Plan Review Details - Permit 16080618
Plan Review Stops For Permit 16080618
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-11-04 Cont ID  
Sent By jwitmer Date 2016-11-04 Time 16:27 Rev Time 0.00
Received By jwitmer Date 2016-11-04 Time 15:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-10-27 Cont ID  
Sent By jwitmer Date 2016-10-27 Time 08:41 Rev Time 0.00
Received By jwitmer Date 2016-10-27 Time 07:44 Sent To  
Notes
2016-10-27 08:41:01BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080618
 ADD: 625 N. FLAGLER DR. SUITE # 625
 CONT: VERDEX CONSTRUCTION
 TEL: 561-440-1600
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. OCT. 27/2016
 ACTION: DENIED
  
 1-3) SEMI-COMPLIED. ROOF STAND NOA 15-0902.05 SUBMITTED
 REVIEWED BY KAMM CONSULTING.
  
  
 4) 2ND REQUEST. PLEASE ALSO PROVIDE THE WIND DESIGN
 CRITERIA AND ASSOCIATED PRESSURES:
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 4.2. RISK CATEGORY.
  
 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 5) 2ND REQUEST. NONE OF THE TABLES WITHIN THE ROOF TOP
 PRODUCT APPROVAL HAVE BEEN IDENTIFIED. THE TABLES HAVE
 TO BE FILED OUT TO BE ABLE TO DETERMINE THE WIND
 PRESSURES DUE TO SURFACE AREA, STAND HEIGHT AND UNIT
 WITH AND TYPE OF ANCHOR TO THE ROOF SLAB OR FRAMING
 MEMBERS. PLEASE PROVIDE THE ATTACHMENT METHOD OF THE
 CONDENSOR UNIT TO THE ROOF TOP A/C STAND. ? 2014 FBC-M-
 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 6) THE NEW SHEET A1.11 IS NOT SIGNED NOR SEALED. PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 FL ADMIN CODE 61G16.003 ARCHITECTS
 PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE
 ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST
 AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC
 61G1-16.003
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-30 Cont ID  
Sent By jwitmer Date 2016-08-30 Time 09:54 Rev Time 0.00
Received By jwitmer Date 2016-08-30 Time 09:10 Sent To  
Notes
2016-08-30 09:54:19BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080618
 ADD: 625 N. FLAGLER DR. SUITE # 625
 CONT: VERDEX CONSTRUCTION
 TEL: 561-440-1600
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUG.30/2016
 ACTION: DENIED
  
 1) PLEASE SEE SHEET M2.1 INDICATES THE NEW MCU-1 TO BE
 INSTALLED ON THE ROOF ON A NEW ROOF RACK. PLEASE
 PROVIDE THE PRODUCT APPROVALS FOR THE NEW ROOF TOP A/C
 RACK.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS (CIRCLE THE STAND TO
 BE INSTALLED)
  
 2) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) SHOW COMPLIANCE WITH: 2014 FBC-B TABLE 1509.7
 CLEARANCE BELOW RAISED ROOF MOUNTED MECHANICAL UNITS.
  
 4) PLEASE ALSO PROVIDE THE WIND DESIGN CRITERIA AND
 ASSOCIATED PRESSURES:
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 4.2. RISK CATEGORY.
  
 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 5) PLEASE PROVIDE THE ATTACHMENT METHOD OF THE
 CONDENSOR UNIT TO THE ROOF TOP A/C STAND. ? 2014 FBC-M-
 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-18 Cont ID  
Sent By vperez Date 2016-10-18 Time 11:05 Rev Time 0.00
Received By vperez Date 2016-10-18 Time 11:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-25 Cont ID  
Sent By vperez Date 2016-08-25 Time 12:36 Rev Time 0.00
Received By vperez Date 2016-08-25 Time 12:36 Sent To  
Notes
2016-08-25 12:44:24INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS PHONE AND DATA, WIRELESS SYSTEMS, ETC. A NOTE
 WILL SUFFICE.
 2. AT THE LEAST 50% OF ALL 125-VOLT, 15- AND 20-AMPERE
 RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED WHERE
 INSTALLED IN PRIVATE OFFICES, OPEN OFFICES, AND
 COMPUTER CLASSROOMS. THIS INCLUDES THOSE INSTALLED IN
 MODULAR PARTITIONS. THERE ARE THREE ACCEPTABLE METHODS
 FOR CONTROLLING THE RECEPTACLES: A SCHEDULED
 TIME-OF-DAY CONTROL DEVICE THAT TURNS THE RECEPTACLES
 OFF AT SPECIFIC PROGRAMMED TIMES. A SEPARATE PROGRAMMED
 SCHEDULE IS REQUIRED FOR EACH FLOOR AND CANNOT EXCEED
 25,000 SQ.FT OF AREA. AN OCCUPANT SENSOR THAT TURNS THE
 RECEPTACLES OFF WITHIN 30-MINUTES OF ALL OCCUPANTS
 LEAVING A SPACE. A SIGNAL FROM ANOTHER CONTROL OR ALARM
 SYSTEM THAT INDICATES THE AREA IS NOT OCCUPIED AND
 FUNCTIONS TO TURN THE RECEPTACLES OFF. THERE ARE (2)
 EXCEPTIONS: RECEPTACLES SPECIFICALLY DESIGNATED FOR
 EQUIPMENT REQUIRING 24-HOUR OPERATION, AS DETERMINED BY
 THE AHJ. SPACES WHERE AN AUTOMATIC SHUTOFF WOULD
 ENDANGER THE SAFETY OR SECURITY OF THE ROOM OR BUILDING
 OCCUPANT(S), AS DETERMINED BY THE AHJ. SHOW COMPLIANCE.
 3. SHOW A RECEPTACLE AT THE A/C LOCATED ON ROOFTOOP TO
 BE WP/GFCI PROTECTED, AND ON PANEL SCHEDULE. NEC 210.63
 4. PROVIDE A NOTE TO COMPLY WITH NEC 450.13B HOLLOW
 SPACE INSTALLATION OF TRANSFORMER. PLEASE CLARIFY IF
 PANEL A IS IN RATED WALL CORRIDOR. PROVIDE NOTE TO
 MAINTAIN FIRE RATINGS.
 5. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-08-19 Cont ID  
Sent By wjolin Date 2016-08-19 Time 14:26 Rev Time 0.00
Received By wjolin Date 2016-08-19 Time 13:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-04 Cont ID  
Sent By jwitmer Date 2016-11-04 Time 16:27 Rev Time 0.00
Received By jwitmer Date 2016-10-28 Time 11:41 Sent To  
Notes
2016-10-31 12:34:32RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-27 Cont ID  
Sent By jwitmer Date 2016-10-27 Time 08:41 Rev Time 0.00
Received By jwitmer Date 2016-10-11 Time 10:33 Sent To  
Notes
2016-10-11 10:34:15C17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-14 Cont ID  
Sent By tklarge Date 2016-09-14 Time 05:39 Rev Time 0.00
Received By tklarge Date 2016-08-15 Time 10:32 Sent To  
Notes
2016-08-16 10:32:12C17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-08-30 Cont ID  
Sent By jwitmer Date 2016-08-30 Time 09:54 Rev Time 0.00
Received By jwitmer Date 2016-08-30 Time 09:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-11-01 Cont ID  
Sent By ccole Date 2016-11-01 Time 08:13 Rev Time 0.00
Received By ccole Date 2016-11-01 Time 07:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-10-14 Cont ID  
Sent By ccole Date 2016-10-14 Time 06:55 Rev Time 0.00
Received By ccole Date 2016-10-13 Time 17:51 Sent To  
Notes
2016-10-14 07:08:381ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16080618
 10/14/16
  
 1) SHEET M2.1: INDICATE THE TYPES AND SIZES OF THE MAIN
 SUPPLY AND RELOCATED BRANCH DUCTS SUPPLYING THE
 RELOCATED VAV BOXES.
  
 2) M2.1: INDICATE THE FLEX DUCT SIZES OR RELOCATE THE
 FLEX DUCT SCHEDULE FROM M6.1.
  
 3) NUMBER THE VAV BOXES AND PROVIDE AN EQUIPMENT
 SCHEDULE LISTING MAKES AND MODELS, AND COOLING,
 HEATING, AND CFM CAPACITIES.
  
 4) PROVIDE A DETAIL FOR INSTALLATION OF THE RELOCATED
 VAV BOXES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-24 Cont ID  
Sent By ccole Date 2016-08-24 Time 08:01 Rev Time 0.00
Received By ccole Date 2016-08-24 Time 08:01 Sent To  
Notes
2016-08-24 08:19:171ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #16080618
 8/24/16
  
 1) SUBMIT AC LOAD CALCULATIONS FOR THE NEW AC SYSTEMS-
 SECTION C403.2.1 FBC-14 ENERGY CONSERVATION,
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 3) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF THE NEW AC CONDENSERS.
  
 4) PROVIDE WIND LOAD ENGINEERING FOR ATTACHMENT OF THE
 CONDENSERS AND STANDS TO THE ROOF STRUCTURE- SECTION
 301.15. SUBMIT NOA # 13-1017.09 WITH REVIEW SIGNATURE
 BY THE EOR.
  
 5) PROVIDE INSTALLATION DETAILS FOR THE NEW AHU'S AND
 MMU.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-10-26 Cont ID  
Sent By gjohnson Date 2016-10-26 Time 13:33 Rev Time 0.00
Received By gjohnson Date 2016-10-26 Time 13:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-09-14 Cont ID  
Sent By tklarge Date 2016-09-14 Time 05:39 Rev Time 0.00
Received By tklarge Date 2016-09-14 Time 05:11 Sent To  
Notes
***NONE***