Plan Review Details - Permit 16080778
Plan Review Stops For Permit 16080778
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-13 Cont ID  
Sent By cthroop Date 2016-09-13 Time 08:22 Rev Time 0.00
Received By cthroop Date 2016-09-13 Time 08:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-26 Cont ID  
Sent By cthroop Date 2016-08-26 Time 12:12 Rev Time 0.00
Received By cthroop Date 2016-08-26 Time 12:12 Sent To E
Notes
2016-08-26 12:14:48BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
  
 1. VALUE APPEARS LOW. PROVIDE CONTRACT SIGNED BY OWNER.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY
 DELAY THE APPLICATION PROCESS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-14 Cont ID  
Sent By mvaldes Date 2016-09-14 Time 14:03 Rev Time 0.00
Received By mvaldes Date 2016-09-14 Time 14:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-29 Cont ID  
Sent By mvaldes Date 2016-08-29 Time 14:35 Rev Time 0.00
Received By mvaldes Date 2016-08-29 Time 14:33 Sent To  
Notes
2016-08-29 14:35:24REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] FBC-E SECTION C405.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH.
 LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
  
 2] PROVIDE AN OWNER SIGNED CONTRACT BECAUSE VALUE
 APPEARS TO BE LOW. FBC-109.3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-14 Cont ID  
Sent By mvaldes Date 2016-09-14 Time 14:03 Rev Time 0.00
Received By mvaldes Date 2016-09-02 Time 14:44 Sent To  
Notes
2016-09-02 14:44:22RESUB ROUTED TO KMARTIN VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-29 Cont ID  
Sent By mvaldes Date 2016-08-29 Time 14:36 Rev Time 0.00
Received By mvaldes Date 2016-08-18 Time 11:54 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-09-08 Cont ID  
Sent By   Date 2016-09-08 Time   Rev Time 0.00
Received By kmartin Date 2016-09-08 Time 09:09 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-08-23 Cont ID  
Sent By mvaldes Date 2016-08-29 Time 14:36 Rev Time 0.00
Received By kmartin Date 2016-08-23 Time 16:25 Sent To  
Notes
***NONE***