Plan Review Details - Permit 16080691
Plan Review Stops For Permit 16080691
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-09-20 Cont ID  
Sent By shill Date 2016-09-20 Time 09:49 Rev Time 0.00
Received By shill Date 2016-09-20 Time 09:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-09-12 Cont ID  
Sent By shill Date 2016-09-12 Time 09:59 Rev Time 0.00
Received By shill Date 2016-09-12 Time 09:59 Sent To  
Notes
2016-09-12 09:59:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE BASE SHEET FASTENING FOR THE JOHNS MANVILLE
 MODIFIED DOES NOT APPEAR TO BE CORRECT, FBC 1609. SEE
 PERIMETER AND CORNER FASTENING; IT APPEARS THAT THE
 PERIMETER REQUIRES 4" FASTENING FOR 3 FIELD ROWS,
 CORNER ZONES REQUIRE 5". (IT APPEARS THAT THE WRONG
 COLUMN WAS UTILIZED WHEN SPECIFYING FASTENING;
 CALCULATIONS APPEAR CORRECT.)
  
 2. WHEN RESUBMITTING, PLEASE COLLATE THREE IDENTICAL
 COMPLETE SETS FOR PERMIT ISSUANCE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-18 Cont ID  
Sent By shill Date 2016-08-18 Time 11:31 Rev Time 0.00
Received By shill Date 2016-08-18 Time 11:31 Sent To  
Notes
2016-08-18 11:38:17****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. TWO SETS OF THE ROOF PLAN WERE SUBMITTED. THREE
 COMPLETE SETS REQUIRED, FBC 107.
  
 2. TWO SETS OF THE ROOF TILE PRODUCT APPROVAL AND
 ENGINEERING WERE SUBMITTED; THREE REQUIRED, FBC 107.
  
 3. THE ENGINEERING FOR THE ROOF TILE ATTACHMENT IS A
 PHOTOCOPY. FS471, DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED
 DATED ORIGINALS.
  
 4. SEE PRIOR CORRECTION LISTS. IF A REVIEW LETTER IS
 SUBMITTED IN LIEU OF AN INTIALED/DATED SHOP DRAWING
 REVIEW STAMP DIRECTLY ON THE SUBMITTAL, THE LETTER IS
 TO BE SIGNED AND SEALED (PER BUILDING OFFICIAL), FBC
 107.
  
 5. PRODUCT APPROVALS ARE TO BE REVIEWED BY THE DESIGNER
 OF RECORD PRIOR TO SUBMITTAL, FBC 107 (ROOF HATCH
 PRODUCT APPROVAL).
  
 6. THE ROOF HATCH PRODUCT APPROVAL IS ILLEGIBLE DUE TO
 THE SIZE. THE DRAWING SHEETS WERE PRINTED HALF SIZE
 (PORTRAIT ORIENTATION RATHER THAN LANDSCAPE). THIS
 DOCUMENT IS USED FOR PLAN REVIEW, INSPECTIONS, AND
 RETAINED AS A PART OF THE PERMIT RECORD FOREVER. A
 CLEAR LEGIBLE COPY IS REQUIRED, FBC 107.
  
 7. THE BASE SHEET CALCULATIONS ARE A PHOTOCOPY.
 DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED DATED ORIGINALS,
 FS471.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-12 Cont ID  
Sent By shill Date 2016-09-12 Time 10:01 Rev Time 0.00
Received By shill Date 2016-09-08 Time 14:37 Sent To  
Notes
2016-08-17 13:21:08SHILL'S DESK