LOWEST FLOOR ELEVATION SHALL BE SUBMITTED TO THE |
| AUTHORITY HAVING JURISDICTION. |
| PLEASE NOTE ON THE 3RD FLOOD ZONE CERTIFICATE SECTION |
| C2 LINE E AND SECTION D AND ATTACHED PHOTOS WILL BE |
| WHERE GENERATOR PADS, THE TOWER FOUNDATION INFORMATION |
| WILL NEED TO BE PLACED AND ELEVATIONS WHERE THE COAX |
| CABLE ENTERS THE BUILDING, THE HEIGHT OF THE ANTENNA |
| ETC... |
| |
| WITH THE ANTENNA COMING IN( AS A REVISION NOT A |
| SEPARATE PERMIT) WITH THE TOP OF THE FOUNDATION BELOW |
| THE BASE FLOOD, THIS I HAD A CONCERN ABOUT. TAKING IT |
| TO THE ASSISTANT BUILDING OFFICIAL DOUG HARVEY WAS OK |
| WITH THAT SINCE THE BOLTS, TOWER ARE MADE OF GALVANIZED |
| METAL. HE WAS CONCERNED THAT THE FLOOD ZONE CERTIFICATE |
| NEEDED TO SHOW THE COAX CABLE ENTERING ABOVE THE |
| REQUIRED 8 FEET NGVD. THIS SHOULD SHOW UP ON THE 3RD |
| REQUIRED ELEVATION CERTIFICATE UNDER THE SECTION C2 AND |
| SECTION D AND PHOTOS. |
| |
| A HOLD OR LOCK HAS BEEN PUT ON THE PERMIT 16010466 FOR |
| THE CERTIFICATE OF COMPLETION/ OR OCCUPANCY UNTIL THE |
| 3RD FLOOD ZONE CERTIFICATE IS RECEIVED, REVIEWED AND |
| APPROVED BY THE CITY. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |