Plan Review Details - Permit 16080940
Plan Review Stops For Permit 16080940
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-12 Cont ID  
Sent By jwitmer Date 2016-09-12 Time 10:56 Rev Time 0.00
Received By jwitmer Date 2016-09-12 Time 10:56 Sent To  
Notes
2016-09-12 10:57:23BUILDING PLAN REVIEW
 W. P. B. REVISION: 16080940
 W. P. B. PERMIT: 16010466
 ADD: 2400 N FLAGLER DR. CURY PARK/ CITY PUMP/ LIFT
 STATION ADDITION & RENOVATION/ ANTENNA TOWER & BASE
 BLDG. RISK CATEGORY: IV/ 180 VULT/ MPH
 CONT: FLORIDA DESIGN DRILLING CORP.
 TEL: 561-844-2966
 E-MAIL: [email protected]
  
 THE CHAPTER 1 OF THE FLORIDA BUILDING CODE IS AN
 ADMINISTRATIVE CODE. WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 REQUIRES 3 FLOOD ZONE CERTIFICATES,
  
 (1) WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1.1 BUILDING
 (1ST) SITE REQUIREMENTS- FLOOD HAZARD AREAS, FLOOD
 ZONES, AND DESIGN FLOOD ELEVATIONS
  
 PLEASE NOTE THIS FLOOD ELEVATION CERTIFICATE IS
 REQUIRED AS PART OF THE PLAN REVIEW REQUIREMENTS, THIS
 IS A PROPOSED ELEVATION HEIGHTS AND MARKED ON THE
 ELEVATION CERTIFICATE LINE C1. CONSTRUCTION DRAWINGS.
  
 (2ND) ELEVATION CERTIFICATE REQUIRED. 110.3 REQUIRED
 INSPECTIONS.
 A. BUILDING
 1. FOUNDATION
 1.2. IN FLOOD HAZARD AREAS, UPON PLACEMENT OF THE
 LOWEST FLOOR, INCLUDING BASEMENT,
 AND PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE
 ELEVATION CERTIFICATION, REQUIRED IN
 SECTION 1612.5, SHALL BE SUBMITTED TO THE BUILDING
 OFFICIAL.
  
 ON 09/07/2016 A #114 INSPECTION WAS PASSED (SLAB)
 DEPENDING ON WHAT SLAB WAS POURED THE 2ND ELEVATION
 CERTIFICATE WOULD BE REQUIRED.
  
 (3RD ) ELEVATION CERTIFICATE REQUIRED. 110.3 110.6
 REQUIRED INSPECTIONS.FINAL. TO BE MADE AFTER THE
 BUILDING IS COMPLETED AND READY FOR OCCUPANCY.
 6.1. LOWEST FLOOR ELEVATION. IN FLOOD HAZARD AREAS, AS
 PART OF THE FINAL INSPECTION, A FINAL CERTIFICATION OF
 THE LOWEST FLOOR ELEVATION SHALL BE SUBMITTED TO THE
 AUTHORITY HAVING JURISDICTION.
 PLEASE NOTE ON THE 3RD FLOOD ZONE CERTIFICATE SECTION
 C2 LINE E AND SECTION D AND ATTACHED PHOTOS WILL BE
 WHERE GENERATOR PADS, THE TOWER FOUNDATION INFORMATION
 WILL NEED TO BE PLACED AND ELEVATIONS WHERE THE COAX
 CABLE ENTERS THE BUILDING, THE HEIGHT OF THE ANTENNA
 ETC...
  
 WITH THE ANTENNA COMING IN( AS A REVISION NOT A
 SEPARATE PERMIT) WITH THE TOP OF THE FOUNDATION BELOW
 THE BASE FLOOD, THIS I HAD A CONCERN ABOUT. TAKING IT
 TO THE ASSISTANT BUILDING OFFICIAL DOUG HARVEY WAS OK
 WITH THAT SINCE THE BOLTS, TOWER ARE MADE OF GALVANIZED
 METAL. HE WAS CONCERNED THAT THE FLOOD ZONE CERTIFICATE
 NEEDED TO SHOW THE COAX CABLE ENTERING ABOVE THE
 REQUIRED 8 FEET NGVD. THIS SHOULD SHOW UP ON THE 3RD
 REQUIRED ELEVATION CERTIFICATE UNDER THE SECTION C2 AND
 SECTION D AND PHOTOS.
  
 A HOLD OR LOCK HAS BEEN PUT ON THE PERMIT 16010466 FOR
 THE CERTIFICATE OF COMPLETION/ OR OCCUPANCY UNTIL THE
 3RD FLOOD ZONE CERTIFICATE IS RECEIVED, REVIEWED AND
 APPROVED BY THE CITY.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-24 Cont ID  
Sent By jwitmer Date 2016-08-24 Time 08:37 Rev Time 0.00
Received By jwitmer Date 2016-08-24 Time 08:30 Sent To  
Notes
2016-08-24 08:32:33BUILDING PLAN REVIEW
 W. P. B. REVISION: 16080940
 W. P. B. PERMIT: 16010466
 ADD: 2400 N FLAGLER DR. CURY PARK/ CITY PUMP/ LIFT
 STATION ADDITION & RENOVATION/ ANTENNA TOWER & BASE
 BLDG. RISK CATEGORY: IV/ 180 VULT/ MPH
 CONT: FLORIDA DESIGN DRILLING CORP.
 TEL: 561-844-2966
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUG. 24/ 2016
 ACTION: DENIED
  
 1) THIS STRUCTURE IS IN AN A5 FLOOD ZONE, FBC BUILDING
 1612 AND CITY OF WPB CODE OF ORDINANCES SECTION 94-546.
 STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 PLEASE NOTE THE TOP OF THE BASE IS IN NGVD AND THE
 GROUND LEVEL NEXT TO THE BASE. THE OTHER CRITICAL
 INFORMATION THAT WILL NEED TO BE FILED OUT ON THE FLOOD
 ZONE CERTIFICATE IS WHAT ELEVATION (IN NGVD) THE
 ELECTRICAL EQUIPMENT ASSOCIATED WITH THE ANTENNA IS
 LOCATED.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-24 Cont ID  
Sent By jwitmer Date 2016-08-24 Time 08:37 Rev Time 0.00
Received By jwitmer Date 2016-08-22 Time 09:27 Sent To  
Notes
2016-08-23 09:27:30REVISION ROUTED TO JWITMER