Plan Review Details - Permit 16080702
Plan Review Stops For Permit 16080702
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-13 Cont ID  
Sent By cthroop Date 2016-09-13 Time 09:15 Rev Time 0.00
Received By cthroop Date 2016-09-13 Time 09:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-23 Cont ID  
Sent By cthroop Date 2016-08-23 Time 08:51 Rev Time 0.00
Received By cthroop Date 2016-08-23 Time 08:51 Sent To  
Notes
2016-08-23 08:57:03BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 8/23/16
  
 1. CONFLICT BETWEEN VALUE OF CONTRACT $24,241 AND
 STATED VALUE ON APPLICATION $19,241. PLEASE RECONCILE.
 2. PROVIDE POOL BARRIER PER FBC R 4502.17.1
  
 [A] 109.3 BUILDING PERMIT VALUATIONS.
 THE APPLICANT FOR A PERMIT SHALL PROVIDE AN ESTIMATED
 PERMIT VALUE AT TIME OF APPLICATION. PERMIT VALUATIONS
 SHALL INCLUDE TOTAL VALUE OF WORK, INCLUDING MATERIALS
 AND LABOR, FOR WHICH THE PERMIT IS BEING ISSUED, SUCH
 AS ELECTRICAL, GAS, MECHANICAL, PLUMBING EQUIPMENT AND
 PERMANENT SYSTEMS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE VALUATION IS UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED ESTIMATES TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FINAL BUILDING
 PERMIT VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 R4502.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED WITH A BARRIER
 COMPLYING WITH SECTIONS R4501.17.1.1 THROUGH
 R4501.17.1.14.
  
 R4501.17.1.1
 THE TOP OF THE BARRIER SHALL BE AT LEAST 48 INCHES
 (1219 MM) ABOVE GRADE, MEASURED ON THE SIDE OF THE
 BARRIER WHICH FACES AWAY FROM THE SWIMMING POOL. THE
 MAXIMUM VERTICAL CLEARANCE BETWEEN GRADE AND THE BOTTOM
 OF THE BARRIER SHALL BE 2 INCHES (51 MM) MEASURED ON
 THE SIDE OF THE BARRIER WHICH FACES AWAY FROM THE
 SWIMMING POOL. WHERE THE TOP OF THE POOL STRUCTURE IS
 ABOVE GRADE, THE BARRIER MAY BE AT GROUND LEVEL OR
 MOUNTED ON TOP OF THE POOL STRUCTURE. WHERE THE BARRIER
 IS MOUNTED ON TOP OF THE POOL STRUCTURE, THE MAXIMUM
 VERTICAL CLEARANCE BETWEEN THE TOP OF THE POOL
 STRUCTURE AND THE BOTTOM OF THE BARRIER SHALL BE 4
 INCHES (102 MM).
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-12 Cont ID  
Sent By mvaldes Date 2016-09-12 Time 17:42 Rev Time 0.00
Received By mvaldes Date 2016-09-12 Time 17:38 Sent To B
Notes
2016-09-12 17:42:58ROUTED TO CT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-22 Cont ID  
Sent By mvaldes Date 2016-08-22 Time 17:39 Rev Time 0.00
Received By mvaldes Date 2016-08-22 Time 17:15 Sent To B
Notes
2016-08-22 17:43:43REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE A LIGHT DETAIL SHOWING BONDING OF THE LIGHT
 NICHE WITH # 8 SOLID COOPER CONDUCTOR AND IF PVC IS
 BEING INSTALLED A # 8 INSULATED EQUIPMENT GROUNDING
 CONDUCTOR MUST BOND THE FORMING SHELL UNLESS LISTED AS
 LOW VOLTAGE. NEC 680.23(B)(1)(2).

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-08-24 Cont ID  
Sent By tklarge Date 2016-08-24 Time 06:23 Rev Time 0.00
Received By tklarge Date 2016-08-24 Time 06:23 Sent To  
Notes
2016-08-24 06:23:38THERE IS NO GAS HEATER WITH THIS POOL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-13 Cont ID  
Sent By cthroop Date 2016-09-13 Time 09:11 Rev Time 0.00
Received By cthroop Date 2016-09-08 Time 12:46 Sent To  
Notes
2016-09-08 12:46:22RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-30 Cont ID  
Sent By rmcdouga Date 2016-08-30 Time   Rev Time 0.00
Received By rmcdouga Date 2016-08-17 Time 14:29 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-08-24 Cont ID  
Sent By tklarge Date 2016-08-24 Time 06:22 Rev Time 0.00
Received By tklarge Date 2016-08-24 Time 06:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-08-18 Cont ID  
Sent By rmcdouga Date 2016-08-30 Time 08:05 Rev Time 0.00
Received By njwira Date 2016-08-18 Time 08:29 Sent To E
Notes
2016-08-18 12:29:418/18/16- PASSED
  
 SF-14 SINGLE FAMILY LOW DENSITY RESIDENTIAL
 NO TREES TO BE REMOVED
 NOT A CORNER LOT
 SIDE SETBACK 5FT.6IN REQUIRED 5FT.
 REAR SETBACK IS MORE THAN 5FT.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442