Plan Review Details - Permit 16080659
Plan Review Stops For Permit 16080659
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-11-04 Cont ID  
Sent By jwitmer Date 2016-11-04 Time 16:53 Rev Time 0.00
Received By jwitmer Date 2016-11-04 Time 16:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-27 Cont ID  
Sent By jwitmer Date 2016-10-27 Time 09:26 Rev Time 0.00
Received By jwitmer Date 2016-10-27 Time 08:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-10 Cont ID  
Sent By jwitmer Date 2016-09-10 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2016-09-10 Time 06:56 Sent To  
Notes
2016-09-10 08:30:45BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080659 (NOT A REVISION)
 ADD: 324 DATURA STREET / SUITE :400
 CONT: GERARD CONTRACTING
 TEL: 561-373-3542
 E-MAIL: ??????????? PLEASE PROVIDE E-MAIL ADDRESS
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. SEPT.10/2016
 ACTION: DENIED
  
 1) THIS IS NOT A REVISION TO AN INTERIOR DEMOLITION
 PERMIT. BEFORE PERMIT ISSUANCE FILL OUT A PERMIT
 APPLICATION FORM AND PAY THE APPROPRIATE PERMIT FEES.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 105.1 PERMIT REQUIRED.
  
 2) THE COVER SHEET CS-1 LIST THIS BUILDING TYPE AS AN
 IB/ UNPROTECTED SPRINKLERED. SEE TABLE 601 FOR A TYPE
 IB BUILDING THE STRUCTURAL MEMBER ARE PROTECTED 2
 HOURS. TYPE IB/PROTECTED/ SPRINKLERED.
  
 3)SHEET A-1.0 PLEASE REVIEW GLAZING IN OFFICES
 102,103,104, 106, 107, 108, 109, 119, 120 & 121 ALL
 INDICATE GLASS WALLS. THERE ARE NO SECTIONS THRU A
 GLASS WALL INDICATING SEE THIS SECTION. PLEASE PROVIDE
 HOW CODE COMPLIANCE WILL BE ACCOMPLISHED EITHER USING
 CPSC CFR PART 1201 OR ANSI Z97.1 2406.2 IMPACT TEST.
  
 4) SHEET A-1.0 ALSO INDICATES DOOR TYPES A1 & B1 AS
 GLASS DOORS. PLEASE PROVIDE HOW CODE COMPLIANCE WILL BE
 ACCOMPLISHED EITHER USING CPSC CFR PART 1201 OR ANSI
 Z97.1 2406.2 IMPACT TEST.
  
 5) SHEET A-1 SHOWS IN THE LOWER LEFT CORNER A RESTROOM
 DETAIL WITH THE WATER CLOSET GRAB BARS MEASURED TO THE
 CENTER LINE. UNDER THE 2014 FBC-ACCESS. CODE 609.4.
 THE HEIGHT OF THE WATER CLOSET GRAB BAR IS MEASURED
 FROM THE TOP OF THE GRIPPING SURFACE TO THE FINISH
 FLOOR NOT THE MID LINE.
  
 6) SHEET A-1 THE ACCESSIBLE MIRROR IN THE RESTROOM IS
 SHOWN TO BE 40 INCHES TO THE BOTTOM OF THE MIRROR.
 PLEASE REVIEW THE 2014 FBC-ACCESS. CODE 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 7) PLEASE PROVIDE SIGNAGE SEE 2014 FBC-ACCESS. CODE ;
 216.3 DIRECTIONAL AND INFORMATIONAL SIGNS.
 216.4 MEANS OF EGRESS.
 703.1. SIGNS SHALL COMPLY WITH 703. WHERE BOTH VISUAL
 AND TACTILE CHARACTERS ARE REQUIRED, EITHER ONE SIGN
 WITH BOTH VISUAL AND TACTILE CHARACTERS, OR TWO
 SEPARATE SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE
 CHARACTERS, SHALL BE PROVIDED.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 9) A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-27 Cont ID  
Sent By albarran Date 2016-10-27 Time 21:20 Rev Time 0.00
Received By albarran Date 2016-10-27 Time 21:03 Sent To I
Notes
2016-10-27 21:21:23APPROVED ELECTRICAL REVIEW. INSPECTOR TO CHECK FOR
 COMPLIANCE WITH NEC 210.63

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-14 Cont ID  
Sent By albarran Date 2016-09-14 Time 18:50 Rev Time 0.00
Received By albarran Date 2016-09-14 Time 17:10 Sent To I
Notes
2016-09-14 18:51:511ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 324 DATURA STREET
 DESCRIPTION: INTERIOR REMODEL OF 4TH FLOOR
 MASTER PERMIT: 15011034
 REVISION # 16080659
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. NOTE THAT IT IS THE AMBIENT CONDITIONS WHICH
 DETERMINE CONDUCTOR INSULATION TYPE AND NOT THE WIRE
 GAUGE. ALL CONDUCTORS EXPOSED TO DAMP OR WET LOCATIONS
 SHALL BE LISTED ACCORDINGLY REGARDLESS OF GAUGE.
 CORRECT ELECTRICAL GENERAL NOTE #7 ACCORDINGLY.
 2. INDICATE ON THE RISER DIAGRAM WHAT IS EXISTING TO
 REMAIN VS. WHAT IS NEW.
 3. FBC-E405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1)
 4. NEC 210.63: A 125 VOLT, SINGLE-PHASE, 15 OR
 20-AMPERE-RATED RECEPTACLE OUTLET SHALL BE INSTALLED AT
 AN ACCESSIBLE LOCATION FOR THE SERVICING OF HVAC
 EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED WITHIN 25
 FT. OF THE EQUIPMENT. IN LIEU OF A ROOF PLAN YOU SHALL
 PROVIDE A DETAIL OF THE HVAC EQUIPMENT WITH ITS
 REQUIRED SERVICE OUTLET.
 5. FBC-EC405.2.2.3: DAYLIGHT ZONE CONTROL SHALL BE
 PROVIDED FOR THE: BREAK ROOM, TECH ROOM AND VARIOUS
 WORK AREAS.
 6. NEC 110.26(D): THE LIGHTING IN THE ELECTRIC ROOM
 CANNOT BE CONTROLLED AUTOMATICALLY.
 7. FBC-EC405.5.2 INTERIOR LIGHTING POWER ALLOWANCE. THE
 TOTAL INTERIOR POWER ALLOWANCE IS DETERMINED ACCORDING
 TO THE APPLICABLE TABLES AS INDICATED IN THIS SECTION.
 PROVIDE A LIGHT DENSITY ALLOWANCE CHART TO SHOW
 COMPLIANCE.
 8. ALL FIRE ALARM WORK TO BE CONDUCTED UNDER A SEPARATE
 PERMIT AND SUBMITTAL.
  
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-10-19 Cont ID  
Sent By pleduc Date 2016-10-19 Time   Rev Time 0.00
Received By pleduc Date 2016-10-19 Time 14:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-09-07 Cont ID  
Sent By pleduc Date 2016-09-07 Time   Rev Time 0.00
Received By pleduc Date 2016-09-07 Time 12:07 Sent To  
Notes
2016-09-07 12:56:38THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) SHEET LS 1 - THERE IS AN INCORRECT REFERENCE TO A
 FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 PLEASE ENSURE COMPLIANCE AND IF REVISIONS ARE SUBMITTED
 IN THE FUTURE PLEASE MAKE CLOUDED CORRECTIONS.
  
  
  
 2) SHEET E 3 - PLEASE ADD TO EXITS LIGHTS AT THE
 BATHROOMS FOYER FOR THE EGRESS TRAVLE PATH AS INDICATED
 ON LS 1.
  
 THE FIRE INSPECTOR WILL VERIFY AT THE TIME OF
 INSPECTION.
  
 IF REVISIONS ARE SUBMITTED IN THE FUTURE PLEASE MAKE
 CLOUDED CORRECTIONS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-11-04 Cont ID  
Sent By   Date 2016-11-04 Time   Rev Time 0.00
Received By lmarchan Date 2016-11-02 Time 13:27 Sent To  
Notes
2016-11-03 13:27:29RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-02 Cont ID  
Sent By ccole Date 2016-11-02 Time 08:31 Rev Time 0.00
Received By ccole Date 2016-10-31 Time 08:57 Sent To  
Notes
2016-11-01 08:57:21RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-27 Cont ID  
Sent By albarran Date 2016-10-27 Time 21:23 Rev Time 0.00
Received By albarran Date 2016-10-12 Time 11:58 Sent To  
Notes
2016-10-27 21:24:4910/27/16 ALL TRADES EXCEPT MECHANICAL APPROVED.
 CONTRACTOR NOTIFIED VIA EMAIL. FILE SENT TO LARGE
 DENIED DRAWER G. MA
2016-10-13 11:58:29C11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-14 Cont ID  
Sent By albarran Date 2016-09-14 Time 18:52 Rev Time 0.00
Received By albarran Date 2016-08-16 Time 14:38 Sent To  
Notes
2016-09-14 18:53:33FAILED MULTIPLE TRADE REVIEWS. CONTRACTOR NOTIFIED VIA
 EMAIL. FILE SENT TO LARGE DENIED DRAWER G. MA
2016-09-02 14:38:50C08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-09-10 Cont ID  
Sent By jwitmer Date 2016-09-10 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2016-09-10 Time 06:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-11-04 Cont ID  
Sent By ccole Date 2016-11-04 Time 14:19 Rev Time 0.00
Received By ccole Date 2016-11-04 Time 14:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-11-02 Cont ID  
Sent By ccole Date 2016-11-02 Time 08:31 Rev Time 0.00
Received By ccole Date 2016-11-02 Time 08:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-10-17 Cont ID  
Sent By ccole Date 2016-10-17 Time 16:53 Rev Time 0.00
Received By ccole Date 2016-10-17 Time 16:53 Sent To  
Notes
2016-10-17 17:31:332ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16080659
 10/17/16
  
 1) THE AC CALCULATIONS MUST BEAR THE SIGNATURE AND SEAL
 OF THE ENGINEER WHO PREPARED THEM- SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION, AND SECTION 61G15-23.002
 FAC.
  
 2) THE PLAN DOES NOT CLEARLY INDICATE HOW AIR WILL BE
 RETURNED TO THE RTU FROM THE TECH ROOM, THE WEST AND
 NORTH OFFICES, THE RECEPTION ROOM, THE WORK AREAS, AND
 CORRIDORS. PLEASE REFER TO SHEETS A-1.0 AND A-3.0: THE
 D WALL TYPE AND THE GLASS PARTITION AND HEADERS ARE
 SHOWN TO BE SPANNING FROM THE FLOOR TO THE STRUCTURE
 ABOVE. A) ADVISORY: PLEASE REFER TO SECTION 601.2:
 CORRIDORS SHALL NOT SERVE AS RETURN DUCTS.
  
 3) PROVIDE THE ROOF PLAN SHEET A1.1 SHOWN IN THE INDEX.
  
 4) THE ARCHITECT HAS REQUESTED THE ENGINEERING FOR
 INSTALLATION OF THE RTU, CURB ADAPTER, AND ROOF STAND
 BE DEFFERRED SUBMITTALS. PLEASE NOTE THAT THE
 ENGINEERING MUST BE SUBMITTED AND APPROVED PRIOR TO
 INSPECTION OF THE INSTALLATIONS.
  
 A) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 B) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-07 Cont ID  
Sent By ccole Date 2016-09-07 Time 16:49 Rev Time 0.00
Received By ccole Date 2016-09-07 Time 16:49 Sent To  
Notes
2016-09-07 17:02:161ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #16080659
 9/7/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH SECTUION C403.2.1 FBC-14 ENERGY
 CONSERVATION. THE SUMMARY CALCULATION ON SHEET M-1 IS
 INCOMPLETE.
  
 2) PROVIDE AN EQUIPMENT SCHEDULE FOR THE VAV BOXES, AND
 TYPICAL BOX INSTALLATION DETAILS.
  
 3) THE RTU, CONDENSER, AND ROOFTOP FAN EQUIPMENT
 MOUNTING DETAILS ARE INCOMPLETE. PLEASE PROVIDE THE
 WIND LOAD DESIGN CRITERIA AND COMPLETE ANCHORING AND
 FASTENING DETAILS- SECTION 301.15. SUBMIT A FL. PRODUCT
 APPROVAL OR MIAMI-DADE NOA FOR THE ROOF STAND.
  
 4) PROVIDE A CONDENSATE DISPOSAL PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-10-26 Cont ID  
Sent By gjohnson Date 2016-10-26 Time 14:23 Rev Time 0.00
Received By gjohnson Date 2016-10-26 Time 13:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-09-14 Cont ID  
Sent By tklarge Date 2016-09-14 Time 03:29 Rev Time 0.00
Received By tklarge Date 2016-09-14 Time 02:13 Sent To  
Notes
2016-09-14 02:40:081) SHT. A-1.0 - ELEV. "A" - .THE GRAB BARS SHALL BE
 MEASURED FROM THE FINISHED FLOOR TO THE TOP OF THE
 GRIPPING SURFACE, NOT TO THE CENTERLINE AS SHOWN. 2014
 FAC SEC. 609.4.
 2) SHT. A-1.0 - SHOW THE HEIGHT OF THE HANDICAPPED
 WATER CLOSET FROM THE FINISH FLOOR. COMPLY WITH 2014
 FAC SEC.604.4.
 3) THE LOCATION OF THE TOILET PAPER DISPENSER SHALL
 COMPLY WITH 2014 FAC SEC. 604.7.
 4) CLARIFY THE SCOPE OF WORK TO BE DONE IN THE GANG
 RESTROOMS #114 & #115..WPB AMEND. TO FBC SEC. 107.1.
 5)


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved