Plan Review Details - Permit 16080471
Plan Review Stops For Permit 16080471
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-11-23 Cont ID  
Sent By cthroop Date 2016-11-23 Time 10:52 Rev Time 0.00
Received By cthroop Date 2016-11-23 Time 10:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-07 Cont ID  
Sent By jwitmer Date 2016-09-07 Time 06:45 Rev Time 0.00
Received By jwitmer Date 2016-09-06 Time 10:01 Sent To  
Notes
2016-09-07 06:37:58BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080471
 ADD: 1451 S. OLIVE AVE.
 CONT: GILBANE BUILDING CO.
 TEL: 561-236-7052
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. SEPT. 07/2016
 ACTION: DENIED
  
 1) THE PERMIT APPLIED FOR IS FOR A STRUCTURAL VISUAL
 MOCK-UP WALL. THIS WALL TO BE REMOVED APPROXIMATELY
 AFTER 12 MONTHS OF COMPLETION. PLEASE CLARIFY 2 ITEMS
 PLEASE:
 1A) THE REMOVAL OF THE WALL AFTER 12 MONTHS OF
 COMPLETION OF THE OVERALL PROJECT OR THE COMPLETION OF
 THE MOCK UP WALL. 107.2.1.3.
  
 1B) THE PERMIT APPLIED FOR INDICATES THIS IS A
 STRUCTURE ONLY PERMIT. THE 2ND CONCERN IS THERE GOING
 TO BE COMPONENTS AND CLADDING COVERING THIS STRUCTURE.
 THERE ARE NO ARCHITECTURAL SHEETS SHOWING THE
 ELEVATIONS AND WHAT THE FINISH PRODUCT IS TO LOOK LIKE.
 2014 FBC-B 1403.2 WEATHER PROTECTION. EXTERIOR WALLS
 SHALL PROVIDE THE BUILDING WITH A WEATHER-RESISTANT
 EXTERIOR WALL ENVELOPE. THE EXTERIOR WALL ENVELOPE
 SHALL INCLUDE FLASHING, AS DESCRIBED IN SECTION 1405.4.
 THE EXTERIOR WALL ENVELOPE SHALL BE DESIGNED AND
 CONSTRUCTED IN SUCH A MANNER AS TO PREVENT THE
 ACCUMULATION OF WATER WITHIN THE WALL ASSEMBLY BY
 PROVIDING A WATER-RESISTIVE BARRIER BEHIND THE EXTERIOR
 VENEER, AS DESCRIBED IN SECTION 1404.2, AND A MEANS FOR
 DRAINING WATER THAT ENTERS THE ASSEMBLY TO THE
 EXTERIOR. PROTECTION AGAINST CONDENSATION IN THE
 EXTERIOR WALL ASSEMBLY SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTION 1405.3.
  
 2014 FBC-B 1609.6.4.4.1 COMPONENTS AND CLADDING.
 WIND PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS
 APPLIED AS FOLLOWS USINGCNET VALUES BASED ON THE
 EFFECTIVE WIND AREA, A, CONTAINED WITHIN THE ZONES IN
 AREAS OF DISCONTINUITY OF WIDTH AND/OR LENGTH ?A,? ?2A?
 OR ?4A? AT: CORNERS OF ROOFS AND WALLS; EDGE STRIPS FOR
 RIDGES, RAKES AND EAVES; OR FIELD AREAS ON WALLS OR
 ROOFS AS INDICATED IN FIGURES IN TABLES IN ASCE 7 AS
 REFERENCED IN TABLE 1609.6.2
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-23 Cont ID  
Sent By cthroop Date 2016-11-23 Time 10:51 Rev Time 0.00
Received By cthroop Date 2016-11-17 Time 16:50 Sent To Z
Notes
2016-11-17 16:53:24TO JROACH

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-07 Cont ID  
Sent By jwitmer Date 2016-09-07 Time 06:45 Rev Time 0.00
Received By jwitmer Date 2016-08-18 Time 13:21 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-11-21 Cont ID  
Sent By cthroop Date 2016-11-23 Time 10:51 Rev Time 0.00
Received By jroach Date 2016-11-21 Time 16:02 Sent To  
Notes
2016-11-21 16:02:20PROVISO
  
 1. A TREE ALTERATION PERMIT SHALL BE ISSUED PRIOR TO
 THE REMOVAL/RELOCATION OF ANY TREES.
  
 2. THE STRUCTURAL MOCK-UP WILL BE REQUIRED TO BE
 REMOVED PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY FOR THE MUSEUM EXPANSION.
  
 QUESTIONS/COMMENTS, CONTACT
 JOHN ROACH, PRINCIPAL PLANNER, AT
 [email protected] OR (561) 822-1448
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-09-02 Cont ID  
Sent By jwitmer Date 2016-09-07 Time 06:38 Rev Time 0.00
Received By jroach Date 2016-08-19 Time 16:35 Sent To B
Notes
2016-09-02 10:38:34ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 09.02.2016
 PERMIT NO.: 16080471
 ADDRESS: 1451 S. OLIVE AVENUE
 CONTRACTOR/CONTACT: MICHAEL IZZO
 TELEPHONE NO.: 561.236.7052
 SCOPE OF REVIEW: STRUCTURAL MOCK-UP
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO SECTION 94.203 OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS, THE STRUCTURE SHALL BE A
 MINIMUM OF 25 FEET FROM THE PROPERTY LINE.
  
 PLEASE NOTE THE FOLLOWING:
  
 1. A TREE ALTERATION PERMIT SHALL BE ISSUED PRIOR TO
 THE REMOVAL/RELOCATION OF ANY TREES.
  
 2. THE STRUCTURAL MOCK-UP WILL BE REQUIRED TO BE
 REMOVED PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY FOR THE MUSEUM EXPANSION/RENOVATIONS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved