Plan Review Details - Permit 16080657
Plan Review Stops For Permit 16080657
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-06-21 Cont ID  
Sent By jwitmer Date 2017-06-21 Time 12:26 Rev Time 0.00
Received By jwitmer Date 2017-06-21 Time 11:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-12-01 Cont ID  
Sent By jwitmer Date 2016-12-01 Time 10:20 Rev Time 0.00
Received By jwitmer Date 2016-12-01 Time 10:20 Sent To  
Notes
2016-12-01 10:20:53BUILDING PLAN REVIEW
 W. P. B. REVISION: 16080657
 W. P. B. PERMIT: 14120431
 ADD: 312 23RD ST.
 CONT: BRADLEY CONSTRUCTION
 TEL: (727)641-2367
 E-MAIL: ???????????????????? PLEASE PROVIDE E-MAIL
 ADDRESS THAT IS HOW WE NOTIFY YOU!!!!!!
  
 PARK PALM BEACH MULTIFAMILY RESIDENTIAL
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
 3RD REVIEW
 DATE: THURS. DEC. 01/ 2016
 ACTION: DENIED
  
 1) REV. # 5 WAS SUBMITTED AND APPROVED BY BUILDING BUT
 NOT ALL TRADES. WHEN RESUBMITTED REV. # 6 WAS ALSO
 INCLUDED IN THIS REVIEW. REVISION # 6 SHOULD HAVE BEEN
 NOTED ON THE REVISION FORM, SINCE REVISION # 5 WAS NOT
 APPROVED BY ALL DISCIPLINES AND THE NEW SHEETS INSERTED
 IN THE PLANS, OLD ONES REMOVED AND MARKED VOID.
  
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.4
 QUALITY OF BUILDING PLANS. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT.
  
 2) FAIR HOUSING PLEASE REVIEW SHEET A-3.22. THE SWING
 OF THE SHOWER DOOR IN THE MASTER BATH, UNIT B3
 INFRINGES ON THE REQUIRED 30 X48 INCH CLEAR FLOOR SPACE
 PARALLEL TO THE SHOWER.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-11 Cont ID  
Sent By jwitmer Date 2016-10-11 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2016-10-11 Time 08:00 Sent To  
Notes
2016-10-11 08:30:18PASSED FAIR HOUSING GUIDELINE (2) USEABLE BATHROOMS
 (B)(VI).SHEET A-3.10.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-06 Cont ID  
Sent By jwitmer Date 2016-09-06 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2016-09-02 Time 14:17 Sent To  
Notes
2016-09-06 09:30:55BUILDING PLAN REVIEW
 W. P. B. REVISION: 16080657
 W. P. B. PERMIT: 14120431
 ADD: 312 23RD ST.
 PCN:74-43-43-10-19-003-0143
 CONT: BRADLEY CONSTRUCTION
 TEL: (727)641-2367
 E-MAIL: ???????????????
  
 PARK PALM BEACH MULTIFAMILY RESIDENTIAL
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
 1ST REVIEW
 DATE: FRI. SEPT. 02/ 2016
 ACTION: DENIED
  
 1) SHEET A-3.10 A SINGLE BEDROOM/ BATH UNIT. THE BATH
 MUST BE A SPECIFICATION A OR SPECIFICATION B, THIS
 DESIGN IS NEITHER AN A OR B SPECIFICATION. TO HAVE THE
 VALVES AS SHOWN YOU WOULD HAVE TO HAVE A 30X 48 INCH
 PARALLEL APPROACH WITH THE 48 INCHES STARTING AT THE
 CONTROL WALL AND PARALLELING THE TUB. THE WATER CLOSET
 IS IN THE WAY. THE WATER CLOSET WOULD NEED TO BE A
 MINIMUM OF 30 INCHES AWAY FROM THE TUB TO THE EDGE OF
 THE WATER CLOSET. THE ORIGINAL DESIGN THE FAIR HOSING
 GUIDELINES SHOW THE CONTROL VALVES ARE ON THE SAME WALL
 AS THE WATER CLOSET THIS CONFORMS TO THE SPECIFICATION
 A.
  
 THE DESIGN PROFESSIONAL IS REQUIRED TO DESIGNATE TO
 WHICH STANDARD THE UNIT BATHROOMS WERE DESIGNED.
 IF SPECIFICATION A IS SELECTED AS THE BASIS FOR
 DESIGNING A BATHROOM, ALL BATHROOMS IN THE DWELLING
 UNIT ALSO MUST COMPLY WITH THE A SPECIFICATION. IF
 SPECIFICATION B IS SELECTED, ONLY ONE BATHROOM IN THE
 DWELLING UNIT MUST MEET THOSE REQUIREMENTS: ALL OTHER
 BATHROOMS IN THE DWELLING UNIT MUST BE ON AN ACCESSIBLE
 ROUTE, DOORS HAVING A 32-INCH CLEAR OPENING.
  
 2A) SHEET A3.22 SHOWS A DWELLING UNIT WITH 2 BEDROOMS
 AND 2 BATHROOMS, ONE HAS A TUB THE OTHER A SHOWER. THE
 DESIGN PROFESSIONAL IS REQUIRED TO DESIGNATE TO WHICH
 STANDARD THE UNIT BATHROOMS WERE DESIGNED.
 IF SPECIFICATION A IS SELECTED AS THE BASIS FOR
 DESIGNING A BATHROOM, ALL BATHROOMS IN THE DWELLING
 UNIT ALSO MUST COMPLY WITH THE A SPECIFICATION. IF
 SPECIFICATION B IS SELECTED, ONLY ONE BATHROOM IN THE
 DWELLING UNIT MUST MEET THOSE REQUIREMENTS: ALL OTHER
 BATHROOMS IN THE DWELLING UNIT MUST BE ON AN ACCESSIBLE
 ROUTE, DOORS HAVING A 32-INCH CLEAR OPENING.
 IF THE DESIGNER INDICATES THAT BATHROOM # 2 IS DESIGNED
 AS THE SPECIFICATION B THEN THE REQUIREMENTS HAVE BEEN
 SATISFIED.
  
 2B) SHEET A3.22 DETAIL # 9 ONLY GIVE THE REQUIRED
 LOCATION FOR THE BACKING AND GRAB BAR FOR THE TOE END
 OF THE TUB. NOT THE BACK WALL NOR THE HEAD OF THE TUB.
 SEE EXAMPLE ?B? FAIR HOUSING.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-08-25 Cont ID  
Sent By vperez Date 2016-08-25 Time 08:39 Rev Time 0.00
Received By vperez Date 2016-08-25 Time 07:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-06-15 Cont ID  
Sent By wjolin Date 2017-06-15 Time 17:15 Rev Time 0.00
Received By wjolin Date 2017-06-15 Time 16:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-11-10 Cont ID  
Sent By wjolin Date 2016-11-10 Time 11:06 Rev Time 0.00
Received By wjolin Date 2016-11-10 Time 10:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-08-31 Cont ID  
Sent By wjolin Date 2016-08-31 Time 10:29 Rev Time 0.00
Received By wjolin Date 2016-08-31 Time 09:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-21 Cont ID  
Sent By tklarge Date 2017-06-21 Time 12:34 Rev Time 0.00
Received By tklarge Date 2017-06-09 Time 10:54 Sent To  
Notes
2017-06-12 10:55:13C21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-01 Cont ID  
Sent By   Date 2016-12-01 Time   Rev Time 0.00
Received By lmarchan Date 2016-11-01 Time 12:45 Sent To  
Notes
2016-11-01 12:45:49C21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-19 Cont ID  
Sent By jroach Date 2016-09-19 Time 11:37 Rev Time 0.00
Received By jroach Date 2016-08-16 Time 15:00 Sent To  
Notes
2016-08-16 15:00:40C21

Review Stop P PLUMBING
Rev No 5 Status P Date 2017-06-21 Cont ID  
Sent By tklarge Date 2017-06-21 Time 12:33 Rev Time 0.00
Received By tklarge Date 2017-06-21 Time 12:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2017-06-20 Cont ID  
Sent By tklarge Date 2017-06-20 Time 08:57 Rev Time 0.00
Received By gjohnson Date 2017-06-20 Time 08:36 Sent To  
Notes
2017-06-20 09:00:084TH REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENT 2ND REQUEST
  
 NOT COMPLIED 1) SHT. A-3.22 - THE SWING OF THE SHOWER
 DOOR IN THE MASTER BATH IN UNIT B3 INFRINGES ON THE
 REQUIRED 30 INCH BY 48 INCH CLEAR FLOOR SPACE PARALLEL
 TO THE SHOWER . CHANGING THE DOOR SWING WILL CORRECT
 THIS ISSUE.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-11-28 Cont ID  
Sent By tklarge Date 2016-11-28 Time 05:23 Rev Time 0.00
Received By tklarge Date 2016-11-28 Time 04:51 Sent To  
Notes
2016-11-28 05:22:161) SHT. A-3.22 - THE SWING OF THE SHOWER DOOR IN THE
 MASTER BATH IN UNIT B3 INFRINGES ON THE REQUIRED 30
 INCH BY 48 INCH CLEAR FLOOR SPACE PARALLEL TO THE
 SHOWER . CHANGING THE DOOR SWING WILL CORRECT THIS
 ISSUE.
 2) THE REVISED SHEETS A-0.00, A-0.01, A-3.10 & A-3.22
 SHALL BE SUBMITTED INTO THE FULL SET OF PLANS AND THE
 OLD PAGES REMOVED. 3RD REQUEST.

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-10-13 Cont ID  
Sent By tklarge Date 2016-10-13 Time 10:04 Rev Time 0.00
Received By tklarge Date 2016-10-13 Time 09:24 Sent To  
Notes
2016-10-13 09:46:511) THE DESIGN PROFESSIONAL IS REQUIRED TO DESIGNATE TO
 WHICH DESIGN SPECIFICATION ( A OR B) OF THE FAIR
 HOUSING ACT THE UNIT BATHROOMS WERE DESIGNED. 2ND
 REQUEST
 IF SPECIFICATION A IS SELECTED AS THE BASIS FOR
 DESIGNING A BATHROOM, ALL BATHROOMS IN THE DWELLING
 UNIT ALSO MUST COMPLY WITH THE A SPECIFICATION. IF
 SPECIFICATION B IS SELECTED, ONLY ONE BATHROOM IN THE
 DWELLING UNIT MUST MEET THOSE REQUIREMENTS: ALL OTHER
 BATHROOMS IN THE DWELLING UNIT MUST BE ON AN ACCESSIBLE
 ROUTE, DOORS HAVING A 32-INCH CLEAR OPENING.
 2A) SHEET A3.22 - UNIT B3 - SHOWS A DWELLING UNIT WITH
 2 BEDROOMS AND 2 BATHROOMS, ONE HAS A TUB THE OTHER A
 SHOWER. THE DESIGN PROFESSIONAL IS REQUIRED TO
 DESIGNATE TO WHICH DESIGN SPECIFICATION OF THE FAIR
 HOUSING ACT (A OR B) THE UNIT BATHROOMS WERE DESIGNED.
 IF SPECIFICATION A IS SELECTED AS THE BASIS FOR
 DESIGNING A BATHROOM, ALL BATHROOMS IN THE DWELLING
 UNIT ALSO MUST COMPLY WITH THE A SPECIFICATION. IF
 SPECIFICATION B IS SELECTED, ONLY ONE BATHROOM IN THE
 DWELLING UNIT MUST MEET THOSE REQUIREMENTS: ALL OTHER
 BATHROOMS IN THE DWELLING UNIT MUST BE ON AN ACCESSIBLE
 ROUTE, DOORS HAVING A 32-INCH CLEAR OPENING.
 3) SHT. A-3.10 & A-.21 - WATER SUPPLY VALVES FOR THE
 STACKED WASHER/DRYER UNIT SHALL BE ACCESSIBLE PER 2010
 FPC SEC.606.3. NOTE THIS ON THE PLAN.2ND REQUEST.
 4) SHT. A-3.41 - SHOW THE LENGTH AND WIDTH DIMENSIONS
 OF THE ACCESSIBLE TOILET ROOMS ON DETAILS #3 & #4. 2ND
 REQUEST.
 5)WHEN SUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-09-14 Cont ID  
Sent By tklarge Date 2016-09-14 Time 05:10 Rev Time 0.00
Received By tklarge Date 2016-09-14 Time 03:35 Sent To  
Notes
2016-09-14 03:38:24 
 PARK PALM BEACH MULTIFAMILY RESIDENTIAL
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
 1ST REVIEW
 DATE: 9/14/2016
 ACTION:DENIED
  
 1) SHEET A-3.10 - SINGLE BEDROOM/ BATH UNIT. THE BATH
 MUST BE A SPECIFICATION A OR SPECIFICATION B, THIS
 DESIGN IS NEITHER AN A OR B SPECIFICATION. TO HAVE THE
 VALVES AS SHOWN YOU WOULD HAVE TO HAVE A 30X 48 INCH
 PARALLEL APPROACH WITH THE 48 INCHES STARTING AT THE
 CONTROL WALL AND PARALLELING THE TUB. THE WATER CLOSET
 IS IN THE WAY. THE WATER CLOSET WOULD NEED TO BE A
 MINIMUM OF 30 INCHES AWAY FROM THE TUB TO THE EDGE OF
 THE WATER CLOSET. THE ORIGINAL DESIGN OF THE FAIR
 HOSING GUIDELINES SHOW THE CONTROL VALVES ARE ON THE
 SAME WALL AS THE WATER CLOSET. THIS CONFORMS TO THE
 SPECIFICATION A.
  
 THE DESIGN PROFESSIONAL IS REQUIRED TO DESIGNATE TO
 WHICH STANDARD THE UNIT BATHROOMS WERE DESIGNED.
 IF SPECIFICATION A IS SELECTED AS THE BASIS FOR
 DESIGNING A BATHROOM, ALL BATHROOMS IN THE DWELLING
 UNIT ALSO MUST COMPLY WITH THE A SPECIFICATION. IF
 SPECIFICATION B IS SELECTED, ONLY ONE BATHROOM IN THE
 DWELLING UNIT MUST MEET THOSE REQUIREMENTS: ALL OTHER
 BATHROOMS IN THE DWELLING UNIT MUST BE ON AN ACCESSIBLE
 ROUTE, DOORS HAVING A 32-INCH CLEAR OPENING.
  
 2A) SHEET A3.22 SHOWS A DWELLING UNIT WITH 2 BEDROOMS
 AND 2 BATHROOMS, ONE HAS A TUB THE OTHER A SHOWER. THE
 DESIGN PROFESSIONAL IS REQUIRED TO DESIGNATE TO WHICH
 STANDARD THE UNIT BATHROOMS WERE DESIGNED.
 IF SPECIFICATION A IS SELECTED AS THE BASIS FOR
 DESIGNING A BATHROOM, ALL BATHROOMS IN THE DWELLING
 UNIT ALSO MUST COMPLY WITH THE A SPECIFICATION. IF
 SPECIFICATION B IS SELECTED, ONLY ONE BATHROOM IN THE
 DWELLING UNIT MUST MEET THOSE REQUIREMENTS: ALL OTHER
 BATHROOMS IN THE DWELLING UNIT MUST BE ON AN ACCESSIBLE
 ROUTE, DOORS HAVING A 32-INCH CLEAR OPENING.
 IF THE DESIGNER INDICATES THAT BATHROOM # 2 IS DESIGNED
 AS THE SPECIFICATION B THEN THE REQUIREMENTS HAVE BEEN
 SATISFIED.
  
 2B) SHEET A3.22 DETAIL # 9 ONLY GIVE THE REQUIRED
 LOCATION FOR THE BACKING AND GRAB BAR FOR THE TOE END
 OF THE TUB. NOT THE BACK WALL NOR THE HEAD OF THE TUB.
 SEE FIGURE "4" FROM FAIR HOUSING REQS. IN 2010 FAC &
 ALSO 24 CFR 100.205.
  
 3) SHT. A-3.10 & A-.21 - WATER SUPPLY VALVES FOR THE
 STACKED WASHER/DRYER UNIT SHALL BE ACCESSIBLE PER 2010
 FPC SEC.606.3.
  
 4) SHT. A-3.41 - SHOW THE LENGTH AND WIDTH DIMENSIONS
 OF THE ACCESSIBLE TOILET ROOMS ON DETAILS #3 & #4.
  
 5)WHEN SUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-11-17 Cont ID  
Sent By jroach Date 2016-11-17 Time 14:20 Rev Time 0.00
Received By jroach Date 2016-11-17 Time 09:56 Sent To  
Notes
2016-11-17 14:20:36PROVISO
  
 ALL ZONING PROVISOS (DATED 6/15/15) AND SHOWN ON THE
 ORIGINALLY-PERMITTED PLANS REMAIN IN EFFECT.
  
  
 QUESTIONS/COMMENTS, CONTACT
 JOHN ROACH, PRINCIPAL PLANNER, AT
 [email protected] OR (561) 822-1448.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2016-09-19 Cont ID  
Sent By jroach Date 2016-09-19 Time 11:37 Rev Time 0.00
Received By jroach Date 2016-09-19 Time 11:37 Sent To  
Notes
2016-09-19 11:41:00PROVISO
  
 ALL ZONING PROVISOS (DATED 6/15/15) AND SHOWN ON THE
 ORIGINALLY-PERMITTED PLANS REMAIN IN EFFECT.
  
  
 QUESTIONS/COMMENTS, CONTACT
 JOHN ROACH, PRINCIPAL PLANNER, AT
 [email protected] OR (561) 822-1448.
  