Plan Review Details - Permit 16080850
Plan Review Stops For Permit 16080850
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-23 Cont ID  
Sent By cthroop Date 2016-09-23 Time 11:28 Rev Time 0.00
Received By cthroop Date 2016-09-23 Time 10:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-25 Cont ID  
Sent By cthroop Date 2016-08-25 Time 12:15 Rev Time 0.00
Received By cthroop Date 2016-08-25 Time 12:14 Sent To  
Notes
2016-08-25 13:22:19BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
  
 1. DESIGNER TO SIGN PLANS.
 2. PROVIDE DESIGN WIND LOADS FOR OPENINGS.
 3. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS.
 4. PROVIDE DEMENSIONS FOR WINDOW OPENINGS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW
 SUBMITTALS.
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2016-10-13 Cont ID  
Sent By mvaldes Date 2016-10-13 Time 17:31 Rev Time 0.00
Received By mvaldes Date 2016-10-13 Time 17:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-09-19 Cont ID  
Sent By cthroop Date 2016-09-23 Time 10:10 Rev Time 0.00
Received By mvaldes Date 2016-09-19 Time 17:46 Sent To B
Notes
2016-09-19 18:12:08REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1] PLEASE CLAIFY AND SHOW ELECTRICAL WORK BEING DONE !
 NO ELECTRICAL PLANS IN THE SUBMITTAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-24 Cont ID  
Sent By mvaldes Date 2016-08-24 Time 17:21 Rev Time 0.00
Received By mvaldes Date 2016-08-24 Time 16:53 Sent To B
Notes
2016-08-24 17:25:04REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1] FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 2] PLEASE CLAIFY AND SHOW ELECTRICAL WORK BEING DONE !

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-10-13 Cont ID  
Sent By mvaldes Date 2016-10-13 Time 17:32 Rev Time 0.00
Received By mvaldes Date 2016-10-04 Time 11:02 Sent To  
Notes
2016-10-05 11:03:04RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-23 Cont ID  
Sent By cthroop Date 2016-09-23 Time 10:10 Rev Time 0.00
Received By cthroop Date 2016-09-15 Time 14:35 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-25 Cont ID  
Sent By cthroop Date 2016-08-25 Time 12:14 Rev Time 0.00
Received By cthroop Date 2016-08-19 Time 09:49 Sent To  
Notes
2016-08-23 09:49:28ROUTED TO ELEC <5K