Plan Review Details - Permit 16080904
Plan Review Stops For Permit 16080904
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-21 Cont ID  
Sent By mvaldes Date 2016-09-21 Time 17:27 Rev Time 0.00
Received By mvaldes Date 2016-09-21 Time 16:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-24 Cont ID  
Sent By skennedy Date 2016-08-24 Time 15:35 Rev Time 0.00
Received By mvaldes Date 2016-08-24 Time 15:00 Sent To  
Notes
2016-08-24 15:40:12REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] CLEARLY IDENTIFY THE SCOPE OF THE REVISION AND
 CLARIFY RACEWAY TYPES PLUS THE # OF CONDUCTORS IN
 CONDUIT ? FBC-107 MINIMUM PLAN REVIEW.
  
 2] ALL EXTERIOR DOORS LEADING TO OUTDOOR ENTRANCES AND
 EXITS SHALL HAVE A SWITCHED CONTROLLED LIGHTING OUTLET.
 NEC 210.70(2)(B)

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-21 Cont ID  
Sent By mvaldes Date 2016-09-21 Time 17:31 Rev Time 0.00
Received By mvaldes Date 2016-09-20 Time 09:00 Sent To  
Notes
2016-09-21 09:01:16RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-24 Cont ID  
Sent By mvaldes Date 2016-08-24 Time 15:35 Rev Time 0.00
Received By mvaldes Date 2016-08-22 Time 13:38 Sent To  
Notes
2016-08-22 13:39:01SKENNEDY DESK