Plan Review Details - Permit 16080550
Plan Review Stops For Permit 16080550
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-17 Cont ID  
Sent By jwitmer Date 2016-10-17 Time 07:40 Rev Time 0.00
Received By jwitmer Date 2016-10-17 Time 07:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-17 Cont ID  
Sent By jwitmer Date 2016-08-17 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2016-08-17 Time 06:29 Sent To  
Notes
2016-08-17 07:01:17BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080550
 ADD: 1649 FORUM PLACE
 CONT: MERCURIO CONSTRUCTION
 TEL: 561-346-5147
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 17/ 2016
 ACTION: DENIED
  
 1) SHEET A1.01 & E1.01. EXIT LIGHTS NOR EMERGENCY
 LIGHTING NOT SHOWN ON THE ARCHITECTURAL FLOOR PLANS.
 SHEET E1 SHOWS BOTH THE EXIT LIGHTS AND EMERGENCY
 LIGHTING, HALL 102 & 106 DO NOT SHOW ANY EXIT
 DIRECTIONAL LIGHTS IN EITHER HALLWAY BETWEEN THE
 CORRIDOR DOORS.
 2014 FBC-B 1011.1 WHERE REQUIRED. EXITS AND EXIT ACCESS
 DOORS SHALL BE MARKED BY AN APPROVED EXIT SIGN READILY
 VISIBLE FROM ANY DIRECTION OF EGRESS TRAVEL. THE PATH
 OF EGRESS TRAVEL TO EXITS AND WITHIN EXITS SHALL BE
 MARKED BY READILY VISIBLE EXIT SIGNS TO CLEARLY
 INDICATE THE DIRECTION OF EGRESS TRAVEL IN CASES WHERE
 THE EXIT OR THE PATH OF EGRESS TRAVEL IS NOT
 IMMEDIATELY VISIBLE TO THE OCCUPANTS. INTERVENING MEANS
 OF EGRESS DOORS WITHIN EXITS SHALL BE MARKED BY EXIT
 SIGNS.
  
 2) SHEET A1.01. SIGNAGE (TACTILE) AT REAR DOOR
 INDICATES THE SIGNAGE SHALL BE PLACED ADJACENT TO THE
 LATCH SIDE OF THE DOOR 60 INCHES CENTERLINE A.F.F. NO
 MENTION OF THE REQUIREMENTS FOR BRAILLE SIGNAGE.
  
 2014 FBC-ACCESSIBILITY CODE 703.2 RAISED CHARACTERS.
 RAISED CHARACTERS SHALL COMPLY WITH 703.2 AND SHALL BE
 DUPLICATED IN BRAILLE COMPLYING WITH 703.3. RAISED
 CHARACTERS SHALL BE INSTALLED IN ACCORDANCE WITH 703.4.
  
 2014 FBC-ACCESSIBILITY CODE 703.4.1 HEIGHT ABOVE FINISH
 FLOOR OR GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE
 LOCATED 48 INCHES (1220 MM) MINIMUM ABOVE THE FINISH
 FLOOR OR GROUND SURFACE, MEASURED FROM THE BASELINE OF
 THE LOWEST TACTILE CHARACTER AND 60 INCHES (1525 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE,
 MEASURED FROM THE BASELINE OF THE HIGHEST TACTILE
 CHARACTER.
  
 3) THE SHEET A1.1 INDICATES THERE WILL BE A
 RECEPTIONIST BUT THERE IS NO DESK PLEASE NOTE
 COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE: 904.3.3
 CHECK WRITING SURFACES. WHERE PROVIDED, CHECK WRITING
 SURFACES SHALL COMPLY WITH 902.3.
 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28
 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-19 Cont ID  
Sent By mvaldes Date 2016-10-19 Time 12:14 Rev Time 0.00
Received By mvaldes Date 2016-10-19 Time 11:39 Sent To  
Notes
2016-10-19 11:54:32REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO'S:
  
 1] FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
  
 2] PER FBC-E SECTION C405.7 A MINIMUM OF 50% OF ALL
 125V, 15 & 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OR PEN OFFICES,
 COMPUTER CLASSROOMS, AND MODULAR PARTITIONS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-15 Cont ID  
Sent By mvaldes Date 2016-08-15 Time 16:00 Rev Time 0.00
Received By mvaldes Date 2016-08-15 Time 15:35 Sent To  
Notes
2016-08-15 16:08:34REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1) NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL
 BE FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT.
  
 2) FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES. ADD A NOTE !
  
 3) PROVIDE THE EXISTING ELECTRIC SERVICE RISER WITH
 WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL.
 COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW
 CIRCUITS ON FLOOR PLAN.
  
 4) PER FBC-E SECTION C405.7 A MINIMUM OF 50% OF ALL
 125V, 15 & 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OR PEN OFFICES,
 COMPUTER CLASSROOMS, AND MODULAR PARTITIONS. ADD A NOTE
 !
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-09-23 Cont ID  
Sent By wjolin Date 2016-09-23 Time 15:59 Rev Time 0.00
Received By wjolin Date 2016-09-23 Time 15:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-08-19 Cont ID  
Sent By wjolin Date 2016-08-19 Time 12:30 Rev Time 0.00
Received By wjolin Date 2016-08-19 Time 11:51 Sent To  
Notes
2016-08-19 12:30:52DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-11-15 Cont ID  
Sent By ccole Date 2016-11-15 Time 08:04 Rev Time 0.00
Received By ccole Date 2016-11-10 Time 09:45 Sent To  
Notes
2016-11-14 09:45:56RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-02 Cont ID  
Sent By ccole Date 2016-11-02 Time 17:27 Rev Time 0.00
Received By ccole Date 2016-11-01 Time 15:16 Sent To  
Notes
2016-11-02 15:16:12RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-19 Cont ID  
Sent By mvaldes Date 2016-10-19 Time 13:09 Rev Time 0.00
Received By mvaldes Date 2016-09-22 Time 12:47 Sent To  
Notes
2016-09-22 12:48:00B22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-23 Cont ID  
Sent By ccole Date 2016-08-23 Time 17:02 Rev Time 0.00
Received By ccole Date 2016-08-12 Time 12:56 Sent To  
Notes
2016-08-12 12:56:18B01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-08-17 Cont ID  
Sent By jwitmer Date 2016-08-17 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2016-08-17 Time 06:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-11-15 Cont ID  
Sent By ccole Date 2016-11-15 Time 08:04 Rev Time 0.00
Received By ccole Date 2016-11-15 Time 07:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-11-02 Cont ID  
Sent By ccole Date 2016-11-02 Time 17:14 Rev Time 0.00
Received By ccole Date 2016-11-02 Time 17:14 Sent To  
Notes
2016-11-02 17:18:293RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16080550
 11/2/16
  
 1) PROVIDE THE SIZE OF THE RETURN DUCT FROM THE WAITING
 AREA TO THE GRILL IN THE CORRIDOR, AND THE MAIN SUPPLY
 TRUNK SIZE.
  
 2) PLEASE NOTE THAT THE NEW MECHANICAL PLANS MUST BE
 INSERTED INTO THE APPROVED MAIN PLAN SETS WHICH SOMEONE
 HAS NOW WRITTEN "VOID" ON.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-09-29 Cont ID  
Sent By ccole Date 2016-09-29 Time 07:33 Rev Time 0.00
Received By ccole Date 2016-09-29 Time 07:33 Sent To  
Notes
2016-09-29 07:35:092ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16080550
 9/29/16
  
 1) 2ND REQUEST FOR MECHANICAL PLANS AND VENTILATION
 CALCULATIONS- SEE 1ST REVIEW COMMENT PRINTED BELOW:
  
 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #16080550
 8/23/16
  
 1) THE PLANS INDICATE A LEVEL 2 ALTERATION PER SECTION
 504.1 FBC-14 EXISTING BUILDING CODE. PLEASE PROVIDE
 MECHANICAL ALTERATION PLANS, AND MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES- SEE SECTION
 809.1 FBC-14 EXISTING BUILDING, AND TABLE 403.3 FBC-14
 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-23 Cont ID  
Sent By ccole Date 2016-08-23 Time 16:44 Rev Time 0.00
Received By ccole Date 2016-08-23 Time 16:44 Sent To  
Notes
2016-08-23 16:48:551ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #16080550
 8/23/16
  
 1) THE PLANS INDICATE A LEVEL 2 ALTERATION PER SECTION
 504.1 FBC-14 EXISTING BUILDING CODE. PLEASE PROVIDE
 MECHANICAL ALTERATION PLANS, AND MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES- SEE SECTION
 809.1 FBC-14 EXISTING BUILDING, AND TABLE 403.3 FBC-14
 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  