Plan Review Details - Permit 16080548
Plan Review Stops For Permit 16080548
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-29 Cont ID  
Sent By jwitmer Date 2016-10-29 Time 14:16 Rev Time 0.00
Received By jwitmer Date 2016-10-29 Time 13:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-08-30 Cont ID  
Sent By jwitmer Date 2016-08-30 Time 14:30 Rev Time 0.00
Received By jwitmer Date 2016-10-29 Time 13:46 Sent To  
Notes
2016-08-30 14:22:24BUILDING PROVISO;
 SHEET 039_A1.1.1E REVISION IS REQUIRED. DOOR 129A TO
 REVERSE SWING. FBC-B 1008.1.2 DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA
 CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS. J.
 WITMER 8/30/16

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-08-26 Cont ID  
Sent By vperez Date 2016-08-26 Time 06:12 Rev Time 0.00
Received By vperez Date 2016-08-25 Time 12:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-08-22 Cont ID  
Sent By scaldero Date 2016-08-22 Time 11:37 Rev Time 0.00
Received By scaldero Date 2016-08-22 Time 10:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-08 Cont ID  
Sent By cpuell Date 2016-11-08 Time 08:47 Rev Time 0.00
Received By cpuell Date 2016-10-24 Time 13:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-12 Cont ID  
Sent By cpuell Date 2016-09-12 Time 07:52 Rev Time 0.00
Received By cpuell Date 2016-08-18 Time 08:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-11-02 Cont ID  
Sent By ccole Date 2016-11-02 Time 14:03 Rev Time 0.00
Received By ccole Date 2016-11-02 Time 12:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-23 Cont ID  
Sent By ccole Date 2016-08-23 Time 09:38 Rev Time 0.00
Received By ccole Date 2016-08-23 Time 09:37 Sent To  
Notes
2016-08-23 09:39:331ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16080548
 8/23/16
  
 1) SUBMIT REVISED AC AND ENERGY CALCULATIONS INDICATING
 COMPLIANCE DATA FOR THE NEW MINI-SPLIT SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-11-07 Cont ID  
Sent By gjohnson Date 2016-11-07 Time 09:42 Rev Time 0.00
Received By gjohnson Date 2016-11-07 Time 09:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-09-10 Cont ID  
Sent By tklarge Date 2016-09-10 Time 07:22 Rev Time 0.00
Received By tklarge Date 2016-09-10 Time 05:12 Sent To  
Notes
2016-09-10 06:52:591) SHT. 077-A2.0 - DETAIL #5 - THE CAFE COUNTER SHALL
 BE A MAXIMUM OF 34 INCHES ABOVE THE FINISH FLOOR. FL.
 ACCESS CODE ACC. SEC. 212, 606.
 2)SHT. 077 - A2.0 - DETAIL #4 - THE 3 COMPARTMENT SINK
 SHOWN IN THE MEN'S RESTROOM SHALL COMPLY WITH FAC
 SEC.212.3, 213.3.4.
 3) A SAMPLING PORT IS REQUIRED ON THE DISCHARGE OUTLET
 OF THE OIL SEPARATOR FOR THE UTILITIES DEPT. TO SAMPLE
 THE EFFLUENT.
 4) SHT.203 - P2.1 - FLAT DRY VENTS ARE SHOWN ON THE OIL
 SEPARATOR. THE VENTS SHALL CONNECT ABOVE THE CENTERLINE
 OF THE DRAIN PIPE PER THE FPC SEC.905.3.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-11-08 Cont ID  
Sent By cpuell Date 2016-11-08 Time 09:43 Rev Time 0.00
Received By cpuell Date 2016-11-08 Time 09:43 Sent To  
Notes
2016-11-08 09:44:17ELEC PASSED SIGNATURES, EMAIL ATTACHED
2016-11-08 09:32:10DIGITAL SIGNATURES ON MECHANICAL SHEETS CHECKED AND
 VERIFIED/CCOLE
2016-11-07 09:44:1311/7/16 SIGNATURE ON PLUMBING SHEETS OK GPJ
2016-10-29 14:10:2810/29/2016 ARCHITECTURAL AND STRUCTURAL SHEETS REVIEWED
 FOR ELECTRONIC SIGNATURE. OK/ JW
2016-08-15 10:22:16DIGITALLY SIGNED SHEET 034 A1.1.1 - GROUND OVERALL
 FLOOR PLAN IS UNDER "SIGNATURES" IN PROJECTDOX

Review Stop Z ZONING
Rev No 2 Status P Date 2016-11-07 Cont ID  
Sent By eschneid Date 2016-11-07 Time 16:43 Rev Time 4.00
Received By eschneid Date 2016-11-01 Time 16:59 Sent To  
Notes
2016-11-07 16:43:59PASSED WITH PROVISOS
  
 A MINOR AMENDMENT IS REQUIRED FOR THE CHANGE TO THE
 SITE PLAN FOR THE RAMP AS WELL AS THE CHANGES TO THE
 INTERIOR LEVELS OF THE PARKING STRUCTURE AND THE
 ELEVATIONS. THE MINOR AMENDMENT SHALL BE SUBMITTED FOR
 REVIEW PRIOR TO THE C.O. FOR THE PORSCHE BUILDING.
 PLEASE REMEMBER THAT MASTER PERMIT 15120536 REQUIRED
 MINOR AMENDMENT REVISIONS THAT HAVE NOT YET BEEN
 SUBMITTED. THE NEW ADA RAMP SQUARE FOOTAGE SHALL BE
 INCLUDED ON THE MINOR AMENDMENT.

Review Stop Z ZONING
Rev No 1 Status F Date 2016-09-01 Cont ID  
Sent By eschneid Date 2016-09-01 Time 09:08 Rev Time 4.00
Received By eschneid Date 2016-08-25 Time 17:14 Sent To  
Notes
2016-09-01 09:12:27FAILED
  
 1) A MINOR AMENDMENT IS REQUIRED FOR THE CHANGE TO THE
 SITE PLAN FOR THE RAMP AS WELL AS THE CHANGES TO THE
 INTERIOR LEVELS OF THE PARKING STRUCTURE AND THE
 ELEVATIONS. THE MINOR AMENDMENT SHALL BE SUBMITTED FOR
 REVIEW PRIOR TO THE C.O. FOR THE PORSCHE BUILDING.
 PLEASE REMEMBER THAT MASTER PERMIT 15120536 REQUIRED
 MINOR AMENDMENT REVISIONS THAT HAVE NOT YET BEEN
 SUBMITTED. THE NEW ADA RAMP SQUARE FOOTAGE SHALL BE
 INCLUDED ON THE MINOR AMENDMENT.
  
 2) IT APPEARS THAT THERE IS SQUARE FOOTAGE BEING ADDED
 AS PART OF THIS PERMIT (OUTSIDE OF THE ADDITIONAL ADA
 RAMP). AN EXAMPLE IS THE OFFICE 135 AREA ON SHEET
 A1.1.1.1E. IF NEW SQUARE FOOTAGE IS BEING PROPOSED,
 PLEASE PROVIDE THE TOTAL SQUARE FOOTAGE FOR THE NEW
 DEALERSHIP BUILDINGS TO VERIFY THAT THE ADDITIONAL
 SQUARE FOOTAGE DOES NOT TRIGGER A MAJOR PLANNED
 DEVELOPMENT. NOTE: APPROVED SQUARE FOOTAGE IS AS
 FOLLOWS:
  
 BUILDING D - ENCLOSED AREA 27,364 SF AND SERVICE BAYS
 10,131 SF
 BUILDING E - ENCLOSED AREA 33,616 SF AND SERVICE BAYS
 16,503 SF
  
 3) STAFF CAN NOT APPROVE THIS PERMIT IF THERE IS AN
 ADDITION OF GREATER THAN FIVE PERCENT OF THE FLOOR AREA
 OR IF THE TRAFFIC TRIPS INCREASE.
  
 4) SHEETS A1.2.1, A1.3.1, A1.5.1, A1.6.1 AND A1.7.1
 (AND SHEETS A1.2.1 C AND D AND SHEETS A1.3.1C AND D AND
 SHEET A1.5.1C AND SHEET A1.6.1C) SHOW TWO LESS PARKING
 SPACES BASED ON THE NEW ELEVATOR AND VESTIBULE. PLEASE
 PROVIDE REVISED PARKING CALCULATIONS TO VERIFY THAT THE
 MINIMUM PARKING REQUIREMENTS ARE STILL BEING MET.
 PLEASE NOTE THAT IT APPEARS THAT THERE ARE COLUMNS IN A
 FEW SPACES ON THE EASTERN SIDE OF THE GARAGE ON EACH
 LEVEL. IF THESE ARE BEING COUNTED AS PART OF THE
 REQUIRED PARKING THEY WILL NEED TO BE MARKED AS COMPACT
 SPACES IF THEY ARE AT LEAST 16 FEET IN LENGTH, BUT NOT
 18 FEET IN LENGTH (NO DIMENSIONS PROVIDED). IF THEY DO
 NOT HAVE THIS MINIMUM DIMENSION, THEY MAY NOT BE
 COUNTED AS REQUIRED PARKING. THE OVERALL SITE PARKING
 DATA TABLE SHALL BE UPDATED TO REFLECT THE USE OF
 COMPACT PARKING SPACES AND THE REDUCED SPACES IN THE
 GARAGE. THE PARKING DATA TABLES ON SHEETS A1.2.1B,
 A1.2.1C, A1.2.1D, A1.3.1B, A1.3.1C, A1.3.1D, A1.5.1B,
 A1.5.1C, A1.5.1D, A1.6.1B, A1.6.1C, AND A1.6.1D DO NOT
 REFLECT THE PARKING COUNTS BASED ON THE NEW ELEVATOR.
  
 5) SHEETS A1.6.1, A1.7.1, AND A3.0 SHOW POLE MOUNTED
 LIGHTS ON THE ROOF FOR THE FIRST TIME. PLEASE NOTE THAT
 THE LIGHTS MAY ONLY EXCEED THE BUILDING HEIGHT BY 10
 PERCENT FOR A TOTAL LIGHT POLE, PLUS FIXTURE, HEIGHT OF
 85.8 FEET. SHEET A3.0 SHOWS THE LIGHT POLE EXCEEDING
 THE MAXIMUM HEIGHT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  